Toshiba MBSWH-150-F3-KK User manual

MBS (Wallmount) Installation - 64523-009 1
Maintenance Bypass Switch - Wall-Mount Cabinet
Dead Front
Keyed
Mechanical
Interlock
Top Access Panel
Bottom Access Panel
Lifting Eyes
Dead Front
Lockable
Front
Panel
Door
MBS - Door Closed MBS - Door Open
LOTO
(Lock out/
Tag out)
Hasp
MBS BREAKER OPTIONS (All cabinets are ANSI-61 Gray (Munsell No. 8.3G 6.10/0.54.))
Part Number* Dim. W x D x H (in) Wt (lb) UPS kVA Voltage Breaker Size Withstand kAIC
MBSWH-150-F3-KK 30.1 x 10.8 x 42.1 130 15 208/120V 60A 65,000
MBSWH-250-F3-KK 30.1 x 10.8 x 42.1 130 25 208/120V 100A 65,000
MBSWH-300-F3-KK 30.1 x 10.8 x 42.1 130 30 208/120V 125A 65,000
MBSWH-500-F3-KK 30.1 x 10.8 x 42.1 130 50 208/120V 200A 65,000
MBSWH-800-F3-KK 36 x 12.8 x 48.1 280 80 208/120V 300A 65,000
MBSWH-10K-F3-KK 36 x 12.8 x 48.1 385 100 208/120V 400A 65,000
MBSWH-150-S3-KK 30.1 x 10.8 x 42.1 130 15 480V 40A 35,000
MBSWH-250-S3-KK 30.1 x 10.8 x 42.1 130 25 480V 40A 35,000
MBSWH-300-S3-KK 30.1 x 10.8 x 42.1 130 30 480V 50A 35,000
MBSWH-500-S3-KK 30.1 x 10.8 x 42.1 130 50 480V 100A 35,000
MBSWH-800-S3-KK 30.1 x 10.8 x 42.1 130 80 480V 125A 35,000
MBSWH-10K-S3-KK 30.1 x 10.8 x 42.1 130 100 480V 175A 35,000
MBSWH-12K-S3-KK 30.1 x 10.8 x 42.1 130 125 480V 200A 35,000
MBSWH-15K-S3-KK 30.1 x 10.8 x 42.1 130 150 480V 250A 35,000
MBSWH-16K-S3-KK 30.1 x 10.8 x 42.1 130 160 480V 250A 35,000
MBSWH-22K-S3-KK 36 x 12.8 x 48.1 280 225 480V 350A 35,000
MBSWH-30K-S3-KK 36 x 12.8 x 48.1 280 300 480V 500A 65,000
MBSWH-37K-S3-KK 36 x 12.8 x 48.1 280 375 480V 600A 65,000
MBSWH-50K-S3-KK 36 x 12.8 x 48.1 280 500 480V 800A 65,000
* -KK: Keyed Mechanical Interlock Key (2-key)
-KS: Solenoid Key (SKRU)

MBS (Wallmount) Installation - 64523-009 2
GENERAL SAFETY
GENERAL SAFETY INSTRUCTIONS
DO NOT attempt to install, operate, maintain or dispose of this equipment until you have read and understood all of the
product safety information and directions that are contained in this manual.
Safety Alert Symbol
The Safety Alert Symbol indicates that a potential personal injury hazard exists. The
symbol is comprised of an equilateral triangle enclosing an exclamation mark.
Signal Words
Listed below are the signal words that are used throughout this manual followed by their descriptions and associated
symbols. When the words DANGER, WARNING, CAUTION and NOTICE are used in this manual they will be followed by
important safety information that must be carefully adhered to.
Warnings in this manual may appear in any of the following ways:
DANGER Danger warning ─ The word DANGER in capital letters preceded by the safety alert symbol indicates
that an imminently hazardous situation exists, and if not avoided will result in loss of life or serious injury
to personnel.
WARNING Warning warning ─ The word WARNING in capital letters preceded by the safety alert symbol indicates
that a potentially hazardous situation exists, and if not avoided may result in loss of life or serious injury
to personnel.
CAUTION Caution warning ─ The word CAUTION in capital letters preceded by the safety alert symbol indicates
that a potentially hazardous situation exists, and if not avoided may result in minor or moderate injury.
NOTICE Notice warning ─ The word NOTICE in capital letters without the safety alert symbol indicates a poten-
tially hazardous situation exists, and if not avoided may result in equipment and property damage.
Other warning symbols may appear along with the Danger and Warning symbol and are used to specify special hazards.
These warnings describe particular areas where special care and/or procedures are required in order to prevent serious
injury and possible death.
1. Electrical warning ─ The electrical warning symbol is a lighting bolt enclosed in a triangle. The Electrical warn-
ing symbol is used to indicate high voltage locations and conditions that may cause serious injury or death if
the proper precautions are not observed.
2. Explosion warning ─ The explosion warning symbol is an explosion image enclosed in a triangle. The Explo-
sion warning symbol is used to indicate locations and conditions where molten exploding parts that may
cause serious injury or death if the proper precautions are not observed.
EQUIPMENT WARNING LABELS
DO NOT attempt to install, operate, maintain or dispose of this equipment until you have read and understood all of the
product warnings and user directions that are contained in this instruction manual.
Shown below are examples of warning labels that may be found attached to the equipment. DO NOT remove or cover
any of the labels. If the labels are damaged or if additional labels are required, contact your TOSHIBA representative for
additional labels.
The following are examples of the warning labels that may be found on the equipment. The labels are there to provide
useful information or to indicate an imminently hazardous situation that may result in serious injury, severe property and
equipment damage, or death if the instructions are not followed.
DANGER
AC VOLTAGE
This MBS receives power from more
than one source. Disconnect all AC
sources before performing any service
or testing inside this unit
MATERIAL - VINYL OR POLYESTER
TEMPERATURE - MINUS 20 TO 100 deg. C
ADHESIVE - V23 OR EQUIV.
MUST RESIST OIL SOLVENTS
ALL MATERIALS USED MUST
BE UL RECOGNIZED
WARNING AREA BACKGROUND COLOR: ANSI DANGER RED
WARNING AREA TEXT COLOR: ANSI WHITE
TEXT AREA BACKGROUND COLOR: ANSI WHITE
TEXT AREA TEXT COLOR: ANSI BLACK
CORNER RADIUS: VENDOR STANDARD
0.00
WARNING AREA
TEXT AREA
0.00
3.00
1.50
64819
THIS MATERIAL IS THE EXCLUSIVE PROPERTY OF TOSHIBA INTERNATIONAL
CORPORATION AND SHALL NOT BE REPRODUCED, USED, OR DISCLOSED
TO OTHERS UNLESS PRIOR WRITTEN AUTHORIZATION IS OBTAINED.
TITLE: SCALE:
DRAWING NO.:
ECN DATE BY
DRAWN: CHECKED: APPROVED:
DANGER LABEL
MULTIPLE SOURCES
64819
FULL
WLM 3-10-11
REV:
0
13131 WEST LITTLE YORK ROAD, HOUSTON, TX 77041 U.S.A.
ZIR 3-10-11WLM 3-9-11
PN 64821
Remove conduit plate prior to drilling. Metal
chips may fall into breaker orifice and cause
a short circuit.
CAUTION
TEXT AREA 1.50”
4.00"
Risk of electrical shock.
MATERIAL - VINYL OR POLYESTER
TEMPERATURE - MINUS 20 TO 100 deg. C
ADHESIVE - V23 OR EQUIV.
MUST RESIST OIL SOLVENTS
ALL MATERIALS USED MUST
BE UL RECOGNIZED
CAUTION AREA BACKGROUND COLOR: ANSI CAUTION YELLOW
CAUTION AREA TEXT COLOR: ANSI BLACK
TEXT AREA BACKGROUND COLOR: ANSI WHITE
TEXT AREA TEXT COLOR: ANSI BLACK
CORNER RADIUS: VENDOR STANDARD
CAUTION
AREA
THIS MATERIAL IS THE EXCLUSIVE PROPERTY OF TOSHIBA INTERNATIONAL
CORPORATION AND SHALL NOT BE REPRODUCED, USED, OR DISCLOSED
TO OTHERS UNLESS PRIOR WRITTEN AUTHORIZATION IS OBTAINED.
TITLE: SCALE:
DRAWING NO.:
ECN DATE BY
DRAWN: CHECKED: APPROVED:
CAUTION LABEL
MBS
64821
1=1
WLM 9-3-11
REV:
0
13131 WEST LITTLE YORK ROAD, HOUSTON, TX 77041 U.S.A.
WLM 3-10-11
ZIR 3-10-11

MBS (Wallmount) Installation - 64523-009 3
WARNING AREA
TEXT AREA
DANGER
Hazardous voltages are used in the operation
of this equipment and could cause severe personal
injury or loss of life.
The following precautions should be observed to
reduce the risk of injury or death.
HAZARDOUS VOLTAGES
Only qualified technicians familiar with this equipment and the
information supplied with it should be permitted to install and
operate this equipment.
Installation of electrical equipment must be done in
accordance with National Electrical Code and any other state
or local codes. Proper grounding and conductor sizing must
be installed for safe operation.
During operation, keep all covers in place and cabinet
doors shut.
When performing visual inspections and maintenance, if
possible, be sure the MBS is turned off and the incoming
AC feed is turned off and locked out.
If it is necessary to make measurements with the power
on, do not touch any electrical connection points. Remove
all jewelry from wrists and fingers. Make sure test equipment
is in good, safe operating condition.
While servicing, stand on some type of insulation, and be
sure not to be grounded.
Follow the safety instructions given in the equipment manual
carefully and observe all danger, warning and caution notices.
64818
MATERIAL - VINYL OR POLYESTER
TEMPERATURE - MINUS 20 TO 100 deg. C
ADHESIVE - V23 OR EQUIV.
MUST RESIST OIL SOLVENTS
ALL MATERIALS USED MUST
BE UL RECOGNIZED
WARNING AREA BACKGROUND COLOR: ANSI DANGER RED
WARNING AREA TEXT COLOR: ANSI WHITE
TEXT AREA BACKGROUND COLOR: ANSI WHITE
TEXT AREA TEXT COLOR: ANSI BLACK
CORNER RADIUS: VENDOR STANDARD
0.00
0.00
3.75
4.50
The UPS and Battery Cabinet will have hazardous
voltages present even after the AC feed is turned off.
THIS MATERIAL IS THE EXCLUSIVE PROPERTY OF TOSHIBA INTERNATIONAL
CORPORATION AND SHALL NOT BE REPRODUCED, USED, OR DISCLOSED
TO OTHERS UNLESS PRIOR WRITTEN AUTHORIZATION IS OBTAINED.
TITLE: SCALE:
DRAWING NO.:
ECN DATE BY
DRAWN: CHECKED: APPROVED:
DANGER LABEL
GENERAL - MBS
64818
FULL
WLM 3-9-11
REV:
0
13131 WEST LITTLE YORK ROAD, HOUSTON, TX 77041 U.S.A.
WLM 3-10-11
ZIR 3-10-11
UNLESS PRIOR WRITTEN AUTHORIZATION IS OBTAINED.
THIS MATERIAL IS THE EXCLUSIVE PROPERTY OF
BE REPRODUCED, USED OR DISCLOSED TO OTHERS
TOSHIBA INTERNATIONAL CORPORATION AND SHALL NOT
APPROVED BY DATE
CHECKED BY
DRAWN BY DATE
DATE
DRAWING NO.
13131 WEST LITTLE YORK ROAD, HOUSTON, TX, 77041 U.S.A.
TITLE SCALE
OFSH.
ORDER NO.
64820
WALL MOUNT MBS CONNECTION
LABEL SHEET
1=1
11
DISK: PRT
REV: 1
AB C
1/2” BOLT-SAE GRADE 8
TORQUE SPEC: 119 FT LB
ENSURE PROPER PHASING
LINE IN
USE COPPER CONDUCTORS ONLY!
REFER TO INSTRUCTION MANUAL FOR WIRE SIZE
AB C
1/2” BOLT-SAE GRADE 8
TORQUE SPEC: 119 FT LB
ENSURE PROPER PHASING
LOAD IN
USE COPPER CONDUCTORS ONLY!
REFER TO INSTRUCTION MANUAL FOR WIRE SIZE
AB C
1/2” BOLT-SAE GRADE 8
TORQUE SPEC: 119 FT LB
ENSURE PROPER PHASING
UPS IN
USE COPPER CONDUCTORS ONLY!
REFER TO INSTRUCTION MANUAL FOR WIRE SIZE
AB C
1/2” BOLT-SAE GRADE 8
TORQUE SPEC: 119 FT LB
ENSURE PROPER PHASING
UPS OUT
USE COPPER CONDUCTORS ONLY!
REFER TO INSTRUCTION MANUAL FOR WIRE SIZE
B1 CB2
NEUTRAL
SKRU
B1
1
2
T
C
4.50"
3.50"
1.75"
MATERIAL - POLYESTER
TEMPERATURE - MINUS 20 TO 100 deg. C
ADHESIVE - V23 OR EQUIV.
MUST RESIST OIL SOLVENTS
ALL MATERIALS USED MUST BE UL & RoHS RECOGNIZED
TEXT BACKGROUND: ANSI WHITE OR SILVER
TEXT COLOR: ANSI BLACK
KISS CUT TO BORDER LINES
6.00"
9.00"
1.75"
CB3
GND
INITIAL RELEASE 04-11
ZIR
1.00"
1.50"
1.00"
WLM 4-24-13
3/8” BOLT-SAE GRADE 8
TORQUE SPEC: 47 FT LB
3/8” BOLT-SAE GRADE 8
TORQUE SPEC: 47 FT LB
3/8” BOLT-SAE GRADE 8
TORQUE SPEC: 47 FT LB
3/8” BOLT-SAE GRADE 8
TORQUE SPEC: 47 FT LB
ECO 86630 04-13
WLM
WLM 3-9-11
ZIR 4-24-13
IMPORTANT SAFETY INSTRUCTIONS
SAVE THESE INSTRUCTIONS
This manual contains important instructions that should be followed during the installation, maintenance, and operation of
the MBS to assure safe and proper operation.
1. Turn o, lockout, and tagout all power sources before connecting the power and SKRU wiring to the equipment or
when performing maintenance.
2. Verify the MBS is de-energized before removing the cabinet dead fronts.
3. Verify cables and terminals are de-energized before installing cable in terminals.
Qualied Personnel ONLY!
Qualied Personnel is one that has the skills and knowledge relating to the construction, installation, operation, and main-
tenance of the electrical equipment and has received safety training on the hazards involved (Refer to the latest edition of
NFPA 70E for additional safety requirements).
Qualied Personnel shall:
1. Have read the entire operation manual.
2. Be trained and authorized to safely energize, de-energize, ground, lockout and tag circuits and equipment, and
clear faults in accordance with established safety practices.
3. Be trained in the proper care and use of protective equipment such as safety shoes, rubber gloves, hard hats,
safety glasses, face shields, ash clothing, etc., in accordance with established safety practices.
4. Be trained in rendering rst aid.
5. Be knowledgeable of batteries and the required handling and maintenance precautions.
For further information on workplace safety visit www.osha.gov.

MBS (Wallmount) Installation - 64523-009 4
SHIPPING DIMENSIONS
The shipping dimensions for the wall-mount MBS are given in the table below.
Table 1: Shipping Dimensions
ITEM Shipping Dim. (LxWxH)
Medium MBS Case 36” x 47” x 14”
Large MBS Case 41” x 53” x 19”
MOUNTING INSTRUCTIONS
The Toshiba wall-mounted Maintenance Bypass cabinet comes fully assembled. The units are equipped with two lifting
eyes each on the top and bottom of the cabinet. Inside on the back panel are four keyholes sized for 1/2” mounting bolts
(customer supplied) that are for mounting the unit to cement wall or metal channel support. See the appropriate draw-
ing for the support dimensions and spacing.
Removable 14 gage steel access plates are provided at the top and bottom for anchoring power cable conduit.
LOCK-OUT/TAG-OUT (LOTO) HASP
A pair of interleaving tabs are included to provide a LOTO hasp to satisfy applications that require
Lock-out/Tag-out capability. Instructions for installing this hasp are given in Appendix A.
POWER CABLING INSTRUCTIONS
The MBS Circuit Breakers are equipped with terminal bus strips. The terminal bus strips are pre-drilled with standard
2-hole NEMA patterns to facilitate installation of power cables:
Medium Case - 3/8 in. bolt holes on 1.75 in. centers
Large Case - 1/2 in. bolt holes on 1.75 in. centers
Use of NEMA two-hole cable terminations is recommended.
NOTE: Cables, Cable Lugs (Fittings), and fastening bolts/hardware are to be provided by others.
Table 2: Recommended Bolt Tightening Specications
ITEM Fasteners Torque
Medium MBS Case Grade 8, 3/8 in. Bolts 47 ft-lb (5.3 N•M)
Large MBS Case Grade 8, 1/2 in. Bolts 119 ft-lb (13.4 N•M)
The following table lists examples of recommended 2 hole compression type ttings.
Table 3: Compression Fittings: 2 hole, 3/8 in. x 1.75”
Ilsco P/N Description Hole
Diameter
Hole
Spacing
Conductor
Size
Fitting Color
CLND-6-38-134 Long Barrel 3/8 in. 1.75 in. #6 Blue
CLND-2-38-134
CSWD -2-38-134
Long Barrel
Short Barrel
3/8 in. 1.75 in. #2 Brown
CLND-1/0-38-134
CSWD -1/0-38-134
Long Barrel
Short Barrel
3/8 in. 1.75 in. 1/0 Pink
CLND-2/0-38-134 Long Barrel 3/8 in. 1.75 in. 2/0 Black

MBS (Wallmount) Installation - 64523-009 5
Ilsco P/N Description Hole
Diameter
Hole
Spacing
Conductor
Size
Fitting Color
CLND-3/0-12-134 Long Barrel 3/8 in. 1.75 in. 3/0 Orange
CLND-4/0-38-134
CSWD -4/0-38-134
Long Barrel
Short Barrel
3/8 in. 1.75 in. 4/0 Purple
CLND-250-38-134
CSWD -250-38-134
Long Barrel
Short Barrel
3/8 in. 1.75 in. 250 Yellow
CLND-350-38-134 Long Barrel 3/8 in. 1.75 in. 350 Red
CLND-500-38-134 Long Barrel 3/8 in. 1.75 in. 500 Brown
Table 4: Compression Fittings: 2 hole, 1/2 in. x 1.75”
Ilsco P/N Description Hole
Diameter
Hole
Spacing
Conductor
Size
Fitting Color
CLND-6-12-134
CSWD -6-12-134
Long Barrel
Short Barrel
1/2 in. 1.75 in. #6 Blue
CLND-4-12-134 Long Barrel 1/2 in. 1.75 in. #4 Grey
CLND-3-12-134 Long Barrel 1/2 in. 1.75 in. #3 White
CLND-2-12-134
CSWD -2-12-134
Long Barrel
Short Barrel
1/2 in. 1.75 in. #2 Brown
CLND-1-12-134 Long Barrel 1/2 in. 1.75 in. #1 Green
CLND-1/0-12-134
CSWD -1/0-12-134
Long Barrel
Short Barrel
1/2 in. 1.75 in. 1/0 Pink
CLND-2/0-12-134
CSWD -2/0-12-134
Long Barrel
Short Barrel
1/2 in. 1.75 in. 2/0 Black
CLND-3/0-12-134 Long Barrel 1/2 in. 1.75 in. 3/0 Orange
CLND-4/0-12-134
CSWD -4/0-12-134
Long Barrel
Short Barrel
1/2 in. 1.75 in. 4/0 Purple
CLND-250-12-134
CSWD -250-12-134
Long Barrel
Short Barrel
1/2 in. 1.75 in. 250 Yellow
CLND-300-12-134
CSWD -300-12-134
Long Barrel
Short Barrel
1/2 in. 1.75 in. 300 White
CLND-350-12-134
CSWD -350-12-134
Long Barrel
Short Barrel
1/2 in. 1.75 in. 350 Red
CLND-400-12-134
CSWD -400-12-134
Long Barrel
Short Barrel
1/2 in. 1.75 in. 400 Blue
CLND-500-12-134
CSWD -500-12-134
Long Barrel
Short Barrel
1/2 in. 1.75 in. 500 Brown

MBS (Wallmount) Installation - 64523-009 6
Connect the power cables as indicated below.
Verify phasing is correct before applying power.
LINE IN
CB1 CB2 CB3
UPS IN LOAD IN
UPS OUT
Figure 1 - MBS Power Cabling Connections
Phase A B C Phase A B C
Phase A B C Phase A B C
NEUTRAL
GND
N
N
GND
GND
N
N
GND
GND

MBS (Wallmount) Installation - 64523-009 7
SKRU Wiring
If the Wall Mount MBS is equipped with a SKRU (Solenoid Key Release Unit) it comes with the SKRU factory-wired to the
MBS Terminal Strip TB-1. TB-1 is mounted on the lower left side of the MBS.
Complete wiring the MBS TB-1 SKRU to the UPS dry contacts TB before energizing the MBS or UPS. The SKRU is pow-
ered from the load side of the MBS output breaker.
Connect one end of the user-supplied 16-18 Gage twisted pair wiring to MBS TB-1 terminals 1 and 2. Connect the other
end to the UPS “Bypass Enable” dry contact TB terminals. See the gure below.
Figure 2 - MBS Wiring for SKRU
UPS
Bypass Enable
TB
End User Supplied Wiring
(16-18 gage twisted pair)
MBS
TB 1
1
2
VSKRU*
SKRU
L
* MBSWH-xxx-F3-KS: 120VAC
MBSWH-xxx-S3-KS: 24VDC
Table 5: SKRU Point to Point Wiring
From UPS Model Terminal Board To MBSWH Terminal Board
4200FA TB2-11 MBSWH TB1-1
4200FA TB2-12 MBSWH TB1-2
4300 TB3-1 MBSWH TB1-1
4300 TB3-2 MBSWH TB1-2
4400 TB3-1 MBSWH TB1-1
4400 TB3-2 MBSWH TB1-2
G8000 TB1-10 MBSWH TB1-1
G8000 TB1-11 MBSWH TB1-2
G9000 (100-750kVA) IOAU-09 TN2-19 MBSWH TB1-1
G9000 (100-750kVA) IOAU-09 TN2-20 MBSWH TB1-2
G9000 (1000kVA) IOAU-19 TN21-25 - 19 MBSWH TB1-1
G9000 (1000kVA) IOAU-19 TN21-25 - 20 MBSWH TB1-2
LOCK-OUT/TAG-OUT OPTION
An optional pair of tabs can be easily attached to the MBS door and frame to satisfy applications that
require Lock-out/Tag-out capability. Call the factory for additional information.

MBS (Wallmount) Installation - 64523-009 8
KEYED MECHANICAL INTERLOCK OPERATION
The MBS ships with a keyed mechanical interlock or SKRU (Solenoid Key Release Unit) interlock. Operation instructions
for both models are shown below, and also displayed on the MBS breaker panel.
NOTICE: Both MBS procedures are make-before-break. Ensure the UPS is in BYPASS mode before switching to
Maintenance Bypass.
Failure to switch the UPS to BYPASS before engaging the MBS may result in damage to the MBS, UPS or both.
3-Breaker MBS with Keyed Mechanical Interlock
Place MBS in Maintenance Bypass Mode
1. Transfer the UPS to static bypass. Verify UPS is in Bypass.
2. Unlock CB2.
3. Close CB2 (Maintenance Bypass Breaker)
4. Open CB3 (UPS Output Breaker)
5. Remove the key from CB2, and insert it in CB3.
6. Lock CB3.
7. Open CB1.(UPS Input Breaker).
Place MBS in UPS Online Mode
1. Close CB1 (UPS Input Breaker).
2. Turn UPS ON. Verify UPS is in Bypass.
3. Turn ON all UPS Battery DC breakers.
4. Unlock CB3.
5. Close CB3 (UPS Output Breaker)
6. Remove the key from CB3, and insert it in CB2.
7. Open CB2 (Maintenance Bypass Breaker)
8. Lock CB2.
9. Return UPS to Online Mode.
3-Breaker MBS with SKRU (Solenoid Key Release Unit)
Place MBS in Maintenance Bypass Mode
1. Transfer the UPS to static bypass. Verify UPS is in Bypass.
2. Turn and extract key A-1 from the SKRU and insert the key in CB2.
3. Unlock CB2.
4. Close CB2 (Maintenance Bypass Breaker)
5. Open CB3 (UPS Output Breaker)
6. Lock CB3.
7. Remove key B-1 from the lock on CB3, and insert it in the SKRU and turn.
8. Open CB1 (UPS Input Breaker).
Place MBS in UPS Online Mode
1. Close CB1 (UPS Input Breaker).
2. Turn UPS ON. Verify UPS is in Bypass.
3. Turn ON all UPS Battery DC breakers.
4. Turn and extract key B-1 from the SKRU. Insert it in the lock on CB3.
5. Unlock CB3.
6. Close CB3 (UPS Output Breaker)
7. Open CB2 (Maintenance Bypass Breaker)
8. Lock CB2. Remove key A-1 from CB2, and insert it in SKRU and turn.
9. Return UPS to Online Mode.

MBS (Wallmount) Installation - 64523-009 9
PARAMETERS 15/160kVA
UNITWEIGHT(LBS/KGS) 130/58.9
VENTILATIONREQTS. NONE
FINISH GRAY
Figure 3 - Dimensional Drawing for 0-200A MBSWH

MBS (Wallmount) Installation - 64523-009 10
PARAMETERS 80/500kVA
UNITWEIGHT(LBS/KGS) 280/127.0
VENTILATIONREQTS. NONE
FINISH GRAY
Figure 4 - Dimensional Drawing for 300A+ MBSWH

MBS (Wallmount) Installation - 64523-009 11
Appendix A - Lock-Out/Tag-Out Hasp Installation
The Toshiba wall-mounted MBS ships with a LOTO (Lock-Out/Tag-Out) hasp to be installed by the User in those applica-
tions requiring that capability.
Installation equipment required:
#2 Phillips Screwdriver
1. Twist the inner tongue and outer loop sections of the hasp in opposite directions, until the 0.5 mm join separates.
2. use the factory supplied hardware to mount the outer loop of the hasp on the MBS door. The two mounting holed for
the screws is located just aoe the door latch.
3. Use the factory supplied hardware to mount the inner tongue of the hasp on the inner edge of the door frame. The
mounting holes are located just above the goor latch.
4. After mounting both parts of the LOTO hasp, close th door carefully and verify the hasp loop slips over the hasp toun-
guer without interference.
5. This completed the installation of the LOTO hasp.


SOCIAL INFRASTRUCTURE SYSTEMS GROUP
POWER ELECTRONICS DIVISION
13131 West Little York Road, Houston, Texas 77041-9990
Tel (713) 466-0277 Fax. (713) 466-8773
US (855) 803-7087 Canada (800) 872-2192
https://www.toshiba.com/tic/industrial/uninterruptible-power-systems
Printed in the U.S.A.
This manual suits for next models
18
Table of contents
Other Toshiba Switch manuals