Fig. 6
When a remote indicator connects with a few of
detectors, a diode 1N5819 needs connecting with
Terminal 4 of the orientation base in series and with
anode of the remote indicator. Either DB-01 or
DB-01D is used depends on which GST-EOL-9307
Active End of Line Unit or 4.7KΩterminal resistor is
connected. The system composition is shown in
Fig.7.
Fig. 7
Output loop of addressable zone monitor unit (the
unit) can be connected with up to 15 conventional
field devices. The unit has the function of checking
loop breakage. When the output is broken, the unit
transmits this fault signal to fire alarm control panel.
When any field device in the output loop is removed,
the unit alarms fault. If an AEOL is connected, it will
not affect the normal operation of other field devices.
Maintenance
1. The detector should be installed just before
commission and kept well before installation, taken
corresponding measures for dust-proof, damp-proof
and corrosion-proof.
2. The dust cover cannot be removed until the project
has been plunged into usage. Otherwise it can’t alarm
normally.
3. Clean the detector at least once a year to ensure
normal operation of the system.
4. Before cleaning, notify the proper authorities that
the system is undergoing maintenance and will
temporarily be out of service. Disable the zone or
system undergoing maintenance to avoid unwanted
alarms.
5. The detector should be tested again after cleaning
and re-installing.
6. The detector should be tested again after cleaning
and reinstallation.
7. Protect the metal component on the PCB against
damp and improper distortion.
8. Fire simulation test should be made to the detector
at least once half a year.
Specification
Operating Voltage 8.5VDC~28VDC
Standby Current ≤60μA
Alarm Current 10mA≤I≤30mA
Fire LED Red. Flashes periodically
(2s~4s) in polling; illuminates
in alarming.
Remote indication
output
Directly connecting with
remote indicator (built in 2k
resistor in series, output
voltage is 5V); don’t illuminate
when in polling; illuminate in
alarming.
Maximum Ripple
Voltage
2V ( peak-to-peak)
Alarm Reset Instantaneous Cut out (2s
Min, 2.5VDCMax.)
Power-up Time ≤10s
Action Temperature 58℃
Response Velocity 3℃/min
Wiring Two-wire, polarity-sensitive
Ingress protection
Rating
IP22
Ambient
Temperature
-10℃~+50℃
Relative Humidity ≤95%, non condensing
Material and Color
of Enclosure
ABS, white (RAL 9016)
Dimensions Diameter: 100mm
High: 41.8mm (without base)
Mounting Hole
Spacing
45mm~75mm
Weight About 120g
Accessories and Tools
Module Name Remarks
DB-01 Orientation base Supplied separately
DB-01D Orientation base Supplied separately
Limited Warranty
GST warrants that the product will be free from defects
in design, materials and workmanship during the
warranty period. This warranty shall not apply to any
product that is found to have been improperly installed
or used in any way not in accordance with the
instructions supplied with the product. Anybody,
including the agents, distributors or employees, is not
in the position to amend the contents of this warranty.
Please contact your local distributor for products not
covered by this warranty.
GST China
Gulf Security Technology Co., Ltd.
No. 80, Changjiang East Road,
QETDZ, Qinhuangdao, Hebei,
P. R. China 066004
Tel: +86 (0) 335 8502528
Fax: +86 (0) 335 8508942
www.gst.com.cn
GST UK
Global System Technology PLC
Lion Court, Staunton Harold Hall,
Melbourne Road, Ashby de la Zouch,
Leicestershire, England LE65 1RT
Tel: +44 1283 225 478
Fax: +44 1283 220 690
www.gst.uk.com
GST Dubai
Global System Technology PLC
PO Box 17998 Unit ZA04
JEBEL ALI Free Zone,
Dubai, UAE
Tel: +971 (0) 4 8833050
Fax: +971 (0) 4 8833053
www.gst.uk.com
This document is subject to change without notice. Please contact GST for more information or questions.