U LED
LED control gear
Standards
EN55015
EN61000-3-2
EN61000-3-3
EN61347-1
EN61347-2-13
EN61547
EN62384
Umodule
+
–
Uconverter
LCU ... D010
L
~
N
+
–
AC
Wiring diagram Connection
Primary
cable
Secondary
cable
LN+ –
brown blue red black
Overload protection
AutomaticshutdownoftheLEDcontrolgearifthemaximumoutputcurrentis
exceeded.Automaticrestartiftheoutputcurrentisbelowthelimit.
Over temperature protection
AutomaticshutdownoftheLEDcontrolgearifthetemperaturelimitisexceeded.
Automaticrestartifthetemperaturefallsbelowthelimit.
8
38
500
Maximum loading of automatic circuit breakers
Automaticcircuitbreakertype C10 C13 C16 C20 B10 B13 B16 B20 Inrushcurrent
InstallationØ1.5mm21.5mm21.5mm22.5mm21.5mm21.5mm21.5mm22.5mm2Imax time
LCU 035/0008 D010 12 16 22 24 6 8 11 12 90A 0.095ms
LCU 035/0012 D010 12 16 22 24 6 8 11 12 90A 0.095ms
PRI:
Ø7.7±0.2mm;2x1.04mm2(17AWG)
SEC:
Ø8±0.2mm;2x1.31mm2(16AWG)
Harmonic distortion in the mains supply (at 230 V / 50 Hz and full load) in %
Type THD 3 5 7 9 11
LCU 035/0008 D010 542211
LCU 035/0012 D010 652211
No-load operation
TheLEDcontrolgearisnotdamagedintheno-loadoperation.Themax.output
voltage(seepage1)canbeobtainedduringno-loadoperation.
Isolation and electric strength testing of luminaires
Electronicdevicescanbedamagedbyhighvoltage.Thishastobeconsidered
duringtheroutinetestingoftheluminairesinproduction.
AccordingtoIEC60598-1AnnexQ(informativeonly!)orENEC303-AnnexA,each
luminaireshouldbesubmittedtoanisolationtestwith500VDCfor1second.This
testvoltageshouldbeconnectedbetweentheinterconnectedphaseandneutral
terminalsandtheearthterminal.
Theisolationresistancemustbeatleast2MΩ.
Asanalternative,IEC60598-1AnnexQdescribesatestoftheelectricalstrength
with1500VAC(or1.414x1500VDC).Toavoiddamagetotheelectronicdevicesthis
testmustnotbeconducted.
Additional information
Additionaltechnicalinformationat
www.tridonic.com→TechnicalData
Guaranteeconditionsat
www.tridonic.com→Services
Nowarrantyifdevicewasopened.
Installation instructions
TheswitchingofLEDsonsecondarysideisnotpermitted.
AproperfunctioningoftheLCUincombinationwiththirdpartydimmingdevices
(e.g.PWM)cannotbeguaranteed.