Reporter GX1122-DGR/H User manual

1
Erbas Teknoloji - Reporter GX1122-DGR/H User Manual
USER MANUAL
GX1122-DGR-rev1.05-1021
GX1122-DGR/H
GSM SMS ALARM & CONTROLLER
www.erbasteknoloji.com
ERBAŞ TEKNOLOJİ
Innovative Solutions

2
Erbas Teknoloji - Reporter GX1122-DGR/H User Manual
SAFETY INSTRUCTIONS
- This user manual contains important notices for installation, usage and safety instructions. Please
read this manual carefully before you start using your device!
- Device is containing a radio transceiver operating on GSM 850/900/1800/1900 MHz bands.
- Do not use device in environments, exceeding temperature limits (device should operate not lower
than -100 C and not higher than +500C).
- Do not use device in chemical or other hazardous environments.
- Device is intended to use in dry and clean places. Do not use device in high humidity.
- Protect your device from dust, moisture, heat and water.
- Do not expose the device to strong vibrations and mechanical impacts.
- Do not attempt to repair device personally.
USE IN ACCORDANCE WITH THE REGULATION
- The use of this device in accordance with the regulation is sending SMS text messages and making
phone calls after an alarm case and controlling remote devices via SMS and phone calls. Other usages
are not permitted.
- Police, fire or healthcare emergency call lines are not permitted to call directly from this device. Do
not configure emergency call numbers into this device.
LIMITED LIABILITY
- The buyer must agree that Reporter devices will reduce the risk of theft, burglary, fire or other
dangers and controls remote devices but do not guarantee any operation against such events.
- Manufacturer will not take any responsibility regarding personal or property or revenue loss while
using devices.
- Manufacturer liability according to local laws does not exceed value of the purchased device.

3
Erbas Teknoloji - Reporter GX1122-DGR/H User Manual
1. DESCRIPTION
Reporter GX1122 is a user friendly and a reliable device which sends you SMS text messages and calls
you in case of input alarm events, restorations and periodically sends heartbeat messages. It also
controls your remote devices via SMS, free phone call and DTMF phone calls.
It includes a lot of useful features like; detailed instant STATUS query, configurable SMS text
messages, configurable input delays, user defined heartbeat periods, alarm call enable/disable,
add/delete admins & users via SMS, relay activation method selection, LED indicators, replaceable
antenna, IP67 water & dust protected industrial enclosure.
GX1122 -DGR has:
-2 x Digital isolated inputs with +3…27 VDC wide range input voltage capacity
-2 x 10A 230VAC high-capacity relays with volt-free NO/NC/COM pins
-8 admin nr capacity
-20 user nr capacity for standard version / 1.000 user nr (H version only) for remote relay control
purposes
Below list shows the alert events from your device:
-Port1 High : Text Message and (optional) phone call ring
-Port1 Low : Text Message and (optional) phone call ring
-Port2 High : Text Message and (optional) phone call ring
-Port2 Low : Text Message and (optional) phone call ring
-Device Activated : Detailed Text Message *
-Keep Alive : Detailed Text Message *
-Status : Detailed Text Message *
* Detailed text message includes: All inputs status, all outputs status, Call mode selection, Alarm
call configuration, Keep alive period and CSQ GSM signal level in dBi.
Note that Reporter devices do not have “voice record” function, so phone calls are used for only ringing
your mobile phone. There is no voice call.
Only a local 850/900/1800/1900 MHz GSM SIM card is required to operate the device. SMS and Call
function is enough for SIM Card. Data or GPRS functions are not required.
All settings and registered admin & user numbers are saved in Reporter’s own memory. So, settings will
not be deleted if power is failed or SIM card is removed/replaced. Device will continue with the last saved
settings & numbers.

4
Erbas Teknoloji - Reporter GX1122-DGR/H User Manual
2. USECASES
2.1. Remote Controlling
This device can be used to control electrically operated devices remotely via SMS Commands or Phone
Calls. With the help of high capacity & operation configurable relays, you may Activate, Deactivate,
Trigger or Time-Based Activate your remote devices. All Admins and Users can use these control
functions.
Use cases might be such as:
-Irrigation systems
-Trigger Gate openers / barriers
-Control Lighting
-Control total electricity of your home/office/plant etc.
-Different kinds of motors and machines and much more…
As soon as integrated relay power is suitable (up to 10A / 240VAC), any kind of
device/machine/system could be controlled with this device. In some cases where required switching
power is higher than the device capacity; then it can still control those devices by some additional
high capacity switching equipment (i.e. contactors).
2.2. Input Monitoring
Any kind of volt-free or +3V…+27VDC voltage ranged sensor/switch/device output could be
connected to Reporter isolated inputs. Thus, Reporter will continuously check for any change on the
inputs, and it will inform all Admins by SMS (optionally Free Phone Call) in case of changes on the
inputs.
Use cases might be such as:
-Burglar alarm systems as a dialer
-Fire alarm systems as a dialer
-Door/window monitoring
-Any sensors like gas/smoke/earthquake monitoring
-Water level monitoring
-Flood monitoring
-Panic alarm monitoring
-Specific electronic devices/system monitoring and much more…

5
Erbas Teknoloji - Reporter GX1122-DGR/H User Manual
3. INSTALLATION
Package includes:
-4 x screws for “Cover Fitting”
-4 x screws for “Wall Mount”
-4 x fixing plugs for “Wall Mount”
-1 x waterproofing fitting
Firstly, unscrew the Cover Fitting screws and then open the top cover.
If you want to mount your device to the wall;
-Place device to the wall
-Point Wall Mount screwing holes (shown below) to the wall
-Drill the wall from pointed places
-Insert fixing plugs into the drilled points
-Screw in the wall mount screws from the screwing points of the device

6
Erbas Teknoloji - Reporter GX1122-DGR/H User Manual
4. GETTING STARTED
4.1. Insert SIM Card
A local SIM card is required to operate the system.
Required SIM card size is NanoSIM (as seen in figure).
SMS and Call (if you require) services should be active on the SIM.
However, Data/Internet/GPRS services are not required.
Before inserting the SIM card, try it with a mobile phone. And then:
oDisable PIN code protection
oSend an SMS to a mobile number for testing
oCall a mobile phone number for testing
After above steps completed, open the screws. And insert SIM card into the device, by pushing it as
shown in below figure.

7
Erbas Teknoloji - Reporter GX1122-DGR/H User Manual
4.2. Connect Inputs and Outputs on Ports
Note: Wires should pass into the holes of the bottom cover! Please check Wiring Diagram!
If you want to apply external powered lines to the inputs; make sure voltage levels are between +3V
and +27V. It is also very important that you need to connect external device’s GND line to Reporter
GND terminal.
If your external equipment is volt-free (i.e. a button, switch, magnetic contact or volt-free relay
output); in this case you may use Reporter’s +12V line to supply your external equipment.
Reporter inputs are digital and isolated.
4.3. Connect Power
Note: Wires should pass into the holes of the bottom cover! Please check Wiring Diagram!
Connect 12V DC power supply into terminal block +12V (positive) and GND (negative/ground).
Two pieces of +12V and two pieces of GND pins are internally
parallel.
Please note external power should be rated at +12VDC and
current should be at least 1000 mA (1A).
5. DEVICE CONFIGURATION
Firstly, make sure “POWER LED” (Red one) is ON. This indicates that external power is ON.
Then check for “NETWORK STATUS LED”.
-Off : Powered off
-Fast Blink : Not ready (registering to network)

8
Erbas Teknoloji - Reporter GX1122-DGR/H User Manual
-Slow Blink : Ready (registered to the network)
Once NETWORK STATUS LED starts blinking slowly; then you are ready to go to next steps.
Note: Device Configuration and Reset is only made by SMS commands. There is no other method.
Below is the table of SMS commands available:
DESCRIPTION
COMMAND
DEFAULT
RANGE
AUTHORISATION
Change Password
PASS:xxxx
1111
0000..9999
ADMIN
Add Admin
ADDA:xxxxxxxxxx
ADMIN
Add User
ADDU:xxxxxxxxxx
ADMIN
Delete Admin
DELA:xxxxxxxxxx
ADMIN
Delete User
DELU:xxxxxxxxxx
ADMIN
Alert Calls Activate
CALL:ON
OFF
ADMIN
Alert Calls Deactivate
CALL:OFF
OFF
ADMIN
Select MOD1 and Trigger Time(x)
MOD1:x
MOD1:2
1..99 secs
ADMIN
Select MOD2
MOD2
MOD1:2
ADMIN
Change SMS Text Messages
PATx:yyyyyyyy#
1..32 chars
ADMIN
Set Input nr(x) Low-to-High Delay
INPHx:y
0
0..99 secs
ADMIN
Set Input nr(x) High-to-Low Delay
INPLx:y
0
0..99 secs
ADMIN
Set Keep Alive (Heartbeat) SMS
Period
KA:x
0 (means
disabled)
0...999
hours
ADMIN
Get Device Status Info
STATUS
ADMIN
Restore Factory Settings
RESET
ADMIN
Activate Relay nr(x)
RLYx:ON
ADMIN & USER
Deactivate Relay nr(x)
RLYx:OFF
ADMIN & USER
Time-based Activate Relay nr(x) for
(y) secs
RLYx:y
0..99 secs
ADMIN & USER
SMS message format is:
Password<space>Command1<space>Command2<space>Command3……
Examples:
1111 ADDA:+901234567890 // Adds an Admin
1111 PASS:4567 CALL:ON // Changes password to 4567 & activates calls
4567 ADDU:+44111111111 ADDU:+44222222222 // Adds two users by using last password
4567 RLY3:5 // Turns ON RLY3 for 5 secs and then turns OFF
4567 RLYALL:OFF // Turns OFF all relays
5.1. Register (Add) Admin Number(s)
Before adding an Administrator (Admin) please be aware of Admins and Users have different
authorizations. Please decide which numbers to add as Admin and which to add User by the help of below
information.
Admin numbers are authorized to make configurations, change & delete settings and reset device, add
& remove users & admins, receive all alert notifications and control device outputs (relays) remotely.
User numbers can only control Relay Outputs via phone call or by sending SMS to the device.

9
Erbas Teknoloji - Reporter GX1122-DGR/H User Manual
Note-1: If there is no Admin registered yet, any number who knows default password may add itself as
Admin.
Note-2: After first Admin is registered to the device; only an existing Admin may add another Admin.
Note-3: Total 8 people can be added as Admin.
Authorization : Admins only (or first number on first use)
Format : Password<space>ADDA:Number
Example : 1111 ADDA:+901234567890
Responses : Process Succeed. // format & password is correct
Process Failed! // format is wrong
Record Succeed. Memory Full // record done but now memory is full
Record Failed! Memory Full // cannot record because memory is full
5.2. Change Password
Authorization : Admins only
Format : Password<space>PASS:NewPassword
Example : 1111 PASS:6666
Responses : Process Succeed. // format & password is correct
Process Failed! // format is wrong
Note: New Password must be always different than “1111”.
5.3. Register (Add) User(s)
Note: Total 20 (1.000 for /H models) people can be added as User.
Authorization : Admins only
Format : Password<space>ADDU:Number
Example : 1111 ADDU:+901234512345
Responses : Process Succeed. // format & password is correct
Process Failed! // format is wrong
Record Succeed. Memory Full // record done but now memory is full
Record Failed! Memory Full // cannot record because memory is full
5.4. Delete Admin
Authorization : Admins only
Format : Password<space>DELA:Number
Example : 1111 DELA:+901234511111
Responses : Process Succeed. // format & pass is correct. Nr exists
Process Failed! // format is wrong
Record Not Found! Process Failed // nr does not exist

10
Erbas Teknoloji - Reporter GX1122-DGR/H User Manual
5.5. Delete User
Authorization : Admins only
Format : Password<space>DELU:Number
Example : 1111 DELU:+901234522222
Responses : Process Succeed. // format & pass is correct. Nr exists
Process Failed! // format is wrong
Record Not Found! Process Failed // nr does not exist
5.6. Alert Calls Activate / Deactivate
Alert Call feature is used if you need a Phone Call to warn you after you receive alert SMS.
These Calls do not include a voice record. It’s a free-call to ring your phone for around 45 seconds.
Alert Calls are DISABLED (OFF) as factory default.
Authorization : Admins only
Format : Password<space>CALL:ON
Password<space>CALL:OFF
Examples : 1111 CALL:ON // enables phone calls
1111 CALL:OFF // disables phone calls
Responses : Process Succeed. // format & pass is correct
Process Failed! // format is wrong
5.7. MOD1/MOD2 Selection (Relay Control by Phone Calls)
To control Relay Outputs by Phone Calls; Reporter has two different mode options.
Only one of them has to be selected. As factory default, MOD1 is selected:
-MOD1 is only used to trigger RLY1 in a predefined period (default: 2 seconds). When you call device;
it will reject the call after a few rings. Then it will Turn ON RLY1 for predefined period and it will
Turn OFF RLY1 after this period. If this mode is selected MOD2 will be disabled.
-MOD2 is used to Turn ON & Turn OFF all available Relays individually via DTMF Call Dial Service.
When you call device; it will pick up and wait you dial Relay Nr and dial “ #/* ” for ON/OFF. If this
mode is selected MOD1 will be disabled.
Authorization : Admins only
Format : Password<space>MOD1:Period
Password<space>MOD2
Examples : 1111 MOD1:6 // select MOD1, set trig. time to 6 secs
1111 MOD2 // select MOD2
Responses : Process Succeed. // format & pass is correct
Process Failed! // format is wrong

11
Erbas Teknoloji - Reporter GX1122-DGR/H User Manual
5.8. Change SMS Text Message Contents
You can change Alarm SMS Text Message Contents according to your requirements. Thus, you will be
able to rename Alarm words instead of remembering which input is connected to which equipment.
Note: Message Content is limited to 32 characters. Upper- or lower-case letters and digits are allowed to
use. Only English letters are accepted according to ASCII.
Content index list is below:
PAT0 : Keep Alive
PAT1…2 : Input1...2 Low-to-High change alert
PAT9…10 : Input1...2 High-to-Low change alert (i.e. Input1 matches with PAT9)
PAT17 : Device Activated (or power restored)
Authorization : Admins only
Format : Password<space>PATx:AlarmText#
Examples : 1111 PAT1:Office Door Opened# // Input1 High alarm content changed
1111 PAT9:Office Door Closed# // Input1 Low alarm content changed
Responses : Process Succeed. // format & pass is correct
Process Failed! // format is wrong
5.9. Input Delay Configurations
As factory default, any instant change on input status will trigger an alert. In some cases, you might
want to add a delay on a specific input change event up to 99 seconds. For example, if you don’t want
to receive alert notifications upon every door open/close event; you may set Input High and/or Input
Low delays to i.e. 60 seconds. Thus, it will not trigger unnecessary alerts and create the alert in case it
left open for at least 1 minute.
Reporter allows you to set these delays on each input individually.
Also, low-to-high and high-to-low events could be set individually as well.
Authorization : Admins only
Format : Password<space>INPHx:Period
Password<space>INPLx:Period
Examples : 1111 INPH2:60 // Input2 High alarm delay is 60 secs
1111 INPL2:0 // Input2 Low alarm delay set to 0
Responses : Process Succeed. // format & pass is correct
Process Failed! // format is wrong
5.10. Set Heartbeat (Keep Alive) Interval Period
You may want to see device status automatically under some periods and make sure everything is
working properly. Reporter’s Heartbeat (or keep alive) feature makes this happen. As a factory default
it is set to 0 hours (which means function is disabled). You may set this between 0…999 Hours (more
than 40 days!).

12
Erbas Teknoloji - Reporter GX1122-DGR/H User Manual
Each keep alive message will include all inputs and outputs current status, mode selection, call
activation, keep alive current interval setting and current GSM CSQ signal level.
Authorization : Admins only
Format : Password<space>KA:Period
Examples : 1111 KA:24 // Set keep alive for once per day
1111 KA:0 // Disable keep alive messages
Responses : Process Succeed. // format & pass is correct
Process Failed! // format is wrong
5.11. Restore Factory Defaults (RESET)
Resetting the device does not mean any performance change on this device. Reset only deletes all
registered numbers and deletes all configurations & password settings. Thus, device will restore itself
into factory settings.
Authorization : Admins only
Format : Password<space>RESET
Examples : 1111 RESET // reset device
Responses : Process Succeed. // format & pass is correct
Process Failed! // format is wrong
6. CHECK DEVICE STATUS (STATUS QUERY)
Anytime, while device is external powered, you may send a Status Query SMS to Reporter. It will reply
to you with detailed current I/O status, some settings and GSM signal level information.
Authorization : Admins only
Format : Password<space>STATUS
Examples : 1111 STATUS // ask status
Responses : INP1:OFF // INP1 is OFF (LOW)
…
INP2:ON // INP2 is ON (HIGH)
RLY1:OFF // RLY1 is OFF (LOW)
…
RLY2:ON // RLY2 is ON (HIGH)
MOD:1 // call mode is MOD1 (trigger mode)
CALL:OFF // alert call feature is disabled
KA:24 // keep alive period is 24 hours
SIGNAL:26 // very good GSM signal (between 0..31)
Process Failed! // format is wrong
7. CONTROL OUTPUTS (RELAYS)
There are three ways to control your relay outputs remotely:
-SMS

13
Erbas Teknoloji - Reporter GX1122-DGR/H User Manual
-Call Trigger (MOD1)
-Call & DTMF Dial (MOD2)
7.1. SMS Method
Authorization : Admins and Users
Format : Password<space>RLYx:ON (* where x is Relay nr)
Password<space>RLYx:OFF (* where x is Relay nr)
Password<space>RLYALL:ON
Password<space>RLYALL:OFF
Password<space>RLYx:Period (trigger in seconds)
Examples : 1111 RLY1:ON // turn on RLY1
1111 RLYALL:OFF // turn off all relays
1111 RLY1:5 // turn on RLY1 for 5 sec. and then off
Responses : Process Succeed. // format & pass is correct
Process Failed! // format is wrong
7.2. Call Trigger Method (MOD1)
MOD1 is only used to trigger RLY1 in a predefined period (default: 2 seconds).
When you call device; it will reject the call after a few rings. Then it will Turn ON RLY1 for predefined
period and it will Turn OFF RLY1 after this period.
If this mode is selected MOD2 will be automatically disabled.
7.3. Call & DTMF Dial Method (MOD2)
MOD2 is used to Turn ON & Turn OFF all available Relays individually via DTMF Call Dial Service.
When you call device; it will hang up and wait you dial Relay Nr and dial “ #/* ” for ON/OFF.
*** If your dials are not detected properly; please make sure you disabled VoLTE feature from your
mobile phone settings (usually under Cellular->Options->Voice&Data->VoLTE). If you still have
problems, please contact your GSM operator.
If this mode is selected MOD1 will be automatically disabled.
Timeout is 30 seconds after last dial. Device hangs up the call after this period.
Dial Format : RlyNr# // turns on (activates) selected relay
RlyNr* // turns off (deactivates) selected relay
Examples : 1# // turns on RLY1
1#2* // turns on RLY1 and turns off RLY2
9# // turns on all relays
9* // turns off all relays
You will hear two beeps if your command is executed successfully.

14
Erbas Teknoloji - Reporter GX1122-DGR/H User Manual
8. TROUBLESHOOTING
TROUBLE
REASON
SOLUTION
Network LED is completely
OFF
No power applied
Make sure you applied external
power and check if power LED is ON
Power failure
LED becomes off after power failure
event
Network LED blinks fast, never
blinks slowly
SIM card not inserted
Remove power adaptor. Insert SIM
card first and then power device.
PIN code not disabled
Remove power adaptor and then
SIM card. Insert SIM card into a
mobile phone. Disable SIM Card PIN
protection from settings. Insert SIM
card to your device first and then
power device.
Signal level not enough / No
network
Change antenna / Change device
location or try with another GSM
operator until finding good signal
level.
I don’t receive replies to my
SMS text messages
SIM card not activated or not
enough credit (for prepaid
cards)
Remove SIM and insert it in a mobile
phone. Make sure SMS services are
working properly
Your mobile phone SMS
services are working over
internet
Disable “SMS Over Internet” feature
from your mobile phone (I.e.:
Disable iPhone iMessage / Xiaomi
MiMessage)
Alarm occurred, I received
SMS but I didn’t receive a Call
Call feature not activated
Check Alert Calls Activate
instructions
SIM card Call service not
activated
Contact SIM card provider
Alarm occurred, I received Call
but didn’t receive an SMS
Network signal was not
enough on Reporter location
or your own mobile phone’s
location.
Check signal level of Reporter.
Sometimes SMS messages are
delivered after some period of its
sent, caused by GSM operators.
Low credit on prepaid card
Check your credit (if prepaid cards
used).
Admins receive SMS/Calls on
alert events, but users don’t
Alert notifications are only
sent to Admins. Users can
only control output relays
Alert notifications are only sent to
Admins. Users can only control
output relays
On MOD2; I dial correct output
nr and then #/* but it doesn’t
turn on/off the target relay
VoLTE (Voice over LTE) or
HDVoice is enabled
- Disable VoLTE from mobile phone
settings
- or switch off cellular network
LTE/4G/5G during MOD2 dial
- or try dialling *#*#86583#*#*
- If above does not help contact your
GSM network operator
On MOD2; I can turn on/off
relays but I don’t hear beeps
during the execution

15
Erbas Teknoloji - Reporter GX1122-DGR/H User Manual
9. TECHNICAL SPECIFICATIONS
GX1122-DGR/H –Technical Specifications
Power Supply
•12V 1000mA (min.) DC Power Supply (NOT included)
Inputs
•2 x Digital & isolated inputs with +3V…+27V range
Outputs
•2 x SDPT relays 240VAC 10A max.
GSM Module
•2G Quad band 850/900/1800/1900 MHz
Antenna
•2dBi Replaceable SMA type antenna
Event Notifications
•SMS / Call: Input Change Events
•SMS / Call: Power Up
•SMS for Keep Alive Messages
•SMS for Status Query
Relay Control Modes
•SMS
•Call Trigger (MOD1)
•Call DTMF Dial (MOD2)
Admin / User Capacity
•8 Admins
•20 Users (1.000 users for H versions)
Configurations via SMS
•Change password
•Add & delete admins and users
•Activate/deactivate alert Call function
•Set call control modes
•Set input delays
•Set keep alive internal
•Change alert SMS contents
•Reset device
Security
•CallerID & Password
Operating Temperature
•-10 0C ~ + 50 0C
Dimensions
•115 x 90 x 55 mm
IP Water & Dust
Protection
•IP67
Package Content
•1 x GX1122-DGR/H GSM Alarm & Controller Device
•1 x User Manual
•4 x Fixing Screws & Fixing Plugs

16
Erbas Teknoloji - Reporter GX1122-DGR/H User Manual
10. NOTES
Device Phone Number
Admin Numbers
User Numbers
Made in Türkiye
Table of contents
Other Reporter Controllers manuals
Popular Controllers manuals by other brands

dixell
dixell XR72CX Installing and operating instructions

JOSTechnik
JOSTechnik HK2.0-R Series Original operating instructions

Stavoklima
Stavoklima DITRONIC User manual, Instructions for Mounting

BENSHAW
BENSHAW EMX4e user guide

Schischek
Schischek RedMax-Y Series quick start guide

Rain Bird
Rain Bird EZ1-D Programming instructions

Smarteh
Smarteh LPC-2.ID1 user manual

Pego
Pego Vision Touch Wellness User and maintenance manual

Carrier
Carrier OPN-OPT-OL Installation and startup guide

cnsat
cnsat Smart Antenna Selector instruction manual

SNT
SNT ACL2 120 Installation, operation and maintenance

Atmel
Atmel AT91 ARM Series Application note