LAN Controller
LAN Controller is a simple, but innovative device which has long been lacking in the mar-
ket network solutions. A small board serves as a web server which presents the various
sensor readings and allows you to remotely control up to 6 outputs. For far rom socket
installation board could be powered by passive PoE. In order to expand the uses of our
Lan Controller we introduced two types of management software (rmware) suitable for
dierent applications. In both versions, in addition to the main page of the Control Pa-
nel from the sensor readings are tabs: Events Cong for programming an array of events,
Scheduler for programming timed events and the Network Cong for all other settings.
Dierences (described further below) between rmware versions are as follows: 2.XX - ISP
version - contains an additional tab to set Watchdog to monitor 5-ve network devices.
3.XX - Home edition - is devoid of tabs Watchdog, but have been added: supports sen-
sor DHT22, reading to 6 temperature probes DS18B20, working digital inputs as bistable
switches - to use wall light switches. Changing the rmware is possible by the user pro-
gram LAN Controller Tools.exe (Windows XP) or via the TFTP protocol - as described in this
manual at p. 25. In Accessory (www.tinycontrol.eu) are presented all sensors and upgrade
kits compatible with Lan Controller.
Examples of applications
ISP
• watchdog function to checking TCP/IP connection and launch outputs if hanging happen
•temperature, supply voltage and person occupancy control in server rooms
•weather condition report on the occasion of IP cameras views
Home control
•home electric stove control (automatically or remote)
•turning on/o home lightening remote, by scheduler or by event, controlling intensity
•turning o TV box if remote is other person hands ;-)
•irrigation control - you don’t need visit your garage to modify irrigation time or you can
turn sprayer precisely in the moment when your favorite neighbor passes near ;-)
Home installations
•temperature controlling and simple automation in your heating system
•temperature and pressure controlling in solar thermal installations
•measurements of heat pump operation
•monitoring of grid voltage and automatic switching to backup with mail notication
•remote control (by LAN or wirelesslan) understands as forwarding command to one of
output of Lan controller from input of other Lan controller
Renewable energy
•measurements of solar cells work
•measurements of wind turbines
•measurements of charging battery
•measurements of power consuming
Agriculture
•Irigation systems
•Animal food processing automatization

manual LAN Controller V2.0 – Firmware: HOME v. 3.13 and ISP v. 2.09 – LANKONT-002
3
www.tinycontrol.eu
RESTARTER, MONITOR, CONTROLLER
FEATURES:
(may vary depending on the rmware version):
•WWW or SNMP v2 management
•rmware upgrade via TFTP
•read data in real time without refreshing page
•possibility switch on/o to 5 relay direct and 1 transistor output up to 1A from page
WWW
•events panel to self-programming by user
•Scheduler (switch on/o output for denite time in week days)
•IP watchdog to ve IP device (only v. 2.09)
•monitoring additional devices eg. PIR sensors
•environmental temperature and supply voltage on board measurement
•temperature and current measurement from connected sensors
•temperature and humidity measurement by DTH22 sensor (only v. 3.13)
•power measurement for DC voltage
•power measurement from grid by elecricity meterer impulse (only v. 3.13)
•possibility to connecting of the additional boards: with 4 switched PoE ports or 4 relays
•set time manualy or by server NTP
•posisibility sensors calibration
•frequency and duty modied PWM output
•remote control: each output of Lan controller setup as server can be controlled remo-
telly by LAN network from inputs of others Lan controllers
•e-mail notication about programmed events
•SNMP TRAP notication about programmed events
•automaticaly send state or value inputs to SNMP server by POST or GET commands
•implemented protocols: HTTP, SNMP, SMTP, SNTP, ICMP, DNS, DHCP.
•supported temperature sensors: PT1000, DS18B20
•support 1wire protocol
We hope that the LAN controller will have new applications not only in the ISP networks,
but most of all as a simple home automation, control the status of any type of installa-
tion, the measurement of renewable energy sources or as a simple measure of the energy
consumption of the various receivers. Therefore, the range of sensors will be expanded to
implement such measurements.
We invite you to visit our website
www.tinycontrol.eu
There you will nd the rmware updates
and information about the new possibilities.

4
manual LAN Controller V2.0 – Firmware: HOME v. 3.13 and ISP v. 2.09 – LANKONT-002
www.tinycontrol.eu
FACTORY SETTINGS
IP address of the module: 192.168.1.100
user: admin
password: admin
TECHNICAL SPECIFICATIONS
•supply voltage: 8÷28 V DC
•power consumption : about 1W
•PoE supply: YES, passive (PoE max. <28V)
•Protection from wrong supply polarization: YES
•interface: ethernet 10Mbit/s
•relay: 255VAC 10A
•operating temperature: –20 to +85 °C
•weight: 50g
•dimensions (in a housing without plugs) 66 x 68 x 40 mm
INPUT/OUTPUT:
•5 ANALOG INPUTS:
temperature, voltage, current (by additional boards) and another physics measurements
•DIGITAL INPUT for 1WIRE bus (connector RJ11):
support for 4
(v. 2.09)
or 6
(v. 3.13)
temperature sensors DS18B20
•DIGITAL INPUT:
support temperature and humidity sensor DHT22
(only v. 3.13)
•4 LOGICAL INPUTS:
for monitoring, as a pulse counter from energy meter
(only v. 3.13)
•1 RELAY OUTPUT:
(NO, NC, C)
•1 TRANSISTOR OUTPUT:
up to 1A
•4 OUTPUTS (Connector IDC10-2):
to switch relays or transistors
•4 PWM OUTPUT:
2,6 KHz do 4 MHz
•measuring the temperature and supply voltage LAN Controller board
•reverse polarization protection

manual LAN Controller V2.0 – Firmware: HOME v. 3.13 and ISP v. 2.09 – LANKONT-002
5
www.tinycontrol.eu
PINS and COMPONENTS DESCRIPTION
Temp. board sensor
Ethernet
10Mbit.
PoE max 28V
IDC10-1
INP3D
INP4D
GND
INP1 - U 0÷7,2 V
INP2 - U 0÷36 V
INP3 - PT1000
GND
OUT5=Usupply
GND
NC
C
NO
Power
max 28V
power LED
relay LED
INP6 - RJ11-
bus
1-Wire for
DS18B20
RELAY OUT0
INP1D
INP2D
jumper pins
IDC10-2
RESET
green LED
orange LED
PIN / Component Description
Power Power supply 8V ÷ 28V DC
power LED Shine LED means power on board
relay LED Shine means relay active
green LED Shine LED means eth link active
orange LED Shine means data transmitted
IDC10-1 Additional outputs, for example, relays
IDC10-2 Additional Inputs / Outputs PWM1÷3
INP1÷4D Logical inputs Low=0~0,8V, High=0,8V~20V
INP4D Also supports a pulse counter (only v. 3.13)
INP1 Input for voltage measure 0 ÷ 7.2V (3.6V if jumper on)
INP2 Input for voltage meas. 0 ÷ 36V
INP3 Input for PT1000 sensor for high temp. measure
GND General ground
OUT5 Transistor output (+), voltage = power supply, max 1A
GND Ground for transistor output (–)
NC Relay OUT0, normally closed contact
C Relay OUT0, common contact
NO Relay OUT0, normally open contact
digital
inputs
}

6
manual LAN Controller V2.0 – Firmware: HOME v. 3.13 and ISP v. 2.09 – LANKONT-002
www.tinycontrol.eu
RELAY BOND:
NO – contact normaly open
C – common contact
NC – contact normaly closed
ATTENTION: In spite of that relay can switch AC voltage 255 VAC 10A, board fail to com-
ply with safety requirements (lack housing, earthing). Therefore that receiver connect
with the assistance safety external relays eg. on DIN bus, controlled by relay on board.
IDC10-1, IDC10-2 and RJ11 (bus 1-WIRE):
NO C NC
RESET BUTTON
Pressing for about 0.5 seconds to change state relays, and withstand longer to near 5 se-
conds (when we’re not logged by the Web module) will reset the module, further deten-
tion for about 10 seconds to change all settings (both network and conguration ) on the
factory, reset conrmation of the settings is fast switching on and o the relay (click-click),
not to be confused with the change of status and exclusion of the relay after a reboot.
User and password: admin
IP: 192.168.1.100
ETHERNET
10 Mbit
PoE max 28 V
POWER
max 28 V
not
use
GND 1-Wire VCC=3.6V
RESET
IDC10-1
9 – VCC
7 – PWM
5 – GND
3 – +3,6 V
1 –
OUT1–10
OUT2 – 8
OUT3 – 6
OUT4 – 4
– 2
IDC10-2
9 – VCC
7 – INP4
5 – GND
3 – +3,6 V
1 – DHT22
INP5 –10
– 8
PWM2 – 6
PWM3 – 4
PWM1 – 2 (only v. 3.13)

manual LAN Controller V2.0 – Firmware: HOME v. 3.13 and ISP v. 2.09 – LANKONT-002
7
www.tinycontrol.eu
SENSORS CONNECT
1. Voltage measurement
INP2
INP1
GND
Measure voltage:
0 ÷ 7.2 V DC
(multiplier 2.0) or
0 ÷ 3.6 V DC
after using jumper
and adjusting the
multiplier (multi-
plier 1.0)
Measure voltage:
0 ÷ 36 V DC
jumper
multiplier
GND
GND – Pin5
Vcc – Pin3
OUT – Pin7
FAULT
Recommended
installation of cables
2. Connecting the current sensor ACS711ex
IP+
IP–
IDC10-1
IDC10-2

8
manual LAN Controller V2.0 – Firmware: HOME v. 3.13 and ISP v. 2.09 – LANKONT-002
www.tinycontrol.eu
Recommended
installation of cables
GND – Pin5
Vcc – Pin3
OUT – Pin7
3. Connecting the current sensor ACS709
IP+
IP–
4. Connecting the sensor LA100-P
– +
72 Ω
INP4
Vcc – Pin9 (12V)
GND – Pin5
IDC10-1
IDC10-2
IDC10-1
IDC10-2

manual LAN Controller V2.0 – Firmware: HOME v. 3.13 and ISP v. 2.09 – LANKONT-002
9
www.tinycontrol.eu
5. Voltage connections to INP5 using a resistive divider
R1
R1
U
U = U1+ U2
U
=
R2
R2
U1
U1
U2
U2
R1+ R2
=R2
U2
R1
U
R2
U2
GND – Pin5
INP5 – Pin10
EXAMPLE
U– Input voltage for the measurement
U2– the voltage at the input INP5 (max. 3.6 V)
for the measurement of up to 36 V, use the divider:
R1= 9 kΩ, R2= 1 kΩ,
for the measurement of up to 360 V, use the divider:
R1= 99 kΩ, R2= 1 kΩ,
As a result of sharing multiplier enter: U/ U2
ACS = 0 – No Reading
ACS = 1.0 – 15A (AC S711e x )
ACS = 2.0 – 30A (AC S711e x )
ACS = 3.0 – 75A (ACS709)
ACS = 4.0 – resistor 0,1Ω
ACS = 5.0 – LA100-P (through resistor 75Ω)
multiplier
6. Set the sensor type INP4 and the value of the multiplier INP5
IDC10-1
IDC10-2

10
manual LAN Controller V2.0 – Firmware: HOME v. 3.13 and ISP v. 2.09 – LANKONT-002
www.tinycontrol.eu
output terminals
of the meter pulse energy
for dierent counters
may dier markings
INP3
GND
PT1000
7. Temperature measurement
8. DHT22 sensor and pulse output from the counter (v. 3.13)
The maximum frequency of counting pulses is 10 pulses per 1 second.
–
+20 21
IDC10-1
IDC10-2

manual LAN Controller V2.0 – Firmware: HOME v. 3.13 and ISP v. 2.09 – LANKONT-002
11
www.tinycontrol.eu
9. PIR motion sensor interface
INP1D÷INP4D
Vcc – Pin9 (9÷24V)
GND – Pin5
setup
operation time
delay setting after which
the loss of movement
can actuated output again
PIR
sensor
Detected
motion
Jumper
setting
Output
low state 0~0,8V
high state 0,8V~20V
IDC10-1
IDC10-2

12
manual LAN Controller V2.0 – Firmware: HOME v. 3.13 and ISP v. 2.09 – LANKONT-002
www.tinycontrol.eu
Management by WWW.
1. Control Panel
Any description
of the measured
physical
quantity,
such as kWh,
L/min, etc.
(only v. 3.13)
Negation for
digital input
for Even Con-
g tripping
(only v. 3.13)
Divider pulse counter
- for example as ours
energy meter sends 1000
pulses per 1 kWh is enter
1000, as it sends 1600
pulses enter 1600, etc.
(only v. 3.13)
Change outputs
state display
Any text
description,
max 8 chars
Reset time – „0” for normal
outputs work (ON/OFF) ,
for time > 0 output change
state and return to state be-
fore after the specied time
in seconds (max 65534).
Value of calibration
- adds to or subtracts
the desired value
Select the type of sensor
connected to the corre-
sponding input
click cause
change relay
state on opposite
(OUT0 relay on
board)
automatic socket
arming at xed
time (two panes:
one - time arming,
second - break
time)
Set State
All output
simultaneously
according to
combo box
Run PWM genera-
tor (when chan-
ging frequency or
ll does not need
to turn o the
generator)
Run Power
measure from
INP3 (voltage)
and INP5 (current)
(only v. 3.13)
Time avera-
ged over
a values
of power
measurement
(in minutes)
(only v. 3.13)
only v. 3.13

manual LAN Controller V2.0 – Firmware: HOME v. 3.13 and ISP v. 2.09 – LANKONT-002
13
www.tinycontrol.eu
The numbers of sensors:
0– inserts 0 value, (then receive a value
from one sensor, positive or negative,
depending on which window (rst or
second) enter zero, and what temp. (+ or –)
indicates a sensor)
3– pt1000
4– temp
6– inp6 (DS18B20)
7– inp7 (DS18B20)
8– inp8 (DS18B20)
9– inp9 (DS18B20)
10 – inp10 (DS18B20)
11 – inp11 (DS18B20)
12 – DTH22 temperature
1.1 ANALOG Inputs State (Control Panel)
Added measurement of temperature die-
rence with the selected temperature sensors
- the value of DIFF in the table.
(enter the numbers of temperature sensors in
the boxes - in the „DIFF” shows the dierence
of their values).
NOTE: The calculation of the value of DIFF is:
[value (+ or –) temp. sensor in field 1] – [value (+ or –) temp. sensor in field 2] = DIFF
Examples:
[+25 °C] – [+5 °C] = +20 °C [+5 °C] – [+25 °C] = –20 °C
[+25 °C] – [–5 °C] = +30 °C [+5 °C] – [–25 °C] = +30 °C
[–25 °C] – [+5 °C] = –30 °C [–5 °C] – [+25 °C] = –30 °C
[–25 °C] – [–5 °C] = –20 °C [–5 °C] – [–25 °C] = +20 °C
[no sensor (typed 0)]– [+10 ° C]= –10 °C
[no sensor (typed 0)]– [–10 °C]= +10 °C
[+10 °C]– [no sensor (typed 0)]= +10 °C
[–10 °C]– [no sensor (typed 0)]= –10 °C
only v. 3.13

14
manual LAN Controller V2.0 – Firmware: HOME v. 3.13 and ISP v. 2.09 – LANKONT-002
www.tinycontrol.eu
Delay of set outputs
after occur events,
in seconds max 65535
2. Events Cong
If checked it responds
to a change of state,
otherwise no reaction (o)
Email text taht
will be send if
events occurance,
max amount char
is 79. Chars „=”
and „&” are not
allowed
The hysteresis
value for
a given input.
Save setings
(ON/OFF
input
you don’t
must save)
inclusion
of an input
After exceeding
a preset value
upwards will be:
the inclusion
of an exit /
PWM generator /
send e-mail /
SNMP Trap
After crossing
the setpoint down
will be:
the inclusion
of an exit /
PWM generator /
send e-mail /
SNMP Trap
tylko
v. 3.13
tylko
v. 2.09

manual LAN Controller V2.0 – Firmware: HOME v. 3.13 and ISP v. 2.09 – LANKONT-002
15
www.tinycontrol.eu
For logical input INP1D ÷ INP4D, e-mail and SNMP Trap notication are send when in-
put level change from 1 to 0 or 0 to 1, additional to email text (at end) will be add value
1 or 0 mark actual input state.
Bistable operation input
- the rst change at INPD
to turn on output, the
second amendment to
disable output
If a value greater than 0,
is at work bistable output
is automatically switched
o after this time,
max 255 seconds
Functional Description Event Table
With this change, you can exibly dene thresholds and intervals in which such slot is to
be enabled / disabled.
If you have the proper checks the condition of a number of sensors is to force the state
OUTX outputs and setting the PWM generator to be that was last registered event.
tylko v. 2.09

16
manual LAN Controller V2.0 – Firmware: HOME v. 3.13 and ISP v. 2.09 – LANKONT-002
www.tinycontrol.eu
3. Scheduler
Format: number output (from 0 to 4),day1,day2,day3,day4,day5,day6, xx:xx:xx(time)
Week Day: Mo - Monday, Tu- Tuesday, We - Wednesday, Th - Thursday, Fi - Friday, Sa - Sa-
turday, Su - Sunday, ## - all week day. Letter size is important.
Example:
0,Mo,12:23:00 - sets out0 every Monday at 12:23:00
1,Sa;Fi,Mo,23:22:03 - sets out1 every Saturday, Friday and Monday at 23:22:03
1,Sa;Fi,Mo,Tu,Su,Th,23:22:03 - sets out1 every Saturday, Friday, Monday, Tuesday, Sunday
and Thursday at 23:22:03
0,##,12:01:30 - sets out0 every week day at 12:01:30
The eect of this may be the inclusion of a relay, switched o or reset (turn on and o) for
a limited period in seconds. (max 65535).
Allows you to
block actions
of Scheduler,
if you change
the input state
INP1D
allows you
to choose which
state INP1D
turn on
the lock

manual LAN Controller V2.0 – Firmware: HOME v. 3.13 and ISP v. 2.09 – LANKONT-002
17
www.tinycontrol.eu
4. Network Conguration
e-mail client set-
tings parameter.
After changing the
settings in order to
test the customer -
should be save your
settings - the „Save
Cong” button.
NOTE:
Some servers (eg. Google) require authentication outgoing mail.
Unfortunately, our device does not provide this functionality.
To send e-mail messages, select the servers that do not require it.

18
manual LAN Controller V2.0 – Firmware: HOME v. 3.13 and ISP v. 2.09 – LANKONT-002
www.tinycontrol.eu
The user name
and password
to access the
module.
You can disable
authorization.
NTP server set-
tings.
Time Interval -
the interval in
minutes betwe-
en synchroniza-
tions.
Fields communi-
ty (password) for
SNMP, must be
the same in your
queries in order
to LK replied.
TRAP Enable –
enabled send
TRAP by SNMP.
HTTP client settings - this is http client conguration.
This tool can easily send at specied intervals (time) value of the input or output states
on a remote server. As an example will use a free server https://www.thingspeak.com,
which allows you to show data in graphs in the timeline. To the contents of the command
to add value I/O, use the „#” and enter the number (a list of numbers p. 20).
Said sample server requires in turn give the command „GET /update?Key=” then the key
to our account (Write API key. Then, in turn attach a data eld &eld=#xx where xx is the
two-digit number of I/O, for example. „&Field=#05”
(NOTE! Record must be double digit, as we enter „5” to write „05”. If you need to send
data from several sensors are elds „eld” separated by commas.
Maximum server name is 31 characters, the maximum string RemouteURL is 127 charac-
ters. The time window, type frequency in seconds with which data will be sent to the se-
rver. In the following example, and for normal queries between „GET” and „/” is a space.
Selecting Auto send and save this state will activate the function.

manual LAN Controller V2.0 – Firmware: HOME v. 3.13 and ISP v. 2.09 – LANKONT-002
19
www.tinycontrol.eu
Enable Automatic Send TRAP – enable
automatic send TRAP by SNMP (above
TRAP Enable must be enable)
Time Interval (max value 10555) – period
to send TRAP from given INPUT,
accuracy 10 s
Time is set individually or with an NTP
server. When set manually each time you
reboot the machine need to set the time.
Output status when you turn on
or reboot the LAN Controller
Assigning an item number
for the currently connected
sensor DS18B20.
1. Connect chosen sensor (others should be removed), 2. Refresh the button „Read ID”, (if it does
not appear ID, reset Lan Controller), 3. Enter the position number and press „Save to” button.
The read ID number will be assigned to the desired position, where „1” corresponds to INP6,
„2” is INP7 ... and „6” is INP11.
To add additional sensors, proceed as described above CONNECTED WITH ONLY ONE,
CURRENTLY added SENSOR.
If you want to remove the assignment, refresh the „Read ID” without sensor (so that the eld
was empt) and memorize the redundant item number („Save to”).
only v. 3.13
only v. 3.13
only v. 2.09

20
manual LAN Controller V2.0 – Firmware: HOME v. 3.13 and ISP v. 2.09 – LANKONT-002
www.tinycontrol.eu
5. Watchdog (only v. 2.09)
Time to respond is 4 seconds,
after this time if no response
one PING failure is counting.
Then if it happen, during wa-
iting for next respond PINGs to
other IP addresses are not re-
alised. It can stretch watchdog
time to other IP addresses.
Amount PING failures, after
this one of three events will be
happen: set (ON) output, set
(OFF) output reset (ON/OFF)
output on denite time (max
65535s).
Selecting this option forces the watchdog
o when in the Event Table occur o / on
the socket.
Upon his return to the previous state out-
put watchdog is started automatically.
(max 65535s).