
EVCO S.p.A. | EVJ 200 | Instruction sheet ver. 1.1 | Code 104J200I113 | Page 2 of 3 | PT 46/16
5. Touch the SET key.
6. Touch the ON/STAND-BY key (or do not operate for 60s) to exit
the procedure.
5.6 View the temperature detected by the probes
Check that the keypad isn’t locked.
1. Touch the DOWN key for 1s.
2. Touch the UP or DOWN key within 15s to select a label.
LAB. DESCRIPTION
Pb1 cabinet temperature (if P4 = 0, 1 or 2)
inlet air temperature (if P4 = 3)
Pb2 evaporator temperature (if P3 = 1 or 2)
Pb3 auxiliary temperature (if P4 = 1, 2 or 3)
Pb4 calculated product temperature (CPT; if P4 = 3)
3. Touch the SET key.
4. Touch the ON/STAND-BY key (or do not operate for 60s) to exit
the procedure.
6 DATA-LOGGER MODULE on SD CARD (not available in EVJ204 and EVJ205)
6.1 Initial information
The data-logger module makes it possible to write information about the device on an SD card
(in CSV format ), in HACCP or service mode.
Data-logger module configuration parameters.
PAR. DEF. PARAMETER MIN... MAX.
Sd0
30
SD card writing interval in HACCP
mode
1... 30 min
Sd1
1
SD card writing interval in service
mode
1... 30 min
Sd2 60 service mode duration 1... 240 min
Sd3 0 enable critical temperature recording 0 = no 1 = yes
Sd4 0 enable cabinet temperature recording 0 = no 1 = yes
Sd5 1 decimal separator type 0 = comma 1 = point
6.2 Writing in HACCP mode
Writing in HACCP mode is always activated, it generates a daily file and a monthly file.
Information written in HACCP mode.
- cabinet temperature (if Sd4 = 1, default “no”)
- critical temperature (if Sd3 = 1, default “no”)
- device switched on/off
- defrost activated/completed
- energy saving activated/deactivated
- alarm activated/restored
- power supply restored
The date and time is written for each piece of information.
6.3 Writing in service mode
Writing in service mode must be manually activated.
Information written in service mode.
- temperature detected by all probes
- enable/disable probes
- device switched on/off
- functions on/off
- defrost activated/completed
- energy saving activated/deactivated
- alarm activated/restored
- power supply restored
The date and time is written for each piece of information.
6.4 Activate/deactivate writing in service mode
Check that the keypad isn’t locked.
1. Touch the DOWN key for 1s.
2. Touch the UP or DOWN key within 15s to select the label “SEr”.
3. Touch the SET key.
4.
Touch the UP or DOWN key within 15s to set “1” (activate
writing) or “0” (deactivate writing).
5. Touch the ON/STAND-BY key (or do not operate for 60s) to exit
the procedure.
6.5 File names
Example of a daily file name written in HACCP mode (e.g. the file “log001_2015_03_26.csv”).
001 the device address is 1 (parameter LA)
2015 the file was written in 2015
03 the file was written in March
26 the file was written on 26 March 2015
Example of a monthly file name written in HACCP mode (e.g. the file “log001_2015_m03.csv”).
001 the device address is 1 (parameter LA)
2015 the file was written in 2015
m03 the file was written in March 2015
Example of a file name written in service mode (e.g. the file “log001_2015_0001.csv”).
001 the device address is 1 (parameter LA)
2015 the file was written in 2015
0001 sequence number
6.6 View data-logger module alarms
Check that the keypad isn’t locked.
1. Touch the DOWN key for 1s.
2. Touch the UP or DOWN key within 15s to select the label “Err”.
3. Touch the SET key.
4. Touch the UP or DOWN key within 15s to see the alarm code.
LAB. DESCRIPTION
FUL no space left on SD card alarm
Sd SD card not inserted or not recognised alarm
5. Touch the ON/STAND-BY key (or do not operate for 60s) to exit
the procedure.
7 SETTINGS
7.1 Setting configuration parameters
1. Touch the SET key for 4s: the display will show the label “PA”.
2. Touch the SET key.
3.
Touch the UP or DOWN key within 15s to set the PAS value
(default “-19”).
4. Touch the SET key (or do not operate for 15s): the display will
show the label “SP”.
5. Touch the UP or DOWN key to select a parameter.
6. Touch the SET key.
7. Touch the UP or DOWN key within 15s to set the value.
8. Touch the SET key (or do not operate for 15s).
9. Touch the SET key for 4s (or do not operate for 60s) to exit the
procedure.
7.2 Set the date, time and day of the week (available in EVJ214, EVJ215 and
EVJ294 or in EVJ204 and EVJ205 with interface EVIF25TBX connected)
N.B.
- If the device is connected to the interface EVIF25TBX, do not disconnect the device
from the mains within two minutes since the setting of the time and day of the
week.
- If the device communicates with the APP EVconnect, the date, time and day of the
week will automatically be set by the smartphone or tablet.
Check that the keypad isn’t locked.
1. Touch the DOWN key for 1s.
2. Touch the UP or DOWN key within 15s to select the label “rtc”.
3. Touch the SET key: the display will show the label “y” followed
by the last two figures of the year.
4. Touch the UP or DOWN key within 15s to set the year.
5. Repeat actions 3 and 4 to set the next labels.
LAB. MEANING OF THE NUMBERS FOLLOWING THE LABEL
n month (01… 12)
d day (01… 31)
h time (00… 23)
nminutes (00… 59)
6. Touch the SET key: the display will show the label for the day of
the week.
7. Touch the UP or DOWN key within 15s to set the day of the
week.
LAB. DESCRIPTION
Mon Monday
tuE Tuesday
UEd Wednesday
thu Thursday
Fri Friday
Sat Saturday
Sun Sunday
8. Touch the SET key: the device will exit the procedure.
9. Touch the ON/STAND-BY key to exit the procedure beforehand.
7.3 Reset the factory settings
N.B.
Check that the factory settings are appropriate; see the section CONFIGURATION
PARAMETERS.
1. Touch the SET key for 4s: the display will show the label “PA”.
2. Touch the SET key.
3. Touch the UP or DOWN key within 15s to set “149”.
4. Touch the SET key (or do not operate for 15s): the display will
show the label “dEF”.
5. Touch the SET key.
6. Touch the UP or DOWN key within 15s to set “1”.
7. Touch the SET key (or do not operate for 15s).
8. Interrupt the power supply to the device.
9. Touch the SET key for 2s before action 6 to exit the procedure
beforehand.
8 CONFIGURATION PARAMETERS
N. PAR. DEF. SETPOINT MIN... MAX.
1 SP 0.0 setpoint r1... r2
N. PAR. DEF. ANALOGUE INPUTS MIN... MAX.
2
CA1
0.0
cabinet probe offset
-25... 25 °C/°F
if P4 = 3, air in probe offset
3 CA2 0.0 evaporator probe offset -25... 25 °C/°F
4 CA3 0.0 auxiliary probe offset -25... 25 °C/°F
5 P0 1 probe type 0 = PTC 1 = NTC
6 P1 1 enable °C decimal point 0 = no 1 = yes
7
P2
0
temperature unit of
measurement
0 = °C 1 = °F
8
P3
1
evaporator probe function
0 = disabled
1 = defrost + fan
2 = fan
9
P4
0
configurable input function
0 = digital input
1 = condenser probe
2 =
critical temperature probe
3 = air out probe
if P4 = 3, regulation temperature
= product temperature (CPT)
10
P5
0
value displayed
0 = regulation temperature
1 = setpoint
2 = evaporator temperature
3 = auxiliary temperature
4 = air in temperature
11
P7
50
inlet air weight for calculated
product temperature (CPT)
0... 100 %
CPT = {[(P7 x (inlet air T)] +
[(100 - P7) x (outlet air T)] :
100}
12 P8 5 display refresh time 0... 250 s : 10
N. PAR. DEF. REGULATION MIN... MAX.
13 r0 2.0 setpoint differential 1... 15 °C/°F
14 r1 -40 minimum setpoint -99 °C/°F... r2
15 r2 50.0 maximum setpoint r1... 199 °C/°F
16 r3 0 enable setpoint block 0 = no 1 = yes
17 r4 0.0 setpoint offset in energy saving 0... 99 °C/°F
18 r6 0.0 setpoint offset in overcooling 0... 99 °C/°F
19 r7 0 overcooling duration 0... 240 min
20
r12
1
position of the r0 differential
0 = asymmetric
1 = symmetric
N. PAR. DEF. COMPRESSOR MIN... MAX.
21
C0
0
compressor on delay after
power-on
0... 240 min
22
C1
5
delay between 2 compressor
switch-ons
0... 240 min
23 C2 3 compressor off minimum time 0... 240 min
24 C3 0 compressor on minimum time 0... 240 s
25
C4
10
compressor off time during
cabinet probe alarm
0... 240 min
26
C5
10
compressor on time during
cabinet probe alarm
0... 240 min
27
C6
80.0
threshold for high condensation
warning
0... 199 °C/°F
differential = 2 °C/4 °F
28
C7
90.0
threshold for high condensation
alarm
0... 199 °C/°F
29 C8 1 high condensation alarm delay 0... 15 min
30
C10
0
compressor hours for service
0... 999 h x 100
0 = disabled
31
C11
10
second compressor switch-on
delay
0... 240 s
N. PAR. DEF. DEFROST MIN... MAX.
32
d0
8
automatic defrost interval
0... 99 h
0 = only manual
if d8 = 3, maximum interval
33
d1
0
defrost type
0 = electric
1 = hot gas
2 = compressor stopped
34 d2 2.0 threshold for defrost end -99... 99 °C/°F
35
d3
30
defrost duration
0... 99 min
se P3 = 1, maximum duration
36 d4 0 enable defrost at power-on 0 = no 1 = yes
37 d5 0 defrost dealy after power-on 0... 99 min
38
d6
1
value displayed during defrost
0 = regulation temperature
1 = display locked
2 = dEF label
39 d7 2 dripping time 0... 15 min
40
d8
0
defrost interval counting mode
0 = device on hours
1 = compressor on hours
2 = hours evaporator
temperature < d9
3 = adaptive
4 = real time
41
d9
0.0
evaporation threshold for
automatic defrost interval
counting
-99... 99 °C/°F
42 d11 0 enable defrost timeout alarm 0 = no 1 = yes
43
d15
0
compressor on consecutive time
for hot gas defrost
0... 99 min
44
d16
0
pre-dripping time for hot gas
defrost
0... 99 min
45
d18
40
adaptive defrost interval
0... 999 min
if compressor on + evapora-
tor temperature < d22
0 = only manual
46
d19
3.0
threshold for adaptive defrost
(relative to optimal evaporation
temperature)
0... 40 °C/°F
optimal evaporation
temperature - d19
47
d20
180
compressor on consecutive time
for defrost
0... 999 min
0 = disabled
48
d21
200
compressor on consecutive time
for defrost after power-on and
overcooling
0... 500 min
if (regulation temperature -
setpoint) > 10°C/20 °F
0 = disabled
49
d22
-2.0
evaporation threshold for
adaptive defrost interval counting
(relative to optimal evaporation
temperature)
-10... 10 °C/°F
optimal evaporation
temperature + d22
50
d25
0
enable air out probe for defrost
during evaporator probe alarm
0 = no 1 = yes
51
d26
6
defrost interval during
evaporator probe alarm
0... 99 h
0 = only manual
if d25 = 1
N. PAR. DEF. ALARMS MIN... MAX.
52
A0
0
select value for high/low
temperature alarms
0 = regulation temperature
1 = evaporator temperature
53
A1
0.0
threshold for low temperature
alarm
-99... 99 °C/°F
54
A2
0
low temperature alarm type
0 = disabled
1 = relative to setpoint
2 = absolute
55
A4
0.0
threshold for high temperature
alarm
-99... 99 °C/°F
56
A5
0
high temperature alarm type
0 = regulation temperature
1 = evaporator temperature
2 = auxiliary temperature
57
A6
120
high temperature alarm delay
after power-on
0... 240 min
58
A7
15
high/low temperature alarms
delay
0... 240 min
59
A8
15
high temperature alarm delay
after defrost
0... 240 min
60
A9
15
high temperature alarm delay
after door closing
0... 240 min
61
A10
10
power failure duration for alarm
recording (not available in
EVJ204 and EVJ205)
0... 240 min
62
A11
2.0
high/low temperature alarms
reset differential
1... 15 °C/°F
63
A12
0
power failure alarm notification
type (not available in EVJ204 and
EVJ205)
0 = HACCP LED
1 = HACCP LED + PF label +
buzzer
2 =
HACCP LED + PF label +
buzzer (if duration > A10)
N. PAR. DEF. FANS MIN... MAX.
64
F0
1
evaporator fan mode during
normal operation
0 = off 1 = on
2 = on if compressor on
3 = thermoregulated (with
regulation temperature
+ F1)
4 = thermoregulated (with
regulation temperature
+ F1) if compressor on
5 = according to F6
6 =
thermoregulated (with F1)
7 = thermoregulated (with
F1) if compressor on
65
F1
-4.0
threshold for evaporator fan
operation
-99... 99 °C/°F
66
F2
0
evaporator fan mode during
defrost and dripping
0 = off 1 = on
2 = according to F0
67
F3
2
evaporator fan off maximum
time
0... 15 min
68
F4
30
evaporator fan off time during
energy saving
0... 240 s x 10
if F0 ≠5
69
F5
30
evaporator fan on time during
energy saving
0... 240 s x 10
if F0 ≠5
70
F6
0
high/low humidity operation
0 = low humidity (with F17
and F18 if compressor
off, on if compressor on)
1 = high humifity (on)
71
F7
5.0
threshold for evaporator fan on
after dripping (relative to
setpoint)
-99... 99 °C/°F
setpoint + F7
72
F8
2.0
threshold for evaporator fan
operation differential
1... 15 °C/°F
73
F9
10
evaporator fan off delay after
compressor off
0... 240 s
if F0 = 2 or 5
74
F10
1
condenser fan mode
0 =
thermoregulated (with F11)
1 = thermoregulated (with
F11) if compressor off,
on if compressor on
2 = thermoregulated (with
F11) if compressor off,
on if compressor on, off
during defrost, pre-
dripping and dripping
75
F11
15.0
threshold for condenser fan on
0... 99 °C/°F
differential = 2 °C/4 °F
76
F12
30
condenser fan off delay after
compressor off
0... 240 s
if P4 ≠1
77
F17
60
evaporator fan off time with low
humidity
0... 240 s