Trane E50 Series Installation and operating instructions

SSAAFFEETTYY WWAARRNNIINNGG
Only qualified personnel should install and service the equipment The installation, starting up, and servicing of heating, ventilating, and air-conditioning
equipment can be hazardous and requires specific knowledge and training Improperly installed, adjusted or altered equipment by an unqualified person
could result in death or serious injury When working on the equipment, observe all precautions in the literature and on the tags, stickers, and labels that
are attached to the equipment
April 2021 BBAASS--SSVVXX007733CC--EENN
Installation, Operation, and Maintenance
E50 Series
Compact Power and Energy Meter
Modbus E50C2-T2
for use with Split Core and Solid Core CTs
PN: X13690277002

©2021 Trane BAS-SVX073C-EN
Introduction
The E50 DIN Rail Power Meter provides a solution for measuring energy data with a single
device Inputs include Control Power, CT, and 3-phase voltage The E50 supports multiple output
options, including solid state relay contacts and Modbus The LCD screen on the faceplate allows
instant output viewing The meter is housed in a plastic enclosure suitable for installation on T35
DIN rail according to EN50022 The E50 can be mounted with any orientation over the entire
ambient temperature range, either on a DIN rail or in a panel The meter is not sensitive to CT
orientation to reduce installation errors
Copyright
This document and the information in it are the property of Trane, and may not be used or
reproduced in whole or in part without written permission Trane reserves the right to revise this
publication at any time, and to make changes to its content without obligation to notify any
person of such revision or change
Trademarks
All trademarks referenced in this document are the trademarks of their respective owners
Warnings, Cautions, and Notices
Safety advisories appear throughout this manual as required Your personal safety and the
proper operation of this machine depend upon the strict observance of these precautions
The three types of advisories are defined as follows:
WARNING
Indicates a potentially hazardous situation which, if not avoided, could result in
death or serious injury.
CAU
TION
Indicates a potentially hazardous situation which, if not avoided, could result in
minor or moderate injury. It could also be used to alert against unsafe practices.
NOTICE
Indicates a situation that could result in equipment or property-damage only
accidents.
Important Environmenta Concerns
Scientific research has shown that certain man-made chemicals can affect the earth’s naturally
occurring stratospheric ozone layer when released to the atmosphere In particular, several of the
identified chemicals that may affect the ozone layer are refrigerants that contain Chlorine,
Fluorine and Carbon (CFCs) and those containing Hydrogen, Chlorine, Fluorine and Carbon
(HCFCs) Not all refrigerants containing these compounds have the same potential impact to the
environment Trane advocates the responsible handling of all refrigerants-including industry
replacements for CFCs and HCFCs such as saturated or unsaturated HFCs and HCFCs
Important Responsib e Refrigerant Practices
Trane believes that responsible refrigerant practices are important to the environment, our
customers, and the air conditioning industry All technicians who handle refrigerants must be
certified according to local rules For the USA, the Federal Clean Air Act (Section 608) sets forth
the requirements for handling, reclaiming, recovering and recycling of certain refrigerants and
the equipment that is used in these service procedures In addition, some states or municipalities
may have additional requirements that must also be adhered to for responsible management of
refrigerants Know the applicable laws and follow them

BAS-SVX073C-EN 3
WWAARRNNIINNGG
PPrrooppeerr FFiieelldd WWiirriinngg aanndd GGrroouunnddiinngg RReeqquuiirreedd!!
FFaaiilluurree ttoo ffoollllooww ccooddee ccoouulldd rreessuulltt iinn ddeeaatthh oorr sseerriioouuss iinnjjuurryy
AAllll ffiieelldd wwiirriinngg MMUUSSTT bbee ppeerrffoorrmmeedd bbyy qquuaalliiffiieedd ppeerrssoonnnneell IImmpprrooppeerrllyy iinnssttaalllleedd aanndd
ggrroouunnddeedd ffiieelldd wwiirriinngg ppoosseess FFIIRREE aanndd EELLEECCTTRROOCCUUTTIIOONN hhaazzaarrddss TToo aavvooiidd tthheessee hhaazzaarrddss,,
yyoouu MMUUSSTT ffoollllooww rreeqquuiirreemmeennttss ffoorr ffiieelldd wwiirriinngg iinnssttaallllaattiioonn aanndd ggrroouunnddiinngg aass ddeessccrriibbeedd iinn
NNEECC aanndd yyoouurr llooccaall//ssttaattee//nnaattiioonnaall eelleeccttrriiccaall ccooddeess
WWAARRNNIINNGG
PPeerrssoonnaall PPrrootteeccttiivvee EEqquuiippmmeenntt ((PPPPEE)) RReeqquuiirreedd!!
FFaaiilluurree ttoo wweeaarr pprrooppeerr PPPPEE ffoorr tthhee jjoobb bbeeiinngg uunnddeerrttaakkeenn ccoouulldd rreessuulltt iinn ddeeaatthh oorr sseerriioouuss
iinnjjuurryy
TTeecchhnniicciiaannss,, iinn oorrddeerr ttoo pprrootteecctt tthheemmsseellvveess ffrroomm ppootteennttiiaall eelleeccttrriiccaall,, mmeecchhaanniiccaall,, aanndd
cchheemmiiccaall hhaazzaarrddss,, MMUUSSTT ffoollllooww pprreeccaauuttiioonnss iinn tthhiiss mmaannuuaall aanndd oonn tthhee ttaaggss,, ssttiicckkeerrss,, aanndd
llaabbeellss,, aass wweellll aass tthhee iinnssttrruuccttiioonnss bbeellooww::
•• BBeeffoorree iinnssttaalllliinngg//sseerrvviicciinngg tthhiiss uunniitt,, tteecchhnniicciiaannss MMUUSSTT ppuutt oonn aallll PPPPEE rreeqquuiirreedd ffoorr
tthhee wwoorrkk bbeeiinngg uunnddeerrttaakkeenn ((EExxaammpplleess;; ccuutt rreessiissttaanntt gglloovveess//sslleeeevveess,, bbuuttyyll gglloovveess,,
ssaaffeettyy ggllaasssseess,, hhaarrdd hhaatt//bbuummpp ccaapp,, ffaallll pprrootteeccttiioonn,, eelleeccttrriiccaall PPPPEE aanndd aarrcc ffllaasshh
ccllootthhiinngg)) AALLWWAAYYSS rreeffeerr ttoo aapppprroopprriiaattee SSaaffeettyy DDaattaa SShheeeettss ((SSDDSS)) aanndd OOSSHHAA
gguuiiddeelliinneess ffoorr pprrooppeerr PPPPEE
•• WWhheenn wwoorrkkiinngg wwiitthh oorr aarroouunndd hhaazzaarrddoouuss cchheemmiiccaallss,, AALLWWAAYYSS rreeffeerr ttoo tthhee
aapppprroopprriiaattee SSDDSS aanndd OOSSHHAA//GGHHSS ((GGlloobbaall HHaarrmmoonniizzeedd SSyysstteemm ooff CCllaassssiiffiiccaattiioonn aanndd
LLaabbeelllliinngg ooff CChheemmiiccaallss)) gguuiiddeelliinneess ffoorr iinnffoorrmmaattiioonn oonn aalllloowwaabbllee ppeerrssoonnaall eexxppoossuurree
lleevveellss,, pprrooppeerr rreessppiirraattoorryy pprrootteeccttiioonn aanndd hhaannddlliinngg iinnssttrruuccttiioonnss
•• IIff tthheerree iiss aa rriisskk ooff eenneerrggiizzeedd eelleeccttrriiccaall ccoonnttaacctt,, aarrcc,, oorr ffllaasshh,, tteecchhnniicciiaannss MMUUSSTT ppuutt
oonn aallll PPPPEE iinn aaccccoorrddaannccee wwiitthh OOSSHHAA,, NNFFPPAA 7700EE,, oorr ootthheerr ccoouunnttrryy--ssppeecciiffiicc
rreeqquuiirreemmeennttss ffoorr aarrcc ffllaasshh pprrootteeccttiioonn,, PPRRIIOORR ttoo sseerrvviicciinngg tthhee uunniitt NNEEVVEERR PPEERRFFOORRMM
AANNYY SSWWIITTCCHHIINNGG,, DDIISSCCOONNNNEECCTTIINNGG,, OORR VVOOLLTTAAGGEE TTEESSTTIINNGG WWIITTHHOOUUTT PPRROOPPEERR
EELLEECCTTRRIICCAALL PPPPEE AANNDD AARRCC FFLLAASSHH CCLLOOTTHHIINNGG EENNSSUURREE EELLEECCTTRRIICCAALL MMEETTEERRSS AANNDD
EEQQUUIIPPMMEENNTT AARREE PPRROOPPEERRLLYY RRAATTEEDD FFOORR IINNTTEENNDDEEDD VVOOLLTTAAGGEE
WWAARRNNIINNGG
FFoollllooww EEHHSS PPoolliicciieess!!
FFaaiilluurree ttoo ffoollllooww iinnssttrruuccttiioonnss bbeellooww ccoouulldd rreessuulltt iinn ddeeaatthh oorr sseerriioouuss iinnjjuurryy
•• AAllll TTrraannee ppeerrssoonnnneell mmuusstt ffoollllooww tthhee ccoommppaannyy’’ss EEnnvviirroonnmmeennttaall,, HHeeaalltthh aanndd SSaaffeettyy
((EEHHSS)) ppoolliicciieess wwhheenn ppeerrffoorrmmiinngg wwoorrkk ssuucchh aass hhoott wwoorrkk,, eelleeccttrriiccaall,, ffaallll pprrootteeccttiioonn,,
lloocckkoouutt//ttaaggoouutt,, rreeffrriiggeerraanntt hhaannddlliinngg,, eettcc WWhheerree llooccaall rreegguullaattiioonnss aarree mmoorree
ssttrriinnggeenntt tthhaann tthheessee ppoolliicciieess,, tthhoossee rreegguullaattiioonnss ssuuppeerrsseeddee tthheessee ppoolliicciieess
•• NNoonn--TTrraannee ppeerrssoonnnneell sshhoouulldd aallwwaayyss ffoollllooww llooccaall rreegguullaattiioonnss
IInnttrroodduuccttiioonn

4BAS-SVX073C-EN
Product Identification, Specifications, and Data Outputs 5
Unit Dimensions 7
Product Diagram and Screen Display 8
Installation 9
Supported Systems 11
Wiring 12
Wiring Symbolism 12
Wiring Diagrams 14
Fuse Recommendations 15
Navigating Screens and Setting Parameters 16
Solid State Output 17
User Interface 18
RS-485 Communications 23
Standard Modbus Default Settings 24
Modbus Point Mapping 25
Modbus Point Mapping 27
Troubleshooting 33
China RoHS Compliance 34
Additional Resources 35
Tab e of Contents

BAS-SVX073C-EN 5
Product Identification, Specifications, and Data Outputs
Product Identification
Model: E50C2-T2
Description: Modbus output, full data set
Output: Pulse, RS-485, Alarm
Measurement Accuracy
Real Power and Energy: IEC 62053-22 Class 0.2S, ANSI C12.20 0.2%
Reactive Power and Energy: IEC 62053-23 Class 2, 2%
Current:
0.4% (+0.015% per °C deviation from 25°C) from 5% to 100%
of range; 0.8% (+0.015% per °C deviation from 25°C) from 1%
to 5% of range
Voltage: 0.4% (+0.015% per °C deviation from 25°C) from 90 VL-N to
600 VacL-L
Sample Rate: 2520 samples per second
Data Update Rate: 1 sec
Type of Measurement: True RMS up to the 21st harmonic 60 Hz; One to three phase AC
system
Input Voltage Characteristics:
Measured AC Voltage:
• Minimum 90 VL-N (156 VL-L) for stated accuracy
• U.L. Maximum: 600 VL-L (347 VL-N)
• CE Maximum: 300VL-N
Metering Over Range: +20%
Impedance: 2.5M ΩL-N/5M ΩL-L
Frequency Range: 45 Hz to 65 Hz
Input Current Characteristics
CT Scaling: Primary:adjustable from 5 A to 32,000 A
Measurement Input Range: 0 Vac to 0.333 Vac or 1 Vac to 1.0 Vac (+20% over range), rated
for use with Class 1 voltage inputs
Impedance: 10.6kΩ(1/3 V mode) or 32.1kΩ(1 V mode)
Control Power
AC:
• 5 VA max.; 90 V min.
• U.L. Maximum: 600 VL-L (347 VL-N )
• CE Maximum: 300VL-N
DC:
External DC current limiting is required.
• 3 W maximum
• U.L and CE: 125 VDC to 300 VDC
Ride-through Time: 100 milliseconds at 120 Vac
Output
Alarm Contacts: N.C., static output (30 Vac/DC, 100 mA maximm @ 25°C, derate
0.56 mA per °C above 25°C)
Real Energy Pulse Contacts: N.O., static output (30 Vac/DC, 100 mA maximum @ 25°C,
derate 0.56 mA per °C above 25°C)
RS-485 Port: 2-wire, 1200 to 38400 baud, Modbus RTU

6BAS-SVX073C-EN
Mechanical Characteristics:
Weight: 0.62 LB. (0.28 kg)
IP40 Degree of Protection (IEC60529): IP40 front display; IP20 Meter
Display Characteristics: Backlit blue LCD
Terminal Block Screw Torque: 0.37 ft-lb (0.5 N·m) nominal/0.44 ft-lb (0.6 N·m) maximum
Terminal Block Wire Size: 24 AWG to 14 AWG (0.2 to 2.1 mm2)
Rail: T35 (35 mm) DIN Rail per EN50022
Operating Conditions:
Operating Temp: -30°C to 70°C (-22°F to 158°F)
Storage Temp: -40° to 85°C (-40° to 185°F)
Humidity Range: <95% RH (non-condensing)
Altitude of Operation: 3000 m
Agency Compliance
U.S. and Canada:
• CAT III;
• Pollution Degree 2
• For distribution systems up to 347 V L-N/600 Vac L-L
CE:
• CAT III;
• Pollution Degree 2
• For distribution systems up to 300 V L-N
Dielectric Withstand: Per U.L. 508, EN61010
Conducted/Radiated Emissions: FCC part 15 Class B, EN55011/EN61000 Class B (residential and
light industrial)
Conducted/Radiated Immunity: U.L. EN61000 Class A (heavy industrial)
U.S./Canada (cULus) U.L. 508 (open type device)/CSA 22.2 No. 14-05
Europe (CE): U.L. EN61010-1
Data Outputs (Modbus Only)
Full Data Set:
• Power (kW), Energy (kWh)
• Configurable for CT & PT ratios, system type, and passwords
• Diagnostic alerts
• Current/Volts are both 3-phase average
• Current by phase and volts by phase Line-Line and Line-
Neutral
• Power: Real, reactive, and apparent 3-phase total and per
phase
• Power factor: 3-phase average and per phase
• Frequency
• Power demand: most recent and peak
• Demand configuration: fixed, rolling block, and external
sync
PPrroodduucctt IIddeennttiiffiiccaattiioonn,, SSppeecciiffiiccaattiioonnss,, aanndd DDaattaa OOuuttppuuttss

BAS-SVX073C-EN 7
Unit Dimensions
4.2 in
(107mm)
3.6 in
(91mm)
1.5 in
(39mm)
2.3 in
(59mm)
1.9 in
(48mm)
1.8 in
(45mm)
3.6 in
(91 mm)
4.2 in
(107 mm)
0.2 in
(4 mm)
3.9 in
(99 mm)
2.4 in
(61 mm)
++
+
4.3 in
(109 mm)
1.2 in
(31 mm) 0.3 in
(8 mm)
0.4 in
(10 mm)
DIN Rail Mount Configuration
(Bottom View)
Overall Dimension
Screw Mount Configuration
(Bottom View)
PPrroodduucctt IIddeennttiiffiiccaattiioonn,, SSppeecciiffiiccaattiioonnss,, aanndd DDaattaa OOuuttppuuttss

8BAS-SVX073C-EN
Product Diagram and Screen Disp ay
Alarm Energy
kWh
1234.5
CONTROL POWER
0.1A 50/60 Hz
A B C N 1 2
+ - S
CT Inputs 1 or 0.333 Vac
VA
VB
VC
Neutral
Earth
Control
Power
Phase Loss
Alarm Output
Phase Loss
Alarm Output
Phase Loss
Alarm Output
Shiled
UL: 90V L-N - 600V L-L CE: 90V L-N - 300V L-N
VOLTAGE INPUTS
CAT III 50/60 Hz
+
–
(X2) A(X1) (X2) B(X1) (X2) C(X1)
IA
IB
IC
X2 X1 X2 X1 X2 X1
Interface display text:
• Top row alphanumeric
• Bottom row numeric only
The red alarm LED lights when any of
the 3 phase voltages drop below the
selected threshold.:
00.0.0.0
8.8.8.8.8Tx
Rx
ERR
Screen Name
or Units
Diagnostic
Alert
Numeric Data
Alive Indicator
LCD Screen Buttons (Up)
Select
(Right)
Next
(Down)
Select
(Left)
Back
+
–
Transmit Data
Receive Data
Receive Data Error
PPrroodduucctt IIddeennttiiffiiccaattiioonn,, SSppeecciiffiiccaattiioonnss,, aanndd DDaattaa OOuuttppuuttss

BAS-SVX073C-EN 9
Insta ation
Read the following guidelines before starting installation
• Disconnect power prior to installation
• Reinstall any covers displaced during installation before re-powering unit
• Mount the meter in an appropriate electrical enclosure near equipment to be monitored
• Do not install the load side of a variable frequency drive (VFD)
Mount the meter using one of the following two methods:
1 DIN Rail Mount
a Attach mounting clips to the underside of housing by sliding them into the slots from the
inside
NNoottee:: The stopping pegs must face the housing and the outside edge of the clip must be
flush with the outside edge of the housing.
b Snap the clips onto the DIN rail
Clip flush with
outside edge
Snap onto
DIN rail
Insert clips from inside
2 Screw Mount
a Attach mounting clips to the underside of housing by sliding them into the slots from the
inside
NNoottee:: The stopping pegs must face the housing and the outside edge of the clip must be
flush with the outside edge of the housing.

BAS-SVX073C-EN 11
Supported Systems
The meter has a number of different possible system wiring configurations (Refer to the table
below and next section, Wiring Diagrams) To configure the meter, set the System Type via the
User Interface, Modbus register 130 The system type tells the meter which of its current and
voltage inputs are valid, which are to be ignored, and if neutral is connected Setting the correct
system type prevents unwanted energy accumulation on unused inputs, selects the formula to
calculate the Theoretical Maximum System Power, and determines which phase loss algorithm
is to be used The phase loss algorithm is configured as a percent of the Line-to-Line System
Voltage (except when in System Type 10) In addition, it calculates the expected Line-to-Neutral
voltages for system types that have Neutral (12 & 40) Values that are not valid in a particular
System Type display as ———— on the User Interface or as QQNNAANN in the Modbus registers or
BACnet Analog Input objects
NNoottee:: To avoid distortion, use parallel wires for control power and voltage inputs.
CTs Voltage Connections System Type Phase Loss Measurement
Wiring
Dia-
gram
#
Wires Qty ID Qty ID Type
Modbus
Reg
130/
User
Inter-
face
(SET-
UP>S
SYS) VLL VLN
Bal-
ance
Wiring
#
Single-Phase Wiring
2 1 A 2 A, N L-N 10 1L+1n AN 1
2 1 A 2 A, B L-L 11 2L AB 2
3 2 A,B 3
A, B,
N
L-L w/
N 12 2L+1n AB
AN,
AB
AN-
AB 3
Three-Phase Wiring
3 3 A, B, C 3A, B, C Delta 31 3L
AB,
BC,
CA
AB-
BC-
CA 4
4 3 A, B, C 4
A, B,
C, N
Grou-
nded
Wye 40 3L-1n
AB,
BC,
CA
AN,
BN,
CN
AN-
BN-
CN
and
AB-
BC-
CA 5,6

12 BAS-SVX073C-EN
Wiring
Wiring Symbo ism
Refer to the following symbols used in the wiring diagrams
Voltage Disconnect Switch
Fuse
Note: Installer is responsible for ensuring compliance
with local requirements.
Earth Ground
X2
X1
X2X2
X1
X1
Current Transducer
Potential Transformer
Protection containing a voltage disconnect switch with
a fuse or disconnect circuit breaker. The protection
device must be rated for the available short circuit
current at the connection point.
Read all Warnings, Cautions, and Notices before proceeding
NNOOTTIICCEE
EEqquuiippmmeenntt DDaammaaggee!!
FFaaiilluurree ttoo ffoollllooww iinnssttrruuccttiioonnss bbeellooww ccoouulldd rreessuulltt iinn oovveerrhheeaattiinngg aanndd ppeerrmmaanneenntt
eeqquuiippmmeenntt ddaammaaggee
TThhiiss pprroodduucctt iiss ddeessiiggnneedd oonnllyy ffoorr uussee wwiitthh 11 VVoolltt oorr 00 333333 VVoolltt ccuurrrreenntt ttrraannssdduucceerrss DDoo nnoott
uussee ccuurrrreenntt oouuttppuutt CCTTss oonn tthhiiss pprroodduucctt
WWAARRNNIINNGG
HHaazzaarrddoouuss VVoollttaaggee!!
FFaaiilluurree ttoo ddiissccoonnnneecctt ppoowweerr bbeeffoorree sseerrvviicciinngg ccoouulldd rreessuulltt iinn ddeeaatthh oorr sseerriioouuss iinnjjuurryy
DDiissccoonnnneecctt aallll eelleeccttrriicc ppoowweerr,, iinncclluuddiinngg rreemmoottee ddiissccoonnnneeccttss bbeeffoorree sseerrvviicciinngg FFoollllooww
pprrooppeerr lloocckkoouutt//ttaaggoouutt pprroocceedduurreess ttoo eennssuurree tthhee ppoowweerr ccaann nnoott bbee iinnaaddvveerrtteennttllyy
eenneerrggiizzeedd VVeerriiffyy tthhaatt nnoo ppoowweerr iiss pprreesseenntt wwiitthh aa vvoollttmmeetteerr
WWAARRNNIINNGG
HHaazzaarrddoouuss VVoollttaaggee aanndd EEqquuiippmmeenntt DDaammaaggee!!
FFaaiilluurree ttoo ffoollllooww iinnssttrruuccttiioonnss bbeellooww ccoouulldd rreessuulltt iinn ddeeaatthh oorr sseerriioouuss iinnjjuurryy
CCTT tteerrmmiinnaallss aarree rreeffeerreenncceedd ttoo nneeuuttrraall oonn tthhee mmeetteerr aanndd mmaayy bbee aatt eelleevvaatteedd vvoollttaaggeess DDoo
nnoott ccoonnttaacctt mmeetteerr tteerrmmiinnaallss wwhhiillee tthhee uunniitt iiss ccoonnnneecctteedd DDoo nnoott ccoonnnneecctt oorr sshhoorrtt ootthheerr
cciirrccuuiittss ttoo tthhee CCTT tteerrmmiinnaallss
DDiissccoonnnneecctt aallll eelleeccttrriicc ppoowweerr,, iinncclluuddiinngg rreemmoottee ddiissccoonnnneeccttss bbeeffoorree sseerrvviicciinngg FFoollllooww
pprrooppeerr lloocckkoouutt//ttaaggoouutt pprroocceedduurreess ttoo eennssuurree tthhee ppoowweerr ccaann nnoott bbee iinnaaddvveerrtteennttllyy
eenneerrggiizzeedd VVeerriiffyy tthhaatt nnoo ppoowweerr iiss pprreesseenntt wwiitthh aa CCAATT IIIIII oorr IIVV vvoollttmmeetteerr rraatteedd ppeerr NNFFPPAA
7700EE

BAS-SVX073C-EN 13
WWAARRNNIINNGG
EElleeccttrriiccaall SShhoocckk,, EExxpplloossiioonn,, oorr AArrcc FFllaasshh HHaazzaarrdd!!
FFaaiilluurree ttoo ffoollllooww tthheessee iinnssttrruuccttiioonnss ccoouulldd rreessuullttss iinn ddeeaatthh oorr sseerriioouuss iinnjjuurryy
IInnssttaallll tthhee pprroodduucctt iinn aann aapppprroopprriiaattee eelleeccttrriiccaall//ffiirree eenncclloossuurree ppeerr llooccaall rreegguullaattiioonnss DDoo nnoott
iinnssttaallll tthhee pprroodduucctt iinn hhaazzaarrddoouuss oorr ccllaassssiiffiieedd llooccaattiioonnss
DDoo nnoott uussee tthhee pprroodduucctt ffoorr lliiffee oorr ssaaffeettyy aapppplliiccaattiioonnss
DDoo nnoott eexxcceeeedd tthhee pprroodduucctt rraattiinnggss oorr mmaaxxiimmuumm lliimmiittss PPrroodduuccttss rraatteedd oonnllyy ffoorr bbaassiicc
iinnssuullaattiioonn mmuusstt bbee iinnssttaalllleedd oonn iinnssuullaatteedd ccoonndduuccttoorrss
CCuurrrreenntt ttrraannssffoorrmmeerr sseeccoonnddaarriieess ((ccuurrrreenntt mmooddee)) mmuusstt bbee sshhoorrtteedd oorr ccoonnnneecctteedd ttoo aa
bbuurrddeenn aatt aallll ttiimmeess
RReemmoovvee aallll wwiirree ssccrraappss,, ttoooollss,, rreeppllaaccee aallll ddoooorrss,, ccoovveerrss aanndd pprrootteeccttiivvee ddeevviicceess bbeeffoorree
ppoowweerriinngg tthhee eeqquuiippmmeenntt
WWiirriinngg

14 BAS-SVX073C-EN
Wiring Diagrams
Figure 1. 1–Phase and 3–Phase Diagrams
N L1
X2
X1 White
Black
A
B
C
N
X1
X2
X1
X2
X1
X2
A
B
C
L1 L2
X2
X1
A
B
C
N
A
B
C
White
Black X1
X2
X1
X2
X1
X2
L1 L2
X2
X1
X2
X1
A
B
C
N
A
B
C
N
White
Black
White
Black
X1
X2
X1
X2
X1
X2
L1 L2 L3
X2
X1
A
B
C
N
A
B
C
X2
X1
X2
X1
White
Black
White
Black
White
Black
X1
X2
X1
X2
X1
X2
L1N L2 L3
X2
X1
A
B
C
N
A
B
C
X2
X1
X2
X1
White
Black
White
Black
White
Black
X1
X2
X1
X2
X1
X2
White
Black
White
Black
White
Black
L1N L2 L3
X2
X1
A
B
C
N
A
B
C
X2
X1
X2
X1
X1
X2
X1
X2
X1
X2
#1: 1-Phase, Line-to-Neutral, 2-Wire System, 1 CT
Use System Type 10 (1L+1n)
#2: 1-Phase, Line-to-Line, 2-Wire System, 1 CT
Use System Type 11 (2L)
#3: 1-Phase, Direct Voltage Connection, 2 CT
Use System Type 12 (2L+1n)
#5: 3-Phase, 4-Wire, Direct Voltage Input Connection, 3 CT
Use System Type 40 (3L+1n)
#6: 3-Phase, 4-Wire Wye Connection, 3 CT, 3 PT
Use System Type 40 (3L+1n)
#4: 3-Phase, 3-Wire System, 3 CT, No PT
Use System Type 31 (3L)
WWiirriinngg

BAS-SVX073C-EN 15
Figure 2. Contro Power Diagrams
L1
1 2G
L2 L3 L1N L2 L3
1 2G
1 2G
L1N L2 L3
1 2G
#1: Direct Connect Control Power, Line-to-Line #2: Line-to-Neutral from 90 Vac to
347 Vac (UL) or 300 Vac (CE)
#3: DC Control power from 125 VDC
to 300 VDC (UL and CE max)
Line-to-Line from 90 Vac to 600 Vac (UL). In UL
installations the lines may be floating (such as
a delta). If any lines are tied to an earth (such as
a corner grounded delta), refer to the
Line-to-Neutral installation limits. In CE
compliant installations, the lines must be
neutral (earth) referenced at less than 300 VacL-N
#4: Control power transformer may be wired
L-N or L-L. Output to meet meter
input requirements
Fuse Recommendations
Keep the fuses close to the power source For selecting fuses and circuit breakers, use the
following criteria:
• Select current interrupt capacity based on the installation category and fault current
capability
• Select over-current protection with a time delay
• Use a voltage rating sufficient for the input voltage applied
• Provide over-current protection and disconnecting means to protect the wiring
NNoottee:: . For AC installations, use Trane A 04 or equivalent. For DC installations, provide
external circuit protection. Suggested: 0.5A, time delay fuses rated for DC operation at
or above the supply voltage
• Use the earth connection (G) for electromagnetic compatibility (EMC), not a protective earth
ground
WWiirriinngg

16 BAS-SVX073C-EN
Navigating Screens and Setting Parameters
These instructions assume the meter is set to factory defaults If it has been previously
configured, all optional values should be checked
Buttons (Up)
Select
(Right)
Next
(Down)
Select
(Left)
Back
+
–
1 Press the + or – button repeatedly until SSEETTUUPP screen displays
2 Press –> to advance to the PPAASSWWDD screen
3 Press –> through the digits Press + or – buttons to select the password (the default is 0000000000)
Exit the screen to the right
4 Press + or – buttons to select the parameter to configure settings
5 Optional: if the unit has an RS-485 interface, the first setup screen is SS CCOOMM (set
communications)
a Press –> to advance to the AADDDDRR screen and through the address digits Press + or –
buttons to select the Modbus address
b Press –> to advance to the BBAAUUDD screen Press + or – buttons to select the baud rate
c Press –> to advance to the PPAARR screen Press + or – buttons to select the parity
d Press –> to return to the SS CCOOMM screen
6 Press – to advance to the SS CCTT (Set Current Transducer) screen If this unit does not have an
RS-485 port, this is the first screen to displays
a Press –> to advance to the CCTT VV screen and through the digits Press + or – buttons to
select the mode CT output voltage
b Press –> to advance to the CCTT SSZZ screen and through the digits Press + or – buttons to
select the CT size in amps
c Press –> to return to the SS CCTT screen
7 Press –> to advance to the SS SSYYSS (Set System) screen
a Press –> to advance to the SSYYSSTTMM screen Press + or – buttons to select the System Type
b Press –> to return to the SS SSYYSS screen
8 Optional: press – to advance to the SS PPTT (Set Potential Transformer) screen If PTs are not
used, then skip this step
a Press –> to advance to the RRAATTIIOO screen and through the digits Press + or – buttons to
select the Potential Transformer step down ratio
b Press –> to return to the SS PPTT screen
9 Press – to advance to the SS VV (Set System Voltage) screen
a Press –> to advance to the VVLLLL (or VLN if system is 1L-1n) screen and through the digits
Press + or – buttons to select the Line to Line System Voltage
b Press –> to return to the SS VV screen
10 Press <– to exit the setup screen and then SSEETTUUPP Verify that the wrench is not displayed on
the LCD
a If the wrench is displayed, press + or – buttons to advance to the AALLEERRTT screen
b Press –> through the screens to see which alert is on

BAS-SVX073C-EN 17
So id State Output
The E50C2-T2 have one (1) normally open (NO) KY Form A output and one (1) normally closed
(N C ) output * One is dedicated to energy (Wh), and the other to Alarm
~=
≤ 100 mA
≤ 100 mA
~=
Alarm Energy Output
+ – S
Load
Load
*Over-current Protective
Device (Not Supplied)
Notes: The solid state pulse outputs are rated for 30 Vac/DC nominal.
Maximum load current is 100 mA at 25°C. Derate 0.56 mA per °C
above 25°C (for example, 86 mA at 50°C).
** Power Supply
3-30 Vdc
6-30 Vac
** Power Supply
3-30 Vdc
6-30 Vac
* While the relay used for phase loss contact is normally closed (NC)
[contacts are closed when the meter is not powered], closure
indicates the presence of an alarm; either loss of phase, when the
meter is power, or loss of power when the meter is not.
The contacts are open when the meter is powered and no phase
loss alarm conditions are present.
** All pulse outputs and communication circuits are only intended
to be connected to non-hazardous circuits (SELV or Class 2).
Do not connect to hazardous voltages.

18 BAS-SVX073C-EN
User Interface
The user can set the display mode to either IEC or IEEE notation in the SETUP menu
Tab e 1. User Interface Menu Abbreviations
Main Menu Main Menu
IEC IEEE Description IEC IEEE Description
D D Demand F ERR F ERR Frequency Error
MAX M Maximum
Demand
I OVR I OVR Over Current
P W Present Real
Power
V OVR V OVR Over Voltage
Q VAR Present
Reactive
Power
PULSE PULSE kWh Pulse Output
Overrun
(configuration
error)
S VA Present
Apparent
Power
_PHASE _PHASE Summary Data for
1, 2, or 3 active
phases
A A Amps ALERT ALERT Diagnostic Alert
Status
UAB, UBC,
UAC
VAB, VBC,
VAC
Voltage Line-
to-Line
INFO INFO Unit Information
V VLN Voltage Line
to Neutral
MODEL MODEL Model Number
PF PF Power Factor OS OS Operating System
U VLL Voltage Line-
to-Line
RS RS Reset System
HZ HZ Frequency SN SN Serial Number
KSh KVAh Accumulated
Apparent
RESET RESET Reset Data
KQh KVARh Accumulated
Reactive
PASWD PASWD Enter Reset or
Setup Password
KPh KWh Accumulated
Real Energy
ENERG ENERG Reset Energy
Accumulators
PLOSS PLOSS Phase Loss DEMND DEMND Reset Demand
Maximums
LOWPF LOWPF Low Power
Factor Error
Other manuals for E50 Series
2
This manual suits for next models
1
Table of contents
Other Trane Measuring Instrument manuals
Popular Measuring Instrument manuals by other brands

ELAN DIGITAL SYSTEMS
ELAN DIGITAL SYSTEMS USBscope50 user guide

Aqua Medic
Aqua Medic pH-Computer Operation manual

red lion
red lion LD Series operating manual

Phase Technologies
Phase Technologies PHASE CONNECT PC4R Installation & operation manual

Check-line
Check-line DLM-107A user guide

FRONIUS
FRONIUS 63A-1 quick start guide