TELEDYNE OLDHAM SIMTRONICS MX 43 User manual

NPM43EN Revision K.0
MX 43
ANALOG AND DIGITAL CONTROLLER
U
SER GUIDE

MX 43
ANALOG AND DIGITAL CONTROLLER
USER GUIDE
II
NPM43EN
Revision K.0
User Manuals in others language are available on Website
https://teledynegasandflamedetection.com
Copyright March 2020 by TELEDYNE OLDHAM SIMTRONICS S.A.S.
All rights reserved. The reproduction of all or any section of this document in any form
whatsoever without the written permission of TELEDYNE OLDHAM SIMTRONICS S.A.S. is
forbidden.
The information contained in this manual is accurate to our knowledge.
As a result of continuous research and development, the specifications of this product may be
modified at any time without prior notice.
The original version is the English one.
TELEDYNE OLDHAM SIMTRONICS S.A.S.
Rue Orfila
Z.I. Est – CS 20417
62027 ARRAS Cedex

MX 43
ANALOG AND DIGITAL CONTROLLER
USER GUIDE
NPM43EN
Revision K.0 III
Table of contents
1General Information....................................................................... 1
User Manual.........................................................................................................1
Symbols used.......................................................................................................1
Safety Instructions..............................................................................................2
Important Information .....................................................................................2
Liability Limits .......................................................................................................2
Warranty................................................................................................................3
2General Introduction ..................................................................... 5
Purpose of the MX 43 controller...................................................................5
The MX 43 Controller ........................................................................................6
The COM 43 Application ................................................................................7
Firmplate ...............................................................................................................8
3Mechanical Installation ................................................................ 9
MX 43 Controller.................................................................................................9
Digital Modules...................................................................................................11
4The MX 43 Controller...................................................................... 13
Overview of the Unit.........................................................................................13
Front Plate.............................................................................................................17
Alarm and Relay Thresholds ..........................................................................20
USB Key Operation............................................................................................22
5Digital Modules................................................................................ 25
Addressable Digital Modules ........................................................................25
RS485 Transmission.............................................................................................26
Configuration of Communication ..............................................................27
Relay modules ....................................................................................................28

MX 43
ANALOG AND DIGITAL CONTROLLER
USER GUIDE
IV
NPM43EN
Revision K.0
16-Logic Input Module ....................................................................................30
8-Analog Input Module...................................................................................32
4-Analog Output Module...............................................................................34
6Wiring and Electrical Connections............................................. 37
Controller Connection.....................................................................................37
4- or 8-Relay Modules ......................................................................................42
16-Logic Input Module ....................................................................................43
8-Analog Input Module...................................................................................43
4-Analog Output Module...............................................................................44
7Menus ................................................................................................ 45
General Menu Tree...........................................................................................45
Navigation Key Functions...............................................................................46
Display in normal mode ..................................................................................46
Main Menu ...........................................................................................................47
8Main Part Numbers ......................................................................... 59
9Cleaning and maintenance ........................................................ 61
Cleaning ...............................................................................................................61
Fuse replacement .............................................................................................61
10 Certificate of Compliance ........................................................... 63
11 Technical Specifications............................................................... 69
MX 43 Controller.................................................................................................69
Relay Module ......................................................................................................71
16-Logic Input Module ....................................................................................72
8-Analog Input Module...................................................................................72
4-Analog Output Module...............................................................................73
12 RS485 Digital Output....................................................................... 75
Card description................................................................................................75
Transfer Table ......................................................................................................76
Address Table......................................................................................................77
13 Functional Safety ............................................................................ 83
Reliability data....................................................................................................83

MX 43
ANALOG AND DIGITAL CONTROLLER
USER GUIDE
NPM43EN
Revision K.0 V
Specific Conditions of Use .............................................................................83
Connecting detectors other than TELEDYNE OLDHAM
SIMTRONICS detectors to the MX 43 controller...................................................84
14 MX 43 in cabinets ........................................................................... 87
Presentation.........................................................................................................87
Codification.........................................................................................................88
Electrical connections.....................................................................................91
Control panel fixing ..........................................................................................94
Internal implantation........................................................................................97
Technical specifications .................................................................................109

MX 43
ANALOG AND DIGITAL CONTROLLER
USER GUIDE
VI
NPM43EN
Revision K.0

MX 43
ANALOG AND DIGITAL CONTROLLER
USER GUIDE
NPM43EN
Revision K.0 1
1General Information
User Manual
The instructions given in this manual must be read thoroughly before installation and start-up,
particularly those concerning the points related to the safety of the end-user. This user manual
must be made available to every person involved in the activation, use, maintenance, and
repair of the unit.
The information, technical data, and diagrams contained in this manual are based on the
information that is available at a given time. In case of doubt, contact
TELEDYNE OLDHAM
SIMTRONICS
for additional information.
The aim of this manual is to supply simple and accurate information to the user
. TELEDYNE
OLDHAM SIMTRONICS
cannot be held liable for any misinterpretations in the reading of this
manual. In spite of our efforts to produce an error-free manual, it may nonetheless contain some
unintentional technical inaccuracies.
In the client’s interest,
TELEDYNE OLDHAM SIMTRONICS
reserves the right to modify the technical
characteristics of its equipment to increase their performance without prior notice.
The present instructions and their content are the inalienable property of
TELEDYNE OLDHAM
SIMTRONICS
.
Symbols used
Icon
Significance
This symbol indicates useful additional information.
This symbol indicates:
Earth ground connection.
This symbol denotes:
Protective earth terminal. A cable of the adequate diameter must be connected to
ground and to the terminal having this symbol.
This symbol denotes:
Attention! In the present mode of use, failure to adhere to the instructions
preceded by this symbol can result in a risk of electric shock and/or death.
This symbol indicates:
You must refer to the instructions.

MX 43
ANALOG AND DIGITAL CONTROLLER
USER GUIDE
2
NPM43EN
Revision K.0
European Union (and EEA) only. This symbol indicates that this product must not be
discarded with household waste, as per the EEA directive (2002/96/EC) and your
own national regulations.
This product must be disposed of at a collection point that is reserved for this purpose, for example,
an official site for the collection of electrical and electronic equipment (EEE) in view of their recycling,
or a point of exchange for authorized products that is accessible when you acquire a new product of
the same type.
Any deviation as regards these recommendations for the disposal of this type of waste can have
negative effects on the environment and public health, as these electric and electronic products
generally contain substances that can be dangerous. Your full cooperation in the proper disposal of
this product promotes a better use of natural resources.
Safety Instructions
Labels intended to remind you of the principal precautions of use have been placed on the unit
in the form of pictograms. These labels are considered an integral part of the unit. If a label falls
off or becomes illegible, please ensure it is replaced. The significance of the labels is detailed
below.
The installation and electrical connections must be carried out by qualified personnel
according to the instructions of the manufacturer and the standards of the competent
authorities.
Failure to adhere to the instructions can have serious consequences on the safety of persons. Please
be extremely rigorous as regards electricity and assembly (coupling, network connections).
Cables with an operating temperature of up to 75°C-167°F must be used because the temperature
inside the controller can reach 60°C-140°F.
Important Information
The modification of the material and the use of parts of an unspecified origin shall entail the
cancellation of any form of warranty.
The use of the unit has been projected for the applications specified in the technical
characteristics. Exceeding the indicated values cannot in any case be authorized.
For MX43 in cabinet, refer to chapter 14.after reading this notice in its entirety
Liability Limits
Neither
TELEDYNE OLDHAM SIMTRONICS
nor any other associated company under any
circumstances can be held liable for any damage, including, without limitations, damages for
loss or interruption of manufacture, loss of information, defect of the MX 43 controller, injuries,

MX 43
ANALOG AND DIGITAL CONTROLLER
USER GUIDE
NPM43EN
Revision K.0 3
loss of time, financial or material loss, or any direct or indirect consequence of loss occurring in
the context of the use or impossibility of use of the product, even in the event that
TELEDYNE
OLDHAM SIMTRONICS
has been informed of such damage.
Warranty
Under normal conditions of use and on return to the factory, parts and workmanship carry a
two year warranty, excluding consumables such as backup power supplies, audio and visible
alarms, etc.

MX 43
ANALOG AND DIGITAL CONTROLLER
USER GUIDE
4
NPM43EN
Revision K.0

MX 43
ANALOG AND DIGITAL CONTROLLER
USER GUIDE
NPM43EN
Revision K.0 5
2General Introduction
Purpose of the MX 43 controller
This controller is intended for the continuous measurement and control of the gases present in
the atmosphere.
Wall-mounted MX 43 Rack-mounted MX 43 EB type Cabinet
to remote
optional modules
Figure 1: Wall-mounted MX 43 and examples of the modules.
The system primarily comprises:
■a wall-mounted MX 43;
■different modules (detector with digital or analog output, logic inputs, analog inputs,
relay outputs, and analog outputs).
The MX 43 instantly handles the measurements of detectors and input modules. As soon as the
measurements reach the programmed limit, a sound and visual alarm are given. At the same
time, the corresponding relay or relays are activated, in turn controlling the additional internal
or external actions envisaged by the user.
The MX 43 controller is programmed by using the COM 43 application.

MX 43
ANALOG AND DIGITAL CONTROLLER
USER GUIDE
6
NPM43EN
Revision K.0
Figure 2 presents a configuration example.
Figure 2: Example of an MX 43 configuration using different analog and digital detectors as well as digital modules.
The MX 43 Controller
2.2.1 Versions
The MX 43 controller is available in several versions:
■Wall-mounted version 4 lines.
■Wall-mounted version 8 lines.
■Rack-mounted version 8 lines.
■MX43S and MX43L in cabinet version 8 line
MX 43
Configuring PC with the
COM
43
application
Analog
detectors
Digital detectors
2 logic
inputs
Analog recorders
Module
4 * 4-20 mA outputs
Module 8 relays
Module
logic input
Module 4 relays
16 logic
inputs
8 analog inputs
External
power
supply
USB
link

MX 43
ANALOG AND DIGITAL CONTROLLER
USER GUIDE
NPM43EN
Revision K.0 7
Figure 3: Wall-mounted version MX 43 (left illustration) or rack- mounted version (right illustration).
The following table details the different configurations that are possible, depending on the type
of unit. On each line, it is possible to connect a 4-20mA analog detector or one, or several,
digitally addressable modules.
Maximum number of
Versions
Modules (1)
Detectors
External relays
Logic inputs
Analog ouputs
4 lines 16 16 8 16 16
8 lines 32 32 24 32 32
(1) Gas detectors, 4 or 8-analog output modules, and 16-logic input modules.
Table 1: Summary of the maximum capacity as per the controller type.
The COM 43 Application
This is intended for setting the MX 43 parameters from a Windows®-operated PC. The operation
and use of this application is covered in a special training course.

MX 43
ANALOG AND DIGITAL CONTROLLER
USER GUIDE
8
NPM43EN
Revision K.0
Firmplate
Example:
It contains relevant information with respect to the controller version (CSA or ATEX variants).
Tag.
Description
1. All models:
Name and address of the Manufacturer
Product name
CE marking with identification of the Notified Body that assessed the TELEDYNE
OLDHAM SIMTRONICS manufacturing quality system (0080 – INERIS)
ATEX marking (Performance requirements of gas detection systems for flammable
gases)
Part Number (P/N)
S/N: Seriel number (S:N): the first four digits correspond to the year (YY) and
month (MM) of manufacture
Warning
2. Electrical data: content differs depending on the model
3. For all CSA models (Ord Loc and Haz Loc)
4. Symbol of Marine Certification and number of the Approval Agency that issued the
certificate (MX43M models)
5. Only for CSA Haz Loc approved versions
5
4
3
2
1

MX 43
ANALOG AND DIGITAL CONTROLLER
USER GUIDE
NPM43EN
Revision K.0 9
3Mechanical Installation
This chapter details the mechanical installation of MX 43 and the digital modules.
MX 43 Controller
3.1.1 Location
The MX 43 shall be installed in premises without explosive atmospheres, away from direct
exposure to sunlight, and protected from humidity, dust, and temperature variations. It shall
preferably be located in a monitored environment (guardhouse, control room, or instrument
room, for example).
3.1.2 Attachment of the wall enclosure
Access to the controller must be ensured in the front in order to facilitate adjustments,
monitoring, and cabling. A space of 400 mm is necessary in front of the MX 43 for opening the
door.
(*) rear fixing legs included.
Figure 4: Size of the wall-mounted version.

MX 43
ANALOG AND DIGITAL CONTROLLER
USER GUIDE
10
NPM43EN
Revision K.0
Use 3 fixing screws 4x25 mm for fixing the case support.
Figure 5: Fixing of the wall- mounted version MX 43 with a support plate.
3.1.3 Setting-up of a 19” Rack – 4 U
Access to the unit must be ensured in order to facilitate adjustments and monitoring, and
likewise in the back in order to allow easy access to the different connectors at the rear.
This rack is built into a bay or a standard 19” cabinet. You should leave ½ U (22 mm) of space
above and below the rack so as to assure the proper ventilation of the MX 43.
Figure 6: Size of the rack-mounted version.

MX 43
ANALOG AND DIGITAL CONTROLLER
USER GUIDE
NPM43EN
Revision K.0 11
Digital Modules
The cabling is the subject of the paragraph
Wiring and Electrical Connections
on
page 37.
3.2.1 Gas detectors
Refer to the manual supplied with each detector.
Location
Each detector shall be positioned at ground level, on the ceiling, at the height of the respiratory
tract, or near air extraction ducts, depending on the density of the gas to be detected or
applied. Heavy gases are detected close to the ground, while lighter gases are present along
the ceiling. If necessary, contact
TELEDYNE OLDHAM SIMTRONICS
for any questions
regarding proper detector positioning.
Fixing
The detectors shall preferably be positioned in an accessible place so that inspections and
maintenance can be carried out as well as to ensure the absolute safety of the operators. The
detectors must not be obstructed by anything that will prevent them from measuring the ambient
environment to be checked.
If mounting an OLCT 10N on a vertical surface, position the cable gland downwards.
3.2.2 Other models
Location
The relay modules, logic outputs, analog outputs, and analog inputs are positioned depending
on the installation layout, mandatorily in places free from explosive atmospheres, protected
from humidity, dust, and temperature variations; for example in technical cabinets.
Fixing
These modules shall be mounted on
a DIN rail in a cabinet or in an
electrical cabinet.
For relay modules connected to low
voltage electrical parts, the
installation is carried out according
to the standards in force.
Figure 7: Fixing of a module (relay, logic outputs,
or analog outputs or inputs) on a DIN rail.

MX 43
ANALOG AND DIGITAL CONTROLLER
USER GUIDE
12
NPM43EN
Revision K.0

MX 43
ANALOG AND DIGITAL CONTROLLER
USER GUIDE
NPM43EN
Revision K.0 13
4The MX 43 Controller
The versions in cabinet have differences in the arrangement of the components. See
specific chapter 14 after reading this notice in its entirety.
Overview of the Unit
4.1.1 External view
Rep.
Function
Rep.
Function
A. Monochromatic, back-lit graphic LCD display H. Failure/maintenance indicator
B. Zone 1 status indicator J. Contextual soft keys
C. Zone 2 status indicator K. Alarm release key
D. Integrated siren (option) L. Free identification of zones
E. Integrated flash (optional) M. Strip for locating zones
F. Lock N. Handle
G. Start/Stop indicator
Figure 8: External view of the wall-mounted and rack-mounted versions.

MX 43
ANALOG AND DIGITAL CONTROLLER
USER GUIDE
14
NPM43EN
Revision K.0
4.1.2 Internal view
Figure 9: Internal view of the wall-mounted version (top) and rack- mounted version (bottom).
Rep.
Function
A. LED digital communication status indicators. The information displayed by each red-green diode pair
of a line is interpreted as follows:
LED Status
Significance
Red Green
Fast blinking Fast blinking Normal functioning of the line
- Tx communication request
- Rx: response of digital module(s).
Irregular
blinking
Irregular
blinking
Bad communication quality with at least one module.
Blinks 1X/sec Off Communication failure. Absence or failure of line modules. A
communication failure is signaled by the activation of the
internal buzzer, the presence of the orange
failure
indicator
and via the default relay.
Off Off No digital module active on the line.
B. Optional 24 VDX NiMH battery pack. (not available on MX43S and MX43L
C. Terminal block for the analog card power supply.
Table of contents
Other TELEDYNE OLDHAM SIMTRONICS Controllers manuals
Popular Controllers manuals by other brands

Excelitas Technologies
Excelitas Technologies OmniCure LX500 quick start guide

Danfoss
Danfoss VLT MCD 600 installation guide

Freescale Semiconductor
Freescale Semiconductor HVP-KV10Z32 quick start guide

Avigilon
Avigilon SDC installation guide

Parker
Parker ET Series Maintenance Instructions & Parts List

Ltech
Ltech T3 Series manual