CLCH-SVX06A-EN • T-Series Climate Changer Air Handler IOM 19
Unit Dimensions and Weights
Nominal airflow115,000 17,500 20,000 25,000 28,500 33,000 40,000 50,000
Airflow at 625 fpm217,500 19,963 22,569 30,206 35,937 40,625 44,234354,9583
Unit size 30 35 40 50 57 66 80 100
Height (inches) 63.5 72.75 72.75 85 97 97 112 124.5
Width (inches) 97 102 115 126 126 141 141 156
Coil, small
with 2-row UW 11 11.5 11.5 14.5 14.5 14.5 14.5 14.5
398 475 518 711 724 842 945 1196
Coil, medium
with 8-row UW 15.5 16 16 n/a n/a n/a n/a n/a
826 973 1082 n/a n/a n/a n/a n/a
Coil, extended-medium
with 8-row UW 19 20 20 20 20 20 20 20
924 1103 1231 1546 1560 2018 2319 2807
Coil, medium-large
with 10-row W 24.5 31 31 31 31 29.5 29.5 29.5
1414 1735 1939 2396 2401 3103 3585 4368
Coil, large
with 10-row W 40 48 48 48 48 n/a n/a n/a
1673 2041 2264 2781 2811 n/a n/a n/a
Coil, electric heat540 48 48 48 48 29.56n/a n/a
934 1146 1239 1370 1396 1280 n/a n/a
Coil, integral face-and-
bypass740 48 48 48 31 29.5 29.5 29.5
1346 1652 1713 2436 2511 2529 2716 3258
Face-and-bypass,
internal 15.5 16 16 19 19 19 19 19
359 444 500 670 681 778 878 1030
Face damper 15.5 16 16 19 19 19 19 19
376 471 526 638 766 927 1033 1195
Humidifier 31 32 32 29 29 29 43.5 43.5
658 796 872 1013 1293 1547 2135 2388
Moisture eliminator 11 11.5 11.5 14.5 14.5 14.5 14.5 14.5
324 392 434 617 626 738 815 958
Fan, horizontal
discharge854.75 62 62 68.5 68.5 84 92 96
1924 2525 2757 3473 3320 4382 4998 5928
Fan, bottom front
discharge865.75 73.5 73.5 83 83 84 92 96
2190 2791 2704 3680 4254 4606 5518 6448
Diffuser 15.5 16 16 19 19 49 54 60
209 312 342 470 481 975 1100 1338
Discharge plenum 40 48 48 48 48 49 54 60
379 529 569 631 658 713 840 1009
Gas heat980 96 96 110 n/a 112.5 108 104
2383 2964 3051 3736 n/a 5008 4884 4816
Side inlet hood
(add to width) 33.25 37.625 35.75 43.13 43.13 48.38 56.38 67.25
105 124 131 170 195 220 273 352
Back inlet hood
(add to length) 27.63 31.25 32.25 34.63 34.63 34.63 38.25 41.25
197 238 266 291 345 368 414 505
Exhaust hood (add to
width or length) 33.31 37.625 35.79 43.18 43.18 48.34 56.35 67.19
70 84 85 113 122 144 183 242
Unit end panels
(add to length) 6666666 6
443 548 605 726 799 928 1029 1211
Note: (1) Nominal airflow is based on 500 fpm through a nominal coil (i.e. 500 x unit size 8 = 4000 cfm). (2) Airflow @ 625 fpm through the flat filter (maximum
filter velocity) (3) Airflow is the maximum recommended velocity through a back inlet hood. (4) Size 3 mixing boxes without filters are 24.75 inches long.
(5) For sizes 3 - 57 blow-thru applications, electric heat sections require, at a minimum, a large section immediately downstream and a medium section
immediately upstream. (6) For size 66 blow-thru applications, electric heat sections require, at a minimum, a medium-large access section downstream and
a medium section immediately upstream. (7) IFB coil sections require a section immediately downstream: (at a minimum) a large section on size 3, medium
section for sizes 6 to 100. (8) Fan section weights include the heaviest fan with the largest ODP motor available.(9) Lengths and weights of gas heat sections
are with the largest capacity burner. Refer to the T-Series Air Handler Gas Heat Quick Select (CLCH-SLB005-EN) or the TOPSS selection program for detailed
dimensions.
Table 4. Section dimensions (inches) and weights (pounds) - unit sizes 30-100