TELEDYNE OLDHAM SIMTRONICS MX32 User manual

NP32V2EN Revision D.0
NP32V2EN Revision D.0
MX32v2
ANALOG AND DIGITAL CONTROLLER

MX32v2
ANALOG AND DIGITAL CONTROLLER
USER MANUAL
II
NP32V2EN
Revision D.0
User Manuals in other languages are available on Website
https://teledynegasandflamedetection.com
Copyright October 2020 by TELEDYNE OLDHAM SIMTRONICS S.A.S. All rights reserved.
The reproduction of all or any section of this document in any form whatsoever without the
written permission of TELEDYNE OLDHAM SIMTRONICS S.A.S. is forbidden.
The information contained in this manual is accurate to our knowledge. As a result of continuous
research and development, the specifications of this product may be modified at any time
without prior notice.
TELEDYNE OLDHAM SIMTRONICS S.A.S.
Rue Orfila
Z.I. Est – CS 20417
62027 ARRAS Cedex

MX32v2
ANALOG AND DIGITAL CONTROLLER
USER MANUAL
NP32V2EN
Revision D.0
III
Table of contents
1General Information............................................................................ 1
1.1 User Manual.........................................................................................................1
1.2 Symbols used.......................................................................................................1
1.3 Safety Instructions..............................................................................................2
1.4 Important Information .....................................................................................2
1.5 Liability Limits .......................................................................................................3
1.6 Warranty................................................................................................................3
2General Introduction .......................................................................... 5
2.1 Purpose of the MX32v2 controller ...............................................................5
2.2 The different Versions.......................................................................................7
2.3 Firmplate ...............................................................................................................8
2.4 The COM 32 Software......................................................................................8
3Mechanical Installation ..................................................................... 9
3.1 MX32v2 Controller .............................................................................................9
3.2 Gas detectors .....................................................................................................10
3.3 Digital Modules...................................................................................................10
4The MX32v2 Controller........................................................................ 11
4.1 Overview of the Unit.........................................................................................11
4.2 Front Plate ............................................................................................................15
4.3 Alarm Thresholds and Relays ........................................................................17
4.4 Firmplate ...............................................................................................................19
5Digital Modules...................................................................................... 21
5.1 Addressable Digital Modules........................................................................21
5.2 RS485 Transmission.............................................................................................22
5.3 Communication Setup....................................................................................22
5.4 Relay modules ....................................................................................................24
5.5 16-Logic Input Module ....................................................................................26

MX32v2
ANALOG AND DIGITAL CONTROLLER
USER MANUAL
IV
NP32V2EN
Revision D.0
5.6 8-Analog Input Module...................................................................................28
5.7 4-Analog Output Module...............................................................................30
6Wiring and Electrical Connections................................................ 33
6.1 Controller Connection.....................................................................................33
6.2 4- or 8-Relay Modules ......................................................................................37
6.3 16-Logic Input Module ....................................................................................37
6.4 8-Analog Input Module...................................................................................38
6.5 4 Analog Output Module...............................................................................39
7Menus........................................................................................................ 41
7.1 General Menu Tree...........................................................................................41
7.2 Navigation Key Functions...............................................................................42
7.3 Display in normal mode ..................................................................................42
7.4 Main Menu ...........................................................................................................44
7.5 System ....................................................................................................................44
7.6 Program.................................................................................................................45
7.7 Calibration ...........................................................................................................45
7.8 4. Maintenance..................................................................................................49
7.9 5. Information ......................................................................................................50
8Main Part Numbers .............................................................................. 55
9Cleaning and maintenance............................................................ 57
9.1 Cleaning ...............................................................................................................57
9.2 Fuse replacement .............................................................................................57
9.3 Replacement of the lithium battery ..........................................................57
10 Certificate of Compliance ............................................................... 59
11 Technical Specifications.................................................................... 63
11.1 MX32v2 Controller .............................................................................................63
11.2 Relay Module......................................................................................................66
11.3 16-Logic Input Module ....................................................................................66
11.4 8-Analog Input Module...................................................................................67
11.5 4-Analog Output Module...............................................................................67
12 RS485 Digital Output............................................................................ 69

MX32v2
ANALOG AND DIGITAL CONTROLLER
USER MANUAL
NP32V2EN
Revision D.0
V
12.1 Card description................................................................................................69
12.2 Transfer Table ......................................................................................................70
12.3 Address Table......................................................................................................71
13 Specific conditions of use and Functional Safety ................... 77
13.1 Reliability data....................................................................................................77
13.2 Specific Conditions of Use .............................................................................77
13.3 Specific instructions for the prevention of explosions according
to ATEX 2014/34/EU European Directive..................................................78

MX32v2
ANALOG AND DIGITAL CONTROLLER
USER MANUAL
VI
NP32V2EN
Revision D.0

MX32v2
ANALOG AND DIGITAL CONTROLLER
USER MANUAL
NP32V2EN
Revision D.0
1
1General Information
WARNING: ALL INDIVIDUALS WHO HAVE OR WILL HAVE
RESPONSIBILITY FOR USING, MAINTAINING, OR SERVICING THIS
PRODUCT MUST READ THIS ENTIRE MANUAL CAREFULLY. FAILURE
TO USE THIS EQUIPMENT PROPERLY COULD RESULT IN SERIOUS
INJURY OR DEATH.
1.1 User Manual
The instructions given in this manual must be read thoroughly before installation and start-up,
particularly those concerning the points related to the safety of the end-user. This user manual
must be made available to every person involved in the activation, use, maintenance, and
repair of the unit.
The information, technical data, and diagrams contained in this manual are based on the
information that is available at a given time. In case of doubt, contact
TELEDYNE OLDHAM
SIMTRONICS
for additional information.
The aim of this manual is to supply simple and accurate information to the user
. TELEDYNE
OLDHAM SIMTRONICS
cannot be held liable for any misinterpretations in the reading of this
manual. In spite of our efforts to produce an error-free manual, it may nonetheless contain some
unintentional technical inaccuracies.
In the client’s interest,
TELEDYNE OLDHAM SIMTRONICS
reserves the right to modify the
technical characteristics of its equipment to increase their performance without prior notice.The
present instructions and their content are the inalienable property of TELEDYNE OLDHAM
SIMTRONICS.
1.2 Symbols used
Icon
Significance
This symbol indicates useful additional information.
This symbol indicates: Earth ground connection.
This symbol denotes: Protective earth terminal. A cable of the adequate diameter
must be connected to ground and to the terminal having this symbol.

MX32v2
ANALOG AND DIGITAL CONTROLLER
USER MANUAL
2
NP32V2EN
Revision D.0
Icon
Significance
This symbol denotes:
Attention! In the present mode of use, failure to adhere to
the instructions preceded by this symbol can result in a risk of electric shock
and/or death.
This symbol indicates: You must refer to the instructions.
European Union (and EEA) only. This symbol indicates that this product must not
be discarded with household waste, as per the EEA directive (2002/96/EC) and
your own national regulations.
This product must be disposed of at a collection point that is reserved for this
purpose, for example, an official site for the collection of electrical and electronic
equipment (EEE) in view of their recycling, or a point of exchange for authorized
products that is accessible when you acquire a new product of the same type.
1.3 Safety Instructions
Labels intended to remind you of the principal precautions of use have been placed on the unit
in the form of pictograms. These labels are considered an integral part of the unit. If a label falls
off or becomes illegible, please ensure it is replaced. The significance of the labels is detailed
below.
The installation and electrical connections must be carried out by qualified personnel
according to the instructions of the manufacturer and the standards of the competent
authorities.Failure to adhere to the instructions can have serious consequences on the
safety of persons. Please be extremely rigorous as regards electricity and assembly
(coupling, network connections).
Cables with an operating temperature of 70°C minimum (158 °F)
must be used
because the temperature inside the controller can reach 70°C (158 °F).
1.4 Important Information
The modification of the material and the use of parts of an unspecified origin shall entail the
cancellation of any form of warranty.The use of the unit has been projected for the applications
specified in the technical characteristics. Exceeding the indicated values cannot in any case be
authorized.

MX32v2
ANALOG AND DIGITAL CONTROLLER
USER MANUAL
NP32V2EN
Revision D.0
3
1.5 Liability Limits
Neither
TELEDYNE OLDHAM SIMTRONICS
nor any other associated company under any
circumstances can be held liable for any damage, including, without limitations, damages for
loss or interruption of manufacture, loss of information, defect of the
MX32v2
controller,
injuries, loss of time, financial or material loss, or any direct or indirect consequence of loss
occurring in the context of the use or impossibility of use of the product, even in the event that
TELEDYNE OLDHAM SIMTRONICS
has been informed of such damage.
1.6 Warranty
Under normal conditions of use and on return to the factory, parts and workmanship carry a
two year warranty, excluding consumables such as backup power supplies, audio and visible
alarms, etc.

MX32v2
ANALOG AND DIGITAL CONTROLLER
USER MANUAL
4
NP32V2EN
Revision D.0

MX32v2
ANALOG AND DIGITAL CONTROLLER
USER MANUAL
NP32V2EN
Revision D.0
5
2General Introduction
2.1 Purpose of the MX32v2 controller
This controller is intended for the continuous measurement and control of the gases present in
the atmosphere.
MX32v2 8 relay output modules
and 4 4-20mA output
modules
Figure 1: MX32v2 and examples of the modules
The system primarily comprises :
•a MX32v2 (1 or 2 lines),
•different modules (analog or digital detectors, logic inputs, analog inputs, relay outputs,
and analog outputs).
The
MX32v2
instantly handles the measurements of detectors and input modules. As soon as the
measurements reach the configured thresholds, the internal buzzer and the LED indicators go
off. At the same time, the corresponding relays are activated to drive the additional actions
programmed by the user.The
MX32v2
controller is programmed by using the
COM 32
configuration software.Figure 2 presents a configuration example.

MX32v2
ANALOG AND DIGITAL CONTROLLER
USER MANUAL
6
NP32V2EN
Revision D.0
Figure 2: Example of an
MX32v2
configuration using different analog
and digital detectors as well as digital modules
MX32v2
Configuring PC with the COM
32 application
Digital detectors
2 logic
inputs
Analog recorders
Four 4-
20mA Analog
Output Module
8 Relay Output Module
Logic Input Module
4 Relay Output
Module
16 logic inputs
Analog inputs
E
xternal power
supply
USB
link
8 Analog Input Module

MX32v2
ANALOG AND DIGITAL CONTROLLER
USER MANUAL
NP32V2EN
Revision D.0
7
2.2 The different Versions
The
MX32v2
controller is available in 3 versions:1 line,
•2 lines,
•Bridge Version (2 channels) for direct monitoring of Wheatstone bridge flammable gas
detectors.
Figure 3:
MX32v2
The following table details the different possible configurations depending on the controller’s
version. On each line, it is possible to connect 4-20mA analog detectors or digital addressable
modules.
Maximum Capacity
Version
Detectors
Analog Input
Modules
Relay Output
Modules
Logic Input
Modules
Analog
Output
Modules
1 line 4 1 2 1 1
2 lines 8 2 4 2 2
Wheatstone
Bridge 2(1) 0 0 0 0
(1) OLC 10, OLC 10Twin or OLC 100 flammable gas detectors
Maximum Capacity
Version
External Relays
Logic Inputs
Analog Outputs
1 line
8
16
4
2 lines 16 16 8
Wheatstone
Bridge 0 0 0
•
Table 1: Summary of the maximum capacity as per the controller type

MX32v2
ANALOG AND DIGITAL CONTROLLER
USER MANUAL
8
NP32V2EN
Revision D.0
2.3 Firmplate
It contains relevant information with respect to the controller version (CSA or ATEX variants).
Tag.
Description
1.
Product Name
2.
Part Number
3.
CSA mark
4. CE marking with identification of the Notified Body that assessed the TELEDYNE
OLDHAM SIMTRONICS manufacturing quality system (0080 - INERIS)
5.
ATEX marking (Performance requirements of gas detection systems for flammable
gases)
6. Serial Number. The first two digits (in this case 17) correspond to the year of
manufacture (in this case 2017).
7.
Variant (1 or 2 lines to work with 4-20mA analog detector or TELEDYNE OLDHAM
SIMTRONICS digital detector, or 2 channels to work with Wheatstone bridge gas
detectors). In this example, version ‘Wheatstone Bridge’.
8. Power supply type (24Vdc or 100-240Vac). In this example, 24Vdc type.
9.
Name and mail address of the Manufacturer
10.
Warnings
2.4 The COM 32 Software
This is intended for setting the
MX32v2
parameters from a Windows®operated PC. The
operation and use of this application is covered in a special training course.
10
9
8
7
171204Y-693
4
5
6
1
2
3

MX32v2
ANALOG AND DIGITAL CONTROLLER
USER MANUAL
NP32V2EN
Revision D.0
9
3Mechanical Installation
3.1 MX32v2 Controller
3.1.1
LocationThe
MX32v2
is intended for indoor use only and shall be installed in
premises without explosive atmospheres, away from direct exposure to sunlight, and protected
from humidity, dust, and temperature variations. It shall preferably be located in a monitored
environment (for instance: guardhouse, control room, or instrument room, etc.).
3.1.2 Attachment of the wall enclosureAccess to the controller must be
ensured in order to facilitate adjustments, monitoring, and cabling. A space of 400 mm is
necessary in front of the
MX32v2
for opening the door. Use 3 fixing screws 4x25 mm for fixing
the case support.
Figure 4: Dimensions
Figure 5: Fixing the
MX32v2

MX32v2
ANALOG AND DIGITAL CONTROLLER
USER MANUAL
10
NP32V2EN
Revision D.0
3.2 Gas detectors
Refer to the manual supplied with each detector.
3.2.1 Location
Each detector shall be positioned at ground level, on the ceiling, at human height or near air
extraction ducts, depending on the density of the gas to be detected or the application. Heavy
gases are detected close to the ground, while lighter gases are present along the ceiling. If
necessary, contact
TELEDYNE OLDHAM SIMTRONICS
for any questions regarding proper
detector positioning.
3.2.2 Fixing
The detectors shall preferably be positioned in an accessible place so that inspections and
maintenance can be carried out as well as to ensure the absolute safety of the operators. The
detectors must not be obstructed by anything that will prevent them from measuring the ambient
environment to be checked.
3.3 Digital Modules
For cabling and electrical information see paragraph
Wiring and Electrical
Connections
on page 33.
LocationThe relay modules, logic outputs, analog outputs, and analog inputs are positioned
depending on the installation layout, mandatorily in places free from explosive atmospheres,
protected from humidity, dust, and temperature variations; for example in technical cabinets.
Fixing
These modules shall be mounted on a DIN rail in
a cabinet or in an electrical cabinet.
For relay
modules connected to low voltage electrical
parts, the installation is carried out according to
the standards in force.
Figure 6: Fixing of a module (relay, logic
outputs, or analog outputs or inputs) on a DIN
rail

MX32v2
ANALOG AND DIGITAL CONTROLLER
USER MANUAL
NP32V2EN
Revision D.0
11
4The MX32v2 Controller
4.1 Overview of the Unit
External view
080
Rep.
Function
Rep.
Function
A.
Monochromatic, back-lit graphic
LCD display
F.
Toggle Latch (one is lockable)
B. Zone 1 status indicator G. Power On/Off indicator
C. Zone 2 status indicator H. Failure/maintenance indicator
D.
Integrated siren (option)
J.
Contextual soft keys
E.
Integrated flash (optional)
K.
Alarm Acknowledgement button
Figure 7: External view of the wall-mounted and rack-mounted versions

MX32v2
ANALOG AND DIGITAL CONTROLLER
USER MANUAL
12
NP32V2EN
Revision D.0
Internal view
Figure 8: Internal view (2 line version on top and Bridge version at the bottom)
Rep.
Function
A. LCD graphic display card
B. USB programmation port
C. On-board additional flashlight (option)
D. Programming (or mode) selector
0.
MX32v2
in normal operation.
1. Read/Write configuration program
2.
MX32v2
firmware update via a PC

MX32v2
ANALOG AND DIGITAL CONTROLLER
USER MANUAL
NP32V2EN
Revision D.0
13
Rep.
Function
Once the unit configuration or update is complete, always set back the
selector in the "0" position. The
MX32v2
will resume automatically.
E.
Microcontroller reset button. Press this button to reset the controller.
F.
On-board additional siren, settable from 85 to 100dB (option)
G. CR2032 lithium battery. Allows data and real time clock saving in case of power
failure. Runtime is approx. 450 days while power off. Keep the
MX32v2
powered
during battery replacement.
H. 100-240Vac (50-60Hz) input terminal
I 100-240Vac / 24Vdc power supply (option)
J 22-28Vdc input terminal. Allows the use of an external power supply (read External
24Vdc Power Supply, page 34)
K. Display contrast setting
L. Remote acknowledgement input terminal (NO dry relay contact)
M Cable glands; 5 x M16 + 2 x M20
N Line #1 terminal (1 to 2 lines depending on the version)
O.
Digital communication status LED indicators (Line #1 on left, Line #2 on right). The
information displayed by each pair of LEDs is interpreted as follows:
LED Status
Significance
Fast blinking
Fast blinking
Line is in normal operation mode- Tx: sends
queries to the attached modules
- Rx: receives data from attached modules
Irregular
blinking
Irregular
blinking
Bad communication quality with at least one
module.
Blinks 1 time
per sec
Off
Communication failure. Absence or failure of one
module
On communication failure
, the internal buzzer,
the failure indicator and
the Fault relay are
activated.
Off Off No active module is present on the line
P. Grounding terminals to connect cable shield for digital and analog connections
Q From top to bottom, relay alarm terminals (R1 to R4 respectively). DPCO relays,
contacts rating 250Vac-30Vdc / 5A

MX32v2
ANALOG AND DIGITAL CONTROLLER
USER MANUAL
14
NP32V2EN
Revision D.0
Rep. Function
R.
Fault and Alarms relays (2 relays are located under the power supply; tag I). From
top to bottom:
•Fault (Fault relay, non-configurable)
•R1, R2, R3, R4 (alarm relays, configurable)
Configuration of Alarm Relays
Alarm relays are to be programmed with
COM 32
software. The PCB printing displays while unpowered. R1 to R4 relays
can be
configured as normally energized
(the coil is powered when not in alarm) or
normally de-energized (the coil is powered when in alarm). There are different way
to program the relays:
•Normal mode: relay operates as the alarm sequence. The sure can set a delay
and chose the relay to be latched or unlatched (see Alarm Acknowledgement,
page 18).
•Buzzer mode: This mode is usually used for audible alarms management. The
‘buzzer’ relay acts as a ‘normal’ relay but can be acknowledged even if the
alarm is still present (in order to turn the siren off).
The time delays are:
. Reset Inhibit: Minimum time of activation, adjustable from 0 to 900 seconds.
. Automatic reset: Time adjustable between 15 and 900 seconds, beyond which
the buzzer relay is automatically deactivated.
. Reactivation time: Time adjustable between 15 and 900 seconds, beyond which
the buzzer relay is automatically reactivated if the alarm is still present.
Alarm Relay Management
by the logic operators OR, AND, NOR, NAND. Up to 4
levels of parentheses. The result of the equation controls the relay.
•Voting operation (x out of y): There must be at least “x” events out of “y” to
activate the relay. Depending on user’s programmation, a FAUT event can be
treated as an alarm event.
S. Relays status DEL indicator. Illuminated when the corresponding relay coil is ON.
T. 4 Amp fuse, protects the 24V power supply input
U. Modbus RS485 communication board (option, see page 69)
V.
Zero setting potentiometer (on the left line #1, on the right line #2)
W.
Span setting potentiometer (on the left line #1, on the right line #2)
X.
Catalytic bead current adjustment (top line #1, bottom line #2). Settings are
reserved to authorized personel
Y. Faut relay terminal. DPCO relay, 250Vac-30Vdc / 5A
This manual suits for next models
1
Table of contents
Other TELEDYNE OLDHAM SIMTRONICS Controllers manuals