
WWW.THERMOSTAHL.PL
- 8 -
MTX-400 and MTX-400 KTS burner technical documentation
Chimney
The exhaust gas ventilation system is an important component of the entire heating system. For safety reasons, and to
ensure proper operation of the burner and boiler, the chimney structure should be designed and built by persons properly
authorised to do this. The construction and mode of execution of the chimney need to be in line with the relevant local
provisions of construction laws in force.
Chimney line draught
In order to ensure proper operation of the burner, it is recommended that a chimney draught regulator be installed within
the exhaust gas ventilation line. This regulator should be adjusted so that the underpressure in the combustion chamber
during operation would not exceed the value of 0.1 mbar.
Exhaust gas temperature measurement
Exhaust gas temperature measurement should be done using a manual or electronic thermometer, or with the use of an
exhaust gas analyser unit. The measurement is taken through an opening, diameter 8, executed on the exhaust gas
ventilation duct, at a distance of double the duct diameter from the heating appliance.
The temperature sensor should be placed in the centre of the gas stream, where the temperature is highest. the
measured temperature value should be between 160 °C and 240 °C. Above this range, chimney losses begin to increase
and the device efficiency falls.
Basic adjustment procedures of the burner
The burner adjustment work should be done necessarily using results of analyses of the exhaust gases. Only in this way
may it be guaranteed that the best values of combustion are ensured, at the same time adhering to a maximum purity of
the exhaust gases, in order to protect the environment.
In order to execute the exhaust gas analysis correctly, it is necessary to have the following devices at hand:
precise chimney draught sensor
soot analysis pump
carbon dioxide analyser
exhaust gas thermometer.
All the measurement values should be recorded in the burner inspection form. The measurements need to be taken at the
operating temperature of the heating appliance. In case of water-based boilers, the water temperature in the boiler must
be at least 60 °C. A condition of achievement of proper measurement results is tightness of the boiler and the exhaust gas
ventilation line. The measurement opening, diameter 8, should be made downstream from the heating appliance on the
exhaust gas ventilation duct, at a distance of double the diameter of the duct, in which it is made
Spray air pressure setting
The spray air pressure should be set on the reducer, fig. 9,
following the start-up phase. The correct air pressure value
is 1.2 bar. This value is appropriate for the full burner power
capacity range.
Fig. 9