manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Teledata
  6. •
  7. Security Sensor
  8. •
  9. Teledata SF3500 User manual

Teledata SF3500 User manual

SF3500
ANALOGUE CLASS P THERMAL DETECTOR
GENERAL DESCRIPTION
This type of detector (figure 1) continuously samples the temperature variation in the protected area to provide the earliest warning of
fire and yet offers a high level of false alarm rejection.
The digital communication protocol employed by the monitoring control panel provides high rates of information exchange in combi-
nation with comprehensive features that ensure fast and secure responses.
These detectors are designed for open area protection and must only be connected to control panels that use the proprietary ana-
logue-intelligent addressable communication protocol for monitoring and control.
The centrally positioned three-colour LED indicator (red, green and amber) provides 360° visibility and thus does not require any
orientation during installation.
An in-built magnet test allows easy activation to verify correct functioning of the detectors on site.
SHORT CIRCUIT ISOLATOR
All standard series devices are provided with short-circuit monitoring isolators on the intelligent loop’s line and can be activated by
the control panel.
Note: Before installing this device please thoroughly read this leaflet and refer to the applicable European Standards and National
Codes of Practice (e.g. BS5839-1:2002 for UK) for guidance on location, spacing and acceptable use. Also seek guidance from the
compatible control panel instructions to ensure appropriate design criteria and configuration specifications are followed.
Figure 1 - View of the detector on its base.
*Product operates down to 15 V, but without LED indication.
TECHNICAL SPECIFICATIONS
Power supply *from 18 V (min) to 40 V (max)
Average standby current consumption 55 uA @ 24 V
Remote output max current consumption
(externally limited) 20 mA
Operating temperature range -30 °C / +70 °C (no icing)
Humidity 95% RH (no condensation)
Height (standard base included) 54 mm
Diameter 110 mm
Weight (standard base included) 130 g
INSTALLATION
This heat detector must be used in combination with compatible control panels employing the communication protocol. The location
of detectors should follow recognised national or international application codes of practice.
The detector may be mounted on any of the following bases:
adaptor base / deep adaptor base
Universal adaptor base / deep adaptor base
adaptor base with shorting clip / deep adaptor base with shorting clip
Universal adaptor base with shorting clip / deep adaptor base with shorting clip
Bases supplied with a metal shorting clip installed between the two negative terminals allow more flexibility when connecting detec-
tors to the loop and permits the continuity of the loop cabling to be tested after installation and prior to the detectors being fitted.
Care must be taken to ensure that the shorting clip is either cut or removed prior to system commissioning!
Connections to the base terminals are polarity sensitive thus please check by referring to the wiring diagram in figures 2, 3,
4 and 5!
REMOTE OUTPUT CAPABILITY
Remote output capability is available as a standard feature so a remote indication lamp or a compatible platform sounder (check
power requirements) may be wired to the base terminals.
If other equipment is connected to the remote output, its supply current must be eventually limited by using an adequate
resistor. Consult the TECHNICAL SPECIFICATIONS table and assess the external device current absorption’s value.
Figure 2 - adaptor base and deep adaptor base loop wiring.
Figure 3 - Universal adaptor base and deep adaptor base loop
wiring.
Figure 4 - adaptor base with shorting clip and deep adaptor base
with shorting clip loop wiring.
Figure 5 - Universal adaptor base with shorting clip and deep
adaptor base with shorting clip loop wiring.
TELEDATA S.R.L. - Via Giulietti 8a, 20132, Milan, Italy www.Teledata-i.com L20-V350X-4001 (v2.3)
Heat test
Use a hair dryer of 1000-1500 W or an heat tool from an approved manufacturer. Direct the heat towards the sensor from its side.
Hold the heat source at about 15 cm away from the sensor in order to prevent damage to its cover during testing.
The detector should trigger an alarm message to the control panel, and, successively, the detector’s red LED should be activated
by the control panel itself.
SETTING THE ADDRESS
Detectors can be addressed using a special hand-held programming unit or they can be auto-addressed by the control panel after
they have been installed (the implementation of the auto-addressing feature depends on the control panel’s manufacturer).
Addresses may be selected from a range from 1 to 240, although, of course, each device on the loop must have a unique address.
CAUTION
Dust covers help to protect the devices
during shipping and when first installed.
They are not intended to provide complete
protection against contamination, therefore,
detectors should be removed before con-
struction, major re-decoration or other dust
producing work is started. DUST COVERS
MUST BE REMOVED BEFORE THE SYSTEM
CAN BE MADE OPERATIONAL.
WARNING
Disconnect loop power before installing the
detector.
5. When the detector is firmly engaged verify the alignment
between the detector and the raised reference marks on the
base (figure 7).
6. After all detectors and other loop devices have been
installed, apply power to the loop in accordance with the
control panel’s installation instructions.
7. Test the detectors as described in the section headed
“TESTING”.
1. Position the detector centrally
on its mounting base (ensure it is
level).
2. Rotate clockwise applying
gentle pressure. The detector will
drop into its keyed location.
3. Press more firmly to win the
force of the contacts.
4. Continue to rotate clockwise a
few degrees until the detector has
fully engaged in the mounting
base.
ANTI-TAMPER MECHANICAL BLOCK FEATURE
The detector may be locked onto its base by remov-
ing the small plastic element on the base’s detector
blocking hook by using a suitable tool (e.g. a small
screwdriver) inserted through the access hole on
the side of the mounting base (figure 6).
To remove the detector from the base, if mechani-
cally blocked, insert a suitable tool (e.g. a small
screwdriver) through the access hole on the side of
the mounting base (figure 6).
Figure 6 - The anti-tamper block and its handling.
TAMPER DETECTION
A fault condition is triggered on the protocol compatible control panel if a detector, on the loop, is removed from its mounting base.
TESTING
Detectors should be tested after installation and during periodic maintenance visits (it is recommended each device should be tested
at least once per year). When the system has been reset, allow, after each test, at least one minute for power stabilisation before the
next test. Detectors can be tested as follows:
Magnet test
Position the magnet (model TMD-01, optional) next to the detector, between the two raised marks on the base (figure 7). The magnet
test simulates heat on the thermistor and verifies the function of all electronic circuits of the detector and its communication with the
control panel. The detector should trigger an alarm message to the control panel, and, successively, the detector’s red LED should
be activated by the control panel itself.
If the detector does not respond to the tests correctly it may be necessary to clean it: in this case follow the instructions indicated in
the “MAINTENANCE” paragraph.
If testing fails again after maintenance then replace the detector with a new one and return the faulty one for servicing.
Alignment between the detector and
the base’s reference raised marks.
Figure 7 - The correctly installed detector.
Magnet test position (model TMD-01).
MAINTENANCE
Before starting any maintenance work, isolate and disable the system in order to avoid accidental and unwanted alarm or fault condi-
tions. Remove the detector from its mounting base to allow inspection in good light at ground level. Inspect the thermistor area; use a
small, soft bristle brush to dislodge any evident contaminants such as insects, spider webs, hairs, etc. Use a small vacuum tube or
clean, dry and compressed air to suck up or blow away any remaining small particles from the thermistor area.
Wipe the exterior housing of the detector with a clean, damp, lint free cloth to remove any surface film that can later attract airborne
contaminants. After all detectors have been inspected, repositioned on their mounting bases and power has been re-applied, check
correct operation as described under the “TESTING” paragraph.
WARNINGS AND LIMITATIONS
Our devices use high quality electronic components and plastic materials that are highly resistant to
environmental deterioration. However, after 10 years of continuous operation, it is advisable to replace the
devices in order to minimize the risk of reduced performance caused by external factors. Ensure that this
device is only used with compatible control panels. Detection systems must be checked, serviced and
maintained on a regular basis to confirm correct operation.
Smoke sensors may respond differently to various kinds of smoke particles, thus application advice
should be sought for special risks. Sensors cannot respond correctly if barriers exist between them and
the fire location and may be affected by special environmental conditions.
Refer to and follow national codes of practice and other internationally recognized fire engineering stan-
dards.
Appropriate risk assessment should be carried out initially to determine correct design criteria and up-
dated periodically.
WARRANTY
All devices are supplied with the benefit of a limited 3 year warranty relating to faulty materials or manu-
facturing defects, effective from the production date indicated on each product.
This warranty is invalidated by mechanical or electrical damage caused in the field by incorrect handling
or usage.
Product must be returned via your authorized supplier for repair or replacement together with full informa-
tion on any problem identified.
Full details on our warranty and product’s returns policy can be obtained upon request.
TELEDATA S.R.L.
Via Giulietti, 8
20132, Milano
Italy
EN 54-5
Point type heat detector
Class A1R and B (class P)
EN 54-17:2005
Short circuit isolator
SF3500
Technical data: see docu-
ment
TDS-V350X held by the
manufacturer.
TELEDATA S.R.L. - Via Giulietti 8a, 20132, Milan, Italy www.Teledata-i.com L20-V350X-4001 (v2.3)

Other Teledata Security Sensor manuals

Teledata SF1000E User manual

Teledata

Teledata SF1000E User manual

Teledata SF3500E User manual

Teledata

Teledata SF3500E User manual

Teledata SWF1000 User manual

Teledata

Teledata SWF1000 User manual

Teledata SWF2000 User manual

Teledata

Teledata SWF2000 User manual

Teledata SF1000 User manual

Teledata

Teledata SF1000 User manual

Teledata SF2000E User manual

Teledata

Teledata SF2000E User manual

Teledata SF2000 User manual

Teledata

Teledata SF2000 User manual

Popular Security Sensor manuals by other brands

Inovelli NZW1201 quick start guide

Inovelli

Inovelli NZW1201 quick start guide

Honeywell Midas quick start guide

Honeywell

Honeywell Midas quick start guide

Satel OPAL Pro manual

Satel

Satel OPAL Pro manual

LEGRAND 0 488 94 manual

LEGRAND

LEGRAND 0 488 94 manual

Elsema MD2010 manual

Elsema

Elsema MD2010 manual

DANLERS SILVAIR MESH-HBWD DALI quick start guide

DANLERS

DANLERS SILVAIR MESH-HBWD DALI quick start guide

Meiji MSD-01 instruction manual

Meiji

Meiji MSD-01 instruction manual

AMC DT15 Installation

AMC

AMC DT15 Installation

PCB Piezotronics 117B221 Installation and operating manual

PCB Piezotronics

PCB Piezotronics 117B221 Installation and operating manual

GJD D-TECT 50 IP manual

GJD

GJD D-TECT 50 IP manual

Renkforce 1034032 operating instructions

Renkforce

Renkforce 1034032 operating instructions

Tecnoalarm DUALRED quick start guide

Tecnoalarm

Tecnoalarm DUALRED quick start guide

System Sensor B110RLP Installation and maintenance instructions

System Sensor

System Sensor B110RLP Installation and maintenance instructions

Tecnosystemi Toolsplit TSCE-500 user manual

Tecnosystemi

Tecnosystemi Toolsplit TSCE-500 user manual

Endress+Hauser NAR 300 operating instructions

Endress+Hauser

Endress+Hauser NAR 300 operating instructions

Optex CX-702S installation instructions

Optex

Optex CX-702S installation instructions

TOOLCRAFT 2331524 operating instructions

TOOLCRAFT

TOOLCRAFT 2331524 operating instructions

Jaycar QC-3506 user manual

Jaycar

Jaycar QC-3506 user manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.