TLV SC-F70 User manual

Multicontroller
SC-F70SC-F70
Pressure Control
Operating Instructions
Manufacturer
172-65280M-00

2
SC-F70SC-F70
Pressure Control Operating Instructions
Table of Contents
Preface....................................................................................................... 3
For Your Safety ........................................................................................ 3
Checking the Model Code and Accessories ............................................ 4
1. Introduction and Installation ................................................................ 5
1.1 How To Use This Book ................................................................ 5
1.2 Setting Feature Jumpers ............................................................... 6
1.3 Attaching to the Panel .................................................................. 8
1.4 Wiring Procedure ........................................................................ 10
2. Using the Panel................................................................................... 15
2.1 Names and Functions on the Panel ............................................ 15
2.2 Guides for Using Keys ............................................................... 17
3. Operation ............................................................................................ 24
3.1 Setting Up the Basic Parameters ................................................ 24
3.2 Test Operation (LOC/MAN Mode) ........................................... 29
3.3 Automatic Operation (LOC/AUT Mode) .................................. 32
3.4 Area Switching Automatic Operation (LOC/AUT Mode) ........ 35
4. Remote Operation (REM/AUT Mode) .............................................. 38
4.1 Remote Analog Input Operation ................................................ 38
4.2 Remote Area Switching Operation ............................................ 41
5. Using Other Convenient Functions.................................................... 45
5.1 Using Alarms. ............................................................................. 45
5.2 Using the Transmission Output................................................. 48
5.3 Using the Communications Function......................................... 49
5.4 Using Other Convenient Features .............................................. 49
5.5 What to Do When Power Is Lost ............................................... 50
6. Summary of Parameter Groups and Areas ........................................ 51
6.1 Parameters ................................................................................... 52
6.2 Areas ........................................................................................... 63
7. Troubleshooting.................................................................................. 64
7.1 Problem Area .............................................................................. 64
7.2 Troubleshooting Errors Displayed ............................................. 69
7.3 Troubleshooting No Error Displayed Problems ........................ 71
7.4 Troubleshooting Valve Control Problems ................................. 73
7.5 Troubleshooting Pressure Sensor Problems .............................. 74
7.6 Troubleshooting Area Switching External Contact Problems .. 76
7.7 Troubleshooting External Analog Input Problems .................... 77
7.8 Troubleshooting Communication Problems .............................. 78
7.9 Troubleshooting Other Problems ............................................... 79
8. Specifications ..................................................................................... 81
9. Product Warranties ............................................................................. 90

3
SC-F70SC-F70
Pressure Control Operating Instructions
Preface
Thank you for choosing the
SC-F70SC-F70
Multicontroller, a multipurpose,
multifunction, easy-to-use controller for your steam system.
About This Book
The multicontroller (hereafter, called the controller) can be used to control
various things, as listed here:
∑Pressure control (These operating instructions)
∑Temperature control
∑Auto-tuning PID control/ heating, cooling PID control
We have prepared a book containing operating instructions for each type
of use.
It is important that you use the correct book for your controller.
When the controller was shipped from our factory, the correct book should
have been packed according to your order, but please recheck it now. This
book contains instructions for using the controller for pressure control.
This book provides, for both inexperienced users and experts, information for
installing and operating your controller, and troubleshooting problems. It
also contains product specifications and warranties.
For Your Safety
∑∑
∑∑
∑Safety mark
Every safety notice in this book is shown with a safety mark ( ).
Please read these notices carefully before proceeding.
Danger: Protecting electrical terminals
This product is designed and manufactured to be used mounted on an
instrument panel and the electrical terminals on the back side of the
controller are left exposed.
Therefore, the user must install a protective cover over the terminals to
prevent electrical shock to the user or damage to the multicontroller.
The book will be updated from time to time according to improvements made to the
product. But if you find a discrepancy between the descriptions in this book and
actual operation, and need help, contact TLV.
!
!
!

4
SC-F70SC-F70
Pressure Control Operating Instructions
Checking Model Code and Accessories
Check to make sure you received the correct model of controller and features,
and that the necessary accessories were enclosed.
1. Model code
The model code label is attached to the side of the controller case. The
label should read:
SC-F70-□*□□
ais one of the following numbers:
2: Pressure control for MC-COS(R)-3 valve
3: Pressure control for MC-COS(R)-16, 15-50mm valve
4: Pressure control for MC-COS(R)-16, 65-150mm valve
5: Pressure control for MC-COS(R)-21 valve
6: Pressure control for MC-VCOS(R) valve
bshows the type of external contact:
N: No external contact feature
A: External analog input
D: External area switching contact input
cshows the communication type:
N: No communication feature
1: RS-232C
4: RS-422A
5: RS-485
2. Accessories
The controller package contains:
1. The controller
2. The Operating Instructions (this book)
3. A mounting hardware set (2 brackets)
4. The Operating Instructions for Communications (When
communication feature is specified)
If the model code differs from your order, or accessories are missing
or damaged, please contact TLV immediately.
a b c

5
SC-F70SC-F70
Pressure Control Operating Instructions
1. Introduction and Installation
This chapter describes how the controller should be set up, mounted, and
cabled.
1.1 How to Use This Book
This chart shows an overview of installation flow, with page numbers for
reference.
⇒ ⇒ ⇒ ⇒ ⇒ ⇒ ⇒ ⇒ ⇒
Setting Feature Jumpers
Attaching to the Panel
Wiring
Setting Up Basic Parameters
Running in Test Mode
Running in Automatic Mode
Running in Remote Mode
Using Other Functions
Troubleshooting
Checking Model Code and
Accessories ∑Reconfirms that you received the correct model
and accessories (see page 4).
∑Customizes the controller with jumpers on a
controller board (see page 6).
∑Mounts the controller on a panel (see page 8).
∑Connects the cable to a control valve, sensor, and
other connectors (see page 10).
∑Turns power on and sets up the basic parameters
(see page 24).
∑Runs the controller in manual mode (see page 30).
∑Runs using areas and parameters in local,
automatic mode (see page 32).
∑Runs using external contacts in remote, automatic
mode (see page 38).
∑Runs using alarms, transmission output, or
communications (see page 45).
∑Resolves problems you may encounter (see page
64).

6
SC-F70SC-F70
Pressure Control Operating Instructions
1.2 Setting Feature Jumpers
The following feature jumpers can be set to customize your controller.
∑To select measurement input type
∑To select analog input (used only with the analog input feature).
These jumpers are set at the factory to your order specifications.
If BOTH of the following conditions are met, there is NO need to check
the jumper setting. You can go to "1.3 Attaching to the Panel" directly.
1. Measurement input uses current mode, or the sensor to be used is a
Danfoss type MBS33M obtained from TLV.
2. Remote analog setting operation is not used.
Warning:
Do not try to use the controller without setting the jumpers correctly
according to your mode of operation. If you do, an unexpected
malfunction may arise.
Use these steps to set the jumpers
1. Make sure the controller is turned off.
2. Remove the controller body from its
case (see Figure 1).
1. While pushing the stopper tab 1
upward,
2. Pull the body by the frame of the
display panel 2 .
3. To identify the two groups of jumpers,
see Figure 2.
Warning:
To prevent damage, do NOT touch any metal parts on the boards
when you do the next step.
4. Using tweezers, remove and insert the jumpers at the appropriate
positions. Refer to Figure 2 for the jumper positions to select
Measurement Input and Analog Input.
Stopper
PARA
AREA
ENT
A.SEL
DISP
MODE
PV
SETAUTREMAT
AL1AL2AL3AL4
FAIL
SC-F70
[Figure 1]
!
!
2
1

7
SC-F70SC-F70
Pressure Control Operating Instructions
1
2
3
4
5
6
1
2
3
4
5
6
1
2
3
4
5
6
Voltage Input
Current Input
Analog Input Selection Jumper
Measurement Input Selection Jumper
Current Input Voltage Input
(High)
MCU Board
1
2
3
4
5
6
Voltage Input (Low)
[Figure 2. Jumper Setting Guide]
5. Restore the body into the case, and make sure it latches firmly at the
stopper.

8
SC-F70SC-F70
Pressure Control Operating Instructions
1.3 Attaching to the Panel
Warning: Do not install the multicontroller in the following conditions:
∑Where the ambient temperature is higher than 50˚C (122˚F) or lower
than 0˚C (32˚F).
∑Where the relative humidity is lower than 20% or higher than 80%.
∑Where corrosive gas is generated.
∑Where strong vibrations and the potential for shock exist.
∑Where there is flooding or splashing of oil.
∑Where there is excessive dust.
∑Where there is any inductive disturbance which adversely affects
electrical instruments.
Controller Dimensions and Panel Cut Sizes
These figures show the sizes of the controller and the panel cut needed
to fit the controller in millimeters (in inches).
!
96(3.780")
96(3.780")
91.8(3.614")
(106)(4.173")
30 (1.181") or more
25 (0.984") or more
100(3.937")
12(0.472")
91.8(3.614")
Panel Cut Sizes
92
+0.8
-0
92
+0.8
-0
(3.622)
+0.031"
-0"
(3.622)
+0.031"
-0"

9
SC-F70SC-F70
Pressure Control Operating Instructions
Procedure for Attaching to the Panel
1. Referring to the previous figures, cut as many square holes in
the panel as are needed for the number of controllers to be
installed.
Note: The panel thickness must be between 1 to 10 mm ( 0.04 to
0.4 inch).
2. Mount the controller into the cut from the front of the panel.
3. Insert one of the brackets shipped with the controller into the
slot on the top of the controller (see Figure 1).
4. With a Phillips head screwdriver, tighten the screw from the
rear of the bracket (see Figure 2).
When no gap is seen between the panel and the controller
tighten one more full turn.
Be careful not to tighten too much, because the controller
case becomes distorted when overly tightened.
5. Repeat steps 3 and 4 to insert the other bracket on the bottom of
the controller and fasten it in place.
[Figure 2]
!
[Figure 1]
Fastening Screw
Bracket Leg Insert

10
SC-F70SC-F70
Pressure Control Operating Instructions
1.4 Wiring Procedure
Refer to the following "Wiring Precautions" and to "Terminal
Configuration" on page 13, to install the cabling.
Warning
Read the following precautions for selecting and wiring cables.
Improper wiring may cause unexpected, intermittent, or difficult to
analyze problems.
Wiring Precautions
1. For input and output signal wire (measurement input, analog input,
transmission output, and control output to the valve):
1.) Lay input and output cables as far as possible from power lines to
the controller or other equipment to avoid noise interference,
especially from inverter power lines as they are liable to produce
interference requiring countermeasures be taken on the inverter
side to suppress noise emission.
2.) Use an electrically isolated receiver when transmission outputs are
utilized. If the receiver is not an isolated type, the connection must
be made using an isolation amplifier.
3.) Use shielded cables for input and output signal cables.
4.) When using shielded cables, to prevent noise from being generated
due to floating capacity and the difference in grounding potential
between the cable core and shield, ground the shield as follows:
a. If the signal source is grounded, ground only the side closest to
the signal source.
b. If the signal source is not grounded, ground the controller side.
!
Signal source Controller
Controller
Signal source

11
SC-F70SC-F70
Pressure Control Operating Instructions
2. For power lines
Wiring of the controller power source should be done so it will not
be affected by noise from power sources. When a source of noise is
nearby and the controller is affected by the noise, use a noise filter.
1.) Certain types of noise filter may not perform properly. Consider
the line voltage, filter frequency characteristics, and other things
before selecting a filter.
We recommend using the ZCB2203-11S filter, manufactured by
TDK.
2.) Be sure to mount noise filters on grounded panels, and use the
shortest cable possible between the noise filter output and
controller power terminal. A filter mounted on a longer cable may
be ineffective.
3.) When power cables and other cables for the controller are
adversely affected by noise, twist the power supply cables together.
The smaller the pitch, the greater effectiveness against noise.
4.) Do not install fuses, switches, or other such items on the cables
between the noise filter output and the controller power terminals,
as this may adversely affect filter performance.
3. For grounding
1.) Use only power cables that conform to local electrical codes.
To ground the controller, use cables with a nominal cross-sectional
area of 2.0 mm2(0.031 sq.in.) or more, use the same contact point
as the contact ground on the actuator, and ground in the shortest
possible distance.
2.) It will take about 3 seconds for the controller to prepare for contact
output when the power is turned on. When using the controller to
send a signal to an external interlock circuit or other circuits, add a
delay relay.
IN OUT
Controller power source Lead Wire
Noise filter
Make interval short
Make as short
as possible
Lead Wire
Controller power
source terminals

12
SC-F70SC-F70
Pressure Control Operating Instructions
4. Other Precautions
1) Use M3.5 crimp terminals with insulating sleeves.
2) Use a time-lag fuse rated for 250 V, 1 A, if you install an external
fuse.
3) Refer to this wire specification table when selecting cables.
Recommended Wire Specifications
Power line
Grounding wire
In, out signal
Wire Specifications
Type
Cabtyre
Cabtyre
2-wire shielded
AWG*
16 or larger
14 or larger
18 or larger
Diameter (mm2)
1.25 or larger
2.00 or larger
0.75 or larger
* American Wire Gage
Warning
Do not turn on power supply to the value with which this controller
will be used until instructed to do so in section 3.1 "Test Operation".
!

13
SC-F70SC-F70
Pressure Control Operating Instructions
Terminal Configuration and Wiring
The next diagram shows a minimum configuration and its wiring. This
is the simplest configuration in which basic operations can be
performed: Using the MBS33M sensor, manufactured by Danfoss,
shipped with the controller from TLV. (Other possible connections are
shown on the next page.)
Warning
1. Do not use unused terminals as relay terminals.
2. There are temperature compensating elements at the bottom of the
terminal marked 21. Be careful not to damage these elements when
wiring cables.
!
Actuator Wiring Terminal
12345
10 11
GND
Shield Cable
Wiring Terminal
+–
Sensor Terminal
1
2
3
4
5
6
7
8
9
10
11
33
34
35
36
37
38
39
40
41
42
43
22
23
24
25
26
27
28
29
30
31
32
12
13
14
15
16
17
18
19
20
21
Control Output Terminals
Current output
Power Terminals
Power
Sensor power
source
1
3
GND
L
N
POWER
AC100-240V
10
11
4-20mA
17
18
4-20mA+DC24V
Controller Power
Power
AC100 - 240V
Shield
[KH15 Sensor]
[Valve Actuator]
Ground
Terminal
2
[Figure 1. Minimum Configuration]

14
SC-F70SC-F70
Pressure Control Operating Instructions
This figure shows all possible connections.
1
2
3
4
5
6
7
8
9
10
11
33
34
35
36
37
38
39
40
41
42
43
22
23
24
25
26
27
28
29
30
31
32
12
13
14
15
16
17
18
19
20
21
Control Output
Terminals
Current output
No.1 Transmission
Output Terminals
No.1 and 2 Alarm
Terminals
Power Terminals
Power
Relay contact
output
Communication Terminals
RS-422A RS-485 RS-232C External Remote Input Terminals
Contact input
Contact Input and
analog input
Sensor Power
Source Terminals
Sensor power
source
Measurement Input Terminals
Current Input with
power source
Current input
Voltage input
LOW Voltage input
HIGH
No.2 Transmission
Output Terminals
No.4 Alarm Terminals
No.3 Alarm Terminals
1
2
3
GND
L
N
POWER
AC100-240V
33
R
(A)
34
R
(B)
35
T
(A)
36
T
(B)
37SG
RS-422A
RD
35
T/R
(A)
36
T/R
(B)
37SG
RS-485
35
SD
36
37SG
RS-232C
12
13
14
15
16
Di1
COM
(-)
Di2
Di3
Di4
12
13
14
15
16
Di1
COM
(-)
0-5V,1-5V
0-10V,0-20mA
4-20mA
17
21
18
19
20
4
5
6
AL1
AL2
COM
NO
NO
7
8
9
NO
NC
COM
10
11
4-20mA
38
39
4-20mA
42
43
4-20mA
40
41
NO
17
18
4-20mA+DC24V
18
19
0-20mA
4-20mA
20
21
0-10mV
0-100mV
0-1V
20
21
18
19
0-5V
1-5V
0-10V
20
21
DC24V
AL3
Relay contact
output
Current output
Relay contact
output
Current output
[Figure 2. Full Configuration]

15
SC-F70SC-F70
Pressure Control Operating Instructions
2. Using the Panel
To run the controller, data must be entered into some areas and parameters in
advance. This chapter shows how to use the keys and how to read messages
displayed on the LEDs, and explains how to enter the necessary data.
2.1 Names and Functions on the Panel
PARAAREA
ENT
A.SELDISP
MODE
SFT AUT
PV
REM AT
AL1 AL2 AL3 AL4
FAIL
SC-F70
: LED Display
: Keys
1
2
3
3
4
5
6
7
8
1
2
4
5

16
SC-F70SC-F70
Pressure Control Operating Instructions
LED Display Functions
∑Shows measured values
∑Shows symbols while setting areas or parameters
∑Shows set values
∑Shows changed values while setting areas or parameters
∑Show the status of the controller
∑
On during control when set values SoFTstart through time
∑On during AUTo mode
∑On during REMote mode
∑Does not light when using pressure control
∑On when a CPU FAILure is detected
∑On when an ALarm condition exists
∑Shows symbol code to indicate what is shown on
Set Value Display
∑Shows status of deviation between set value (SV)
and measured value (PV)
∑On when PV is greater than SV
∑On when PV is less than SV
Name
Measured Value (PV)
Set Value (SV)
Indicator Lamp
SFT
AUT
REM
AT
FAIL
AL1
AL2
AL3
AL4
Symbol Display
Deviation Display
△
▽
No.
1
2
3
4
5
Functions
∑Calls up and scrolls through operational displays
∑Selects an area number
∑Refers to or sets an area group
∑Refers to or sets a parameter group
∑Registers the new setting
∑Increments a setting value
∑Decrements a setting value
∑Changes operation modes
Keys
Name
Display key
Area Select key
Area key
Parameter key
Enter key
Up key
Down key
Mode key
No.
1
2
3
4
5
6
7
8
<
<
A.SEL
AREA
DISP
PARA
MODE
ENT

17
SC-F70SC-F70
Pressure Control Operating Instructions
2.2 Guide for Using keys
This section explains how to use keys to accomplish your specific tasks:
1) If you want to know the controller's target set value, soft start time, or
valve control output during normal controller operation, or you want to
terminate any of the following 2), 3), 4), or 5) key operations:
Go to " Key Operation Flow" on page 18.
2) If you want to select an area number for an operation:
Go to " Key Operation Flow" on page 19.
3) If you want to know or change the values set in a specific area:
Go to " Key Operation Flow" on page 20.
4) If you want to know or change the values set in a specific parameter:
Go to " Key Operation Flow" on page 21.
5) If you want to know or change the mode of operation:
Go to " Key Operation Flow" on page 22.
DISP
A.SEL
AREA
MODE
PARA

18
SC-F70SC-F70
Pressure Control Operating Instructions
DISP
DISP
The value set for the soft-start time is displayed for the first
2 seconds, then the remaining hours for the soft start is
displayed.
<
<
This panel appears only when a soft-start time has been
set. Ramp value is the transient target value in the process
of ramp operation.
The first digit indicates the area number.
DISP
DISP
DISP
DISP
In MAN mode, you can set a new value to control the valve.
DISP
DISP
PARAAREA
ENT
A.SELDISP
MODE
測定値
目標値
PV
SC-F70
PARAAREA
ENT
A.SELDISP
MODE
測定値
ランプ値
PV
SC-F70
PARAAREA
ENT
A.SELDISP
MODE
測定値
ソフト時間
PV
SC-F70
PARAAREA
ENT
A.SELDISP
MODE
測定値
制御出力値
PV
SC-F70
PARAAREA
ENT
A.SELDISP
MODE
測定値
新制御出力値
PV
SC-F70
Other than
status
Measurement value
Target value
Measurement value
Ramp value
Measurement value
Soft time
Measurement value
Value control output Value control output
Measurement value
®®
®®
®Key Operation Flow
At any time, pressing the key displays the following controller
values:
DISP
Note: When you press the key the first time in MAN mode, the
current control value is displayed.
DISP

19
SC-F70SC-F70
Pressure Control Operating Instructions
®®
®®
®Key Operation Flow
The controller provides eight memory areas in which target values and
other control values are stored. The storage location is called an area.
Each push of the key increases the area number sequentially,
and pressing the key selects the displayed area number for the
operation.
Note: When in REM mode, pressing the key is invalid and an
E22 error code appears. Change to LOC mode first, then try
again.
A.SEL
ENT
Area No.
Works in LOC mode only
Confirms selection
A.SEL
A.SEL
A.SEL
A.SEL
A.SEL
A.SEL
ENT
ENT
A.SEL
ENT
A.SEL
A.SEL
A.SEL
PARAAREA
ENT
A.SELDISP
MODE
測定値
目標値
PV
SC-F70
PARAAREA
ENT
A.SELDISP
MODE
測定値
目標値
PV
SC-F70
PARAAREA
ENT
A.SELDISP
MODE
測定値
目標値
PV
SC-F70
PARAAREA
ENT
A.SELDISP
MODE
測定値
目標値
PV
SC-F70
PARAAREA
ENT
A.SELDISP
MODE
測定値
目標値
PV
SC-F70
PARAAREA
ENT
A.SELDISP
MODE
測定値
目標値
PV
SC-F70
Other than
status
Measurement value
Target value
Measurement value
Target value
Measurement value
Target value
Measurement value
Target value
Measurement value
Target value
Measurement value
Target value

20
SC-F70SC-F70
Pressure Control Operating Instructions
PARAAREA
ENT
A.SELDISP
MODE
目標値
PV
SC-F70
PARAAREA
ENT
A.SELDISP
MODE
新目標値
PV
SC-F70
PARAAREA
ENT
A.SELDISP
MODE
新目標値
PV
SC-F70
PARAAREA
ENT
A.SELDISP
MODE
目標値
PV
SC-F70
PARAAREA
ENT
A.SELDISP
MODE
目標値
PV
SC-F70
PARAAREA
ENT
A.SELDISP
MODE
ソフトスタート
時間
PV
SC-F70
PARAAREA
ENT
A.SELDISP
MODE
新
ソフトスタート
時間
PV
SC-F70
PARAAREA
ENT
A.SELDISP
MODE
不感帯
PV
SC-F70
Other than
status
Target value
New Target value New Target value
New Soft start time
Soft start time
Target value
Target value Dead Zone
Instructions:
1. Each push of the key advances the area group number displayed.
2. Each push of the key advances the area item number displayed.
3. When a new value is entered by keys, the decimal point of the
target value starts blinking. When you press the key to register the
new value, the blinking stops.
4. When you press the key the first time, the area number currently in
use is displayed.
AREA
ENT
ENT
AREA
AREA AREA
ENT
AREA
AREA
<
<
ENT
<
<
ENT
ENT
AREA
AREA
ENT
AREA
<
<
ENT
AREA
®®
®®
®Key Operation Flow
Each area contains 10 items, such as SV, tM, AL1 to AL4, oH, oL, Mr,
and db. By pressing the key, you can display the contents of
each item, and in combination with the and
keys, you can change these values.
<
<
ENT
Area No.
AREA
1
1
2
2
Other manuals for SC-F70
2
Table of contents
Other TLV Controllers manuals
Popular Controllers manuals by other brands

BIFFI
BIFFI COMPACT Series Use and maintenance manual

Emerson
Emerson Vilter Vission 20/20 Operation and service manual

Balboa Instruments
Balboa Instruments GL8000 Mach 3 Tech sheet

Keating Of Chicago
Keating Of Chicago UA Flame Master Lo-Temp Griddle Service instructions

Akerstroms
Akerstroms SESAM 800 RXM operating manual

Resource Data Management
Resource Data Management PR0750-MOB Installation & user guide