Thenow HSN-J15-Z User manual

1
Shanghai Thenow Purification Technology Co.Ltd
Wine Cellar Cooling Units
Self-contained
User Manual
Thank you for purchasing this “Thenow”product;
Please read this manual carefully before attempting to install, operate or service;
Please retain this booklet for future reference.

2
!!! WARNING !!!
To avoid the risk of electrical shock, property damage, personal injure or
death, please read the following instructions carefully with safety or
warning labels.
*During transportation or moving, please follow the correct direction on the packing case.
*After transportation or moved, it needs to be allowed to stand for more than 24 hours before it can be turned on.
*Do not attempt to carry out any measurement, device replacement or other maintenance work not covered in
this manual, otherwise it may lead to warranty failure, endanger normal operation, extend equipment downtime
and increase additional maintenance costs.
Disconnect electric power from the appliance before performing any
maintenance or repairs, failure to do so could result in death or electrical
shock.

3
1. Product Introduction..............................................................4
2. Dimensions & Technical Data...............................................5
3. Installation & Debugging.......................................................7
4. Introduction of Controller.....................................................15
5. Maintenance..........................................................................18
6. Troubleshooting.....................................................................20
7. Warranty................................................................................21
Table of Contents

4
Wine Cellar Cooling Units Through-the-Wall
Thenow through-the-wall wine cellar cooling unit is specially designed to match the demands in foreign markets,
It is a ductless wine cellar cooling units with evaporator and condenser are housed together in one unit. it offers
a compact design that can be applied to the unique today’s do-it-yourself modern wine cellar or wine wall.
Features:
Compact design, flexible installation;
Quiet and efficient operation;
Build-in wet film pad and PTC heater, better control the temperature and humidity;
Intelligent control panel, famous brand sensors with stable quality, integrated ModBus connection;
Famous brand compressor, safe, stable and low energy consumption;
Traditional Chinese knot design air grille, better heat dissipation.
Working Principle
1.Refrigeration
Using cycling vapor compression refrigeration system,when the compressor work, indraft low temperature and
pressure refrigerant gas from evaporator, compressed by compressor into high temperature and pressure gas,
and then into the condenser to condense into liquid, meantime release heat, after throttling under the function of
the thermal expansion valve, entering into the evaporator and absorbed heat,then evaporate into gas, finally
back to the compressor through the suction tube and complete a refrigeration cycle ; On the other hand,through
changing of refrigerant flow direction, total or partial condensing heat generated from refrigeration can be
exhausted to outside,to achieve the purpose of adjusting the indoor temperature.
2. Dehumidification Principle
When the wet air flows through the evaporator surface, the air temperature will drop, when it falls below the dew
point,the steam in the air will condense out, gathering and drainage of water pipes in the receiving plate, the
controller automatically adjusts the compressor start-up time according to the setting humidity , so as to achieve
the purpose of adjusting humidity.
3. Heating
Electric heating compensation.
4.Humidification
Adopt circulating water wet-film auto control humidification system, wet film is made of Swedish organic polymer
material with sterilization and disinfection function
Product Introduction

5
Dimensions HSN-JT20:
Dimensions & Technical Data

6
Technical Data
Model
Unit
JT20
Cellar Size
Semi Buried
m³
4~7
Insulated*
m³
4~12
Power
V/HZ
220V/50Hz
Cooling
KW
0.72
Heating
KW
1
Air Flow
m3/h
170
Static Pressure
Pa
30
Noise
dB(A)
42
Refrigerant
/
R290
Control
/
PC Full-touch smart control
Temperature
℃
10-18℃, ±2℃
Humidity
℃
50~70%, ±5%
Total Power
KW
1.5
Humidifier
/
Wet-film
Humidity Capacity
Kg/h
1
Dimension (L*W*H)
mm
881*450*379
Drainage
mm
ф20
Note: Cellar inside dry-bulb t=12℃60% Outside dry-bulb t=35℃,wet-bulb t=28℃
Insulated*: Cellar walls and ceiling insulation with 60mm polyurethane.
Cellar size in above sheet is just experience value. There are several factors such as glass, stone, concrete,
insulation, ambient temperature, ventilation etc. which will change the required amount of Kw needed to properly
cool your wine room or wine cabinet. We strongly recommend you contact with us or our distributors beforehand
to help you to choose the model matched. We do not bear the losses caused by the selection errors caused by
the above reasons.

7
Pre Installation Inspection
A. Check the outer packing for breakage.
B. Machine model (nameplate), check whether it is consistent with what you ordered.
C. The appearance of the whole machine is intact.
D. Sit unit upright for at least 24 hours before installation.
Check the Packing Details :
Note: Item 7,8,9 are all optional accessories, if client not confirmed them before ordering, packing details
will not include these items or part of them.
Warning: Our company is not responsible for any accident caused by opening the panel and electric control
cabinet without the permission of the company.
Item No.
Item
Q’ty
Dimension
1
Cooling Unit
1 pc
801×450×379mm
2
User Manual
1pc
A5
3
Control Panel
1pc
90×90mm
4
Head Outside The Wire
1pc
DN15
5
Controller Cable
1pc
3m
6
Flange Mounting Bracket
(Through-the-wall)
1pc
446×425×100mm
7
Supply Air Flange Cover
(Optional)
1pc
399×379×41mm
8
Return Air Flange
(Optional)
1pc
φ196
9
Screw
(Optional)
6pcs
M4
Installation and Debugging

8
Installation
Disconnect electric power from the appliance before performing any maintenance or repairs,failure to do so
could result in death or electrical shock.
Because of potential safety hazards under a certain condition, we strongly recommend against the use of an
extension cord. However, if you still elect to use an extension cord, it is absolutely necessary that it will be a
related national standard LISTED 3-wire grounding type appliance extension cord having a 3- blade grounding
plug and a 3-slot receptacle that will plug into the appliance. The marked rating of the extension cord shall be
220V 15A.
Installation Conditions
1. After the unit is installed, the inclination angle of the installation plane cannot exceed 1 degree, and the
installation bracket or platform should be able to bear the weight of the unit.
2. In order to ensure good ventilation performance of the unit and daily maintenance and repair, it is required to
leave enough space for machine disassembly and maintenance work.
3. There should be no strong magnetism, steam, or dust around the unit, meantime, ensure that there are no
heat sources, corrosion, and combustible gases in the installation area.
4. After the unit is installed, there should be enough heat dissipation space on the condensing side to ensure
ventilation.
* The ventilation and heat dissipation of the unit play a vital role in the normal operation and performance
guarantee of the unit. When the unit is running in ‘constant temperature’ and ‘automatic’ mode, a large amount of
heat will be generated on the condensing side of the unit. In order to dissipate the heat smoothly, the condensing
side of the unit needs to be ventilated well, otherwise it will affect the unit’s overall performance and lifespan. If
there is no ventilation on the condensing side of the unit, it is necessary to install an exhaust fan for forced
ventilation.

9
5. To avoid any air leakage, before install the unit, foam tape needs to be placed in the bottom and side of the
unit.
6. Working environment: Temperature 5℃-35℃,Humidity RH<80%
7. Recommend air duct: A- Heat-insulating phenolic board, thickness 15~20mm
B- Stainless steel duct, 20mm insulation
8. When connecting the air duct, supply air flange cover and return air flange are recommended to choose.The
connection between the air duct and the unit should be sealed without air leakage.
9. If the unit is installed in a high-temperature and high-humidity environment, it is recommended to paste rubber
and plastic insulation cotton with a thickness of more than 10mm on the surface of the unit to avoid condensation
on the surface of the unit.
10. If the unit is connected to the air duct to supply air, it must be ensured that the pressure loss of the air duct
does not exceed the static pressure outside the unit. (It is recommended that the total length of the air duct
should not exceed 6 meters, and the air flow in the air duct should not exceed 3m/s.) If the condensing side of
the unit is installed outdoors, an air conditioner rain cover should be installed.
In order to avoid fire or electric shock hazard, please do not expose the
equipment to damp environment.
Installation Steps
1. Mounting Tools
2. Make sure installation location
Choosing the wall surface where the unit will be installed, and find out the position of the wall studs. The unit
installation should avoid the wall studs;
Item No.
Item
Photo
Item No.
Item
Photo
1
Level
3
Screwdriver
2
Hammer
4
Saw

10
Make sure the installation position of the unit on the wall, and the distance from the top of the unit to the ceiling
shall not be less than 100mm.
Mark hole location for the unit,outline a rectangle 412mm(width) by 391mm(height) where the unit will be placed
into the wall.
Next, using a saw cut the hole in the drywall, Be careful not to cut into any electrical lines or plumbing.
3. Insert the mounting flange bracket
Slide the flange mounting bracket into the hole so that the flange is flush with the wall, and fixed it firmly to the
wall with screws.
Make sure the mounting bracket flat without tilted, using airtight sealant or caulking seal the flange sides and
bottom to the wall as needed.
4. Fixed the mounting flange bracket
Through the 8 fixing holes on the front of the flange bracket, use screws to fix the flange on the wall, make sure
that the screws are flush with the flange surface of the bracket, and must not be over-tightened or over-loose.
5. Mounting the unit
Slide the unit in along the mounting flange bracket. Slide the condensing fan side of the device into the bracket
until the desired depth is reached, making sure that the humidification solenoid valve and power cord of the
device do not touch the flange of the bracket.
6. Seal all cracks and gaps
Seal all cracks and gaps around the unit with an airtight sealant or caulking to prevent air leakage and movement
of the unit
7. Attach the condensate drain line
Note: The drain line must be connected well before starting the unit.
There is a condensate drain hole at the bottom of the unit on the condensation side, and the diameter of the
condensate drain is DN15
a. It is recommended to connect the water seal at the bottom of the condensate drain pipe, and the other end of
the drain pipe should be placed in a bucket or directly connected to the drain pipe;
b. If the other end of the drain pipe is placed in a bucket, the bucket must be emptied in time to avoid water

11
overflowing the bucket or prevent mold from water growing. If the machine runs for a long time, it is
recommended to connect the drain pipe to the open floor drain or sink.
c. The drain at the bottom of the unit needs to be connected to a water seal. The size of the water seal is shown
in the attached picture (users prepare the water seal by themselves).
8. Connect the water inlet pipe
Note: The water inlet pipe for humidity must be connected well before starting the unit.
There is a humidification water inlet interface on the right side facing the air outlet of the unit, and the diameter of
the humidification water supply pipe is DN08
a. Connect the manual water flow regulating valve to the humidification water inlet pipeline.
b. Purified water is preferred for humidification. If there is no pure water, tap water can also be used. Avoid
limescale as much as possible, or it will affect the humidification effect.
c. To better control the wet-film water inlet flow rate, electromagnetic water valve and water flow gauge are
suggested to be installed. Otherwise, the water will always be supplied to the machine in a normally open state,
which will cause the equipment to leak and fail to operate.
Below suggested water flow rate of Thenow self-contained cooling units for your checking: ( Unit: L/M)
Note: Make sure the smooth drainage too.
Model
HSN-J15-Z
HSN-JC8
HSN-JT20
Inlet Water Rate
0.5
1
1.8

12
Common Mounting Methods:
HSN-JT20 I: Through-the-wall

13
HSN-JT20 II : Duct Work

14
Online Debugging
1. Preparation work before starting the unit
a. Confirm that the power supply of the user distribution box is single-phase 220V, the fluctuation range does not
exceed 10%, and the capacity of the distribution box meets the unit use requirements;
b. Refer to the internal electrical schematic diagram of the unit to complete the wiring, and at the same time
ensure that the unit is effectively grounded;
c. Before starting up and running, make sure that the unit has been installed correctly, the air supply outlet and
the return air inlet have been sealed to ensure no air leakage, no obstruction of condensation air intake,
sufficient heat dissipation space, and the controller panel has been installed correctly;
Condenser Airflow Pathways Supply and Return Airflow Pathways
d. Connect well the humidification water pipe, the humidification water supply is smooth, and adjust the manual
water valve switch to make the water flow appropriate (customer-provided manual water valve switch);
e. The drain at the bottom of the condensing side is connected to the water seal, and the water seal drain is led
to an empty bucket or an open floor drain or sink.
After everything is in good condition, perform the following operations:
1.) Power the machine.
2.) Turn on the unit. Set the unit running mode at ‘Auto’ , input the setting temperature and humidity, refer to
controller functions in this manual.
3.) Testing the fan. Factory default is ‘AUTO’ fan operation, under this the fans runs continuously between the
two speed when the unit is calling for cooling. Users can also change the fan operation from ‘AUTO’ to ‘Manual’

15
operation, choosing it running at high speed or low speed freely.
4.) Running the unit. Check unit to confirm the compressor is running, such as the hum of the compressor or cool
air leaving the unit. Check for any unusual noise or vibration, such as clanking or rubbing.
After the machine runs for 30 minutes or several hours, up to a day or more:
1. Check the alarm record. If all functions work well, no alarm record will be generated.
2. Check the machine for leaks.
3. Check whether the temperature is lower than that when the machine is started. Generally, the coil temperature
is reduced by 5-14℃as the normal range.
4.If the cooling of the unit can operate normally and there is no water leakage, the debugging work is completed.
Note: After transportation or moved, it needs to be allowed to stand for more than 24 hours before it can be
turned on.
Controller Introduction:
CK-4C-86 series controller is a new type of controller to realize intelligent control of constant temperature and
humidity for a wine cellar and wine cabinet cooling units,which is widely used in precise temperature control
places with small volume.
The controller adopts 4-inch large -screen colorful display technology,timing control,automatic/manual control of
air flow speed , automatic operation of the appropriate air flow speed , comfortable energy saving , accurate and
reliable.
Functional features:
1. With 4-inch capacitive full-touch display, clear picture and easy to operate.
2. Real-time display of temperature, humidity and clock.
3. Timing control.
4. Fan speed manual/automatic control selection.
5. Multiple operating mode options.
6. Built-in advanced parameter settings,manufacturers can freely set according to different customer needs.
7. Standard 86 mounting bottom case for quick and easy installation.
8. Power off and restart function.
9. Alarm can be remembered.
Introduction of Controller

16
Technical Specifications
Power Supply
PCB:AC220V±10% 50/60HZ
Display:DC12V
Shall Material
Flame retardant ABS+PC
Power
<12W
Pich of Installation
60mm
Size
PCB:123mm×85mm
Display:91mm×90mm
Storage Environment
-10~~70℃5%~~95%RH
Working Condition
-10~~70℃5%~~95%RH
1. Remove the plastic frame and screw from the packaging box,and then install and fix the plastic frame to the
86 mounting box inside the wall after the wire is threaded out of the plastic frame.
2. Correct wiring according to electrical connection diagram and wiring marking.
3. Snap the product lower point to the plastic frame,then press and hold the upper part of the product into the
plastic frame.
4. Confirm whether the shell is fastened and the installation is completed.

17
Functions:
1.Turn ON/OFF the unit
2.Setting
3.Setting temperature
4.Setting humidity
5.Running mode display
6.Coil temperature
7.Running Mode Setting
8.Fan running mode(Manual/Auto)
9.Fan speed
10.Cellar temperature
11.Cellar humidity
Note: Because all Thenow Cooling Units are using same displayer now, for the single cooling unit like JC8,
some functions indicating above are not available. Very regretful for the troubles may bringing to you.
Turn system ON/OFF
Touch the switch icon in the lower
left corner to turn on or off the unit
Color red is on and green is off
Set temperature
1. Touch icon ‘Set'
2. Find 'Temperature' , click to enter
and set temperature
Set humidity
1. Touch icon ‘Set'
2. Find 'Humidity' , click to enter and
set humidity
Set time
1. Touch icon ‘Set'
2. Find 'Time' , click to enter and set
time

18
Mode
Touch icon 'Mode' to choose the
running mode, default value is 'Auto'
Fan Running Mode
Touch icon next to the switch,
choosing the running mode of the
fan at 'A' or 'M'
(A-Auto running speed,
M-Selecting running speed
manually)
Set the fan speed
(Only available at the
fan work under
“Manual” running
mode)
Touch the fan icon to change the
fan speed
1、Using Requirements
(1) Working conditions: Surrounding temperature at 5℃-35℃, relative humidity lower than 90% ;
(2) Please make certain power supply is specified voltage, it’s strictly prohibited to operate equipment with phase
missing or under voltage;
(3) If the equipment has not been used for a long time ,please make sure to turn off the power.
2、Cleaning and Replacing
Disconnect electric power from the appliance before any operation, otherwise there will
be the risk of electric shock.
1. Because the temperature probe is a sensitive element,in dusty place,please use low pressure water to clean
regularly (for example,with the dust ball blowing wash),when the accuracy become poor, please correct or
replace;
2. The return air outlet of this product is equipped with a filter to filter the dust in the wine cellar. The air filter
Maintenance

19
should be cleaned at least once every six months under the running environment of the wine cellar.
The cleaning steps are as follows:
a. Please unplug the power supply without taking out the unit, as shown in the figure below, first remove the air
filter cover shown in number 4 in the figure.
b. As shown in No. 3 in the figure below, take out the air filter to be cleaned, clean it and dry it. After cleaning, put
back the filter according to the original method;
c. Install the filter cover (number 4) and fix it firmly.
3. This product uses a wet film for humidification, and the wet film pad need to be replaced every 3 years.
The replacement steps are as follows:
a. Please unplug the power supply without taking out the unit, as shown in the figure below, first remove the front
cover shown in number 1 in the below figure.
b. As shown in No. 2 in the figure below, take out the humidifying wet film pad to be replaced and put in a new
one. Note that the direction and placement of the wet film pad must be the same as the original one without
bending and deformation, otherwise it will directly affect the humidification effect..
c. After the replacement work is completed, install and restore the unit front cover (number 1) and fix it firmly.

20
WARNING
Disconnect electric power from the appliance before performing any maintenance or repairs,failure to do
so could result in death or electrical shock.
If maintenance is needed, wait for 3 minutes after power failure (let capacitor discharge on PCB), and then
open the maintenance door.
The surface temperature of the condenser may be very high. Do not touch it to prevent burns.
Even if the fan and compressor have stopped ,there is still a dangerous voltage at the terminals of the
starting capacitor.
Troubleshooting
Status
Reason
Suggestion
Cooling unit not
running
1. No power.
2. Power cord unplugged.
3. Low voltage.
4. Incorrect or loose wirings.
5. Ambient temperature above 35°C or
lower 5°C.
6. Setting higher than ambient
temperature.
7. Defrosting mode on.
1. Check power at receptacle & fuses.
2. Plug-in power cord plug.
3. Contact an authorized electrician.
4. Check all wirings and connections.
5. Ambient temperature not meet unit working
conditions.
6. Lower temperature setting .
7. Wait 5-30minutes.
Cannot
dehumidification
1. Inlet or outlet air grille is stuck.
2. Air filter is stuck.
3. Refrigerant leakage.
4. Compressor not working.
5. Fan is not working
1. Please check the air grille and clean it.
2. Check air filter.
3. Add refrigerant.
4. Check whether the compressor is normal.
5. Check the fan.
No air exhaust
1.The air supply is blocked.
2. Fan is not working.
1. Check and clean air outlet.
2. Check the fan.
Louder noise
1. Loose parts.
2. Air filter is stuck.
3. The unit is not installed smoothly.
1. Check parts.
2. Clean filter.
3. Install the machine smoothly.
Temperature too
high
1. Setting too high.
2. Improper cabinet seals.
3. Ambient temperature too high.
4. Cabinet/room too large.
5. Fan fault.
6. Refrigerant leakage.
1. Lower setting.
2. Check gasket and door opening.
3. Check installation location.
4. Check for excessive size or the machine
model choice is improper.
5. Check both evaporator and condenser fans.
6. Add refrigerant.
Troubleshooting
This manual suits for next models
2
Table of contents
Other Thenow Wine Cooler manuals
Popular Wine Cooler manuals by other brands

Caso
Caso WineChef Pro 180 operating manual

Southern Enterprises
Southern Enterprises HZ031300TX Assembly instructions

Candy
Candy Wine Cooler Instruction booklet

Respekta
Respekta WKS 49 user manual

montpellier
montpellier WS94SDX Installation and operating instructions

Sub-Zero
Sub-Zero Wolf IW Series Service manual

Guzzanti
Guzzanti GZ-52A instruction manual

Kenmore
Kenmore 461.99619 owner's manual

Electrolux
Electrolux E24WC75HSS Specifications

U-Line
U-Line U-1224WCINT-60B User guide & service manual

Indel Webasto
Indel Webasto isotherm DIVINO THE ONE Install & user's guide

GE
GE MONOGRAM ZDW24ABB Dimensions and specifications