TTrig is a measurement interval switch for the TriOS G2 sensors OPUS and NICO. Due to its low standby power
(<1mW),itisideallysuitedforoperationwithabatteryaspowersupply.Itisdesignedtominimizeenergyconsumptionbetween
measurements.
TheTTrig features an additional connection for commissioning and controlling a wiper (W55).
Remote or self-sucient measuring stations can thus be operated maintenance-free for several months.
An RJ-45 Ethernet interface provides access to the sensor's G2 web interface for downloading the measurement data from the
data logger with a notebook.
Technical Specications
POWER SUPPLY
Voltage supply 12...24VDC, max. 4A
Power in standby <1mW
SENSOR INTERFACES
Connection M12 forTriOS G2 sensors; 1x RJ-45
Standard RS-485
Protocol Modbus RTU
Analog interfaces No
OTHER INTERFACES
Connection 1x M8 connector for wiperW55
Trigger output
ENVIRONMENT
Operating temperature 0...+40 °C
Storage temperature -10...+70 °C
Relative air humidity 0...95 % (non-condensing)
Protection type IP64
MECHANICAL SYSTEM
Dimensions (width x height x
depth) 140 x 80 x 60 mm
Weight 0.5 kg

TTrig //
2
D04-05Aen201908 Quick GuideTTrig
TriOS Mess- und Datentechnik GmbH · Bürgermeister-Brötje-Str. 25 · D-26180 Rastede · Germany
Short Guide
Compatibility
TheTTrig can only be used with one sensor and one wiper at the same time and can only be used for sensors with integrated
data logger (OPUS, NICO).
Scope of Delivery
TTrig
Connections
Cable
bushing M8
connection M12
connection
Control panel
2 rotary encoders for setting measurement interval and delay
5 buttons with the following functions:
• Start automatic measurement*
• Service (switch on sensor permanently for data download)
• Sensor single measurement
• Wiper activation
• Reset (reset program)
*If the red power fail LED ashes, this button can be pressed to start a manual attempt to restore normal operation.
LEDs
Description Colour Function Behaviour
Start white Measurement interval active LED ashes briey once every 20 seconds
white Sensor initialisation LED ashes continuously
Wiper white Wiper active LED lights up permanently
Sensor white Sensor active
LED lights up permanently 2 minutes before measu-
rement
LED ashes three times briey during measurement
LED lights up permanently 1 minute after measure-
ment
Service yellow Service active LED lights up permanently
yellow Sensor initialisation failed LED ashes briey once every 20 seconds
Power fail red Critical power supply (<11V) LED ashes briey once every 20 seconds

TTrig //
3
D04-05Aen201908 Quick GuideTTrig
TriOS Mess- und Datentechnik GmbH · Bürgermeister-Brötje-Str. 25 · D-26180 Rastede · Germany
Commissioning
Electrical installation
Afteropeningtheprotectivecover,theTTrigisrstconnectedtoapowersupply(12..24VDC).A2-pinPhoenixconnectorislocat-
ed on the left-hand side for this purpose.
Sensor connection and wiper connection
The sensor must then be connected to the M12 socket and optionally a wiper to the M8 socket.The following table shows the
conguration options.
Function test
TheWIPER andSENSOR buttonsshould beoperatedmanually oneafter theotherfor thesubsequentfunction test.Thefunction
of the wiper is visible by its movement. For OPUS it is recommended to download the data logger and check the completeness
of the measurements.
Conguration of automatic measurement
The measurement interval is set on site on theTTrig (rotary encoder "1. INTERVAL"). In addition, a start delay (rotary encoder "2.
DELAY") can be activated. The following table shows the conguration options.
Cable
bushing M8
connection M12
connection
Rotary encoder position 1.Interval
0 15 minutes
1 30 minutes
2 1 h
3 2 h
4 3 h
5 4 h
6 6 h
7 8 h
8 12 h
9 24 h
Rotary encoder position 2. Delay
0 No delay time
1 1 h
2 2 h
3 3 h
4 4 h
5 6 h
6 8 h
7 10 h
8 15 h
9 20 h

TTrig // Quick Guide
4
D04-05Aen201908 Quick GuideTTrig
TriOS Mess- und Datentechnik GmbH · Bürgermeister-Brötje-Str. 25 · D-26180 Rastede · Germany
Start of automatic measurement
Pressing the start button ("3. START") starts the automatic measurement.This function of the start button is only available again
after a reset or disconnection of the power supply.
The following procedure should be observed after the start of the automatic measurement:
Sequence of the rst measurement after activation by pressing the start button.
START LED WIPER LED SENSOR LED Function
1. Flashes quickly OFF OFF Sensor initialisation
2. Flashes quickly ON OFF Wiper cleans
3. Flashes quickly OFF ON Sensor boots
4.* Flashes every 20 s OFF Flashes 3 x fast Measurement
5. Flashes every 20 s OFF ON Data backup
6. Flashes every 20 s OFF OFF Automatic measurement running
During active automatic measurement, the start LED lights up once every 20 seconds.
* If instead the yellow service LED ashes every 20 s, please refer to the section Troubleshooting/Sensor not
found.
Data storage and retrieval
All measurement data is only stored on the internal 2GB SD card of the sensor.
A notebook can be connected via an RJ-45 socket on theTTrig so that the stored measurement data can be downloaded via the
web interface. Press the "Service" button on theTTrig to supply the sensor with power for the entire period. In service mode the
automatic measurements are interrupted, "Skipped" is entered in the comment line of the next measurement.
Establishing a connection to the sensor
Step 1 Connect a notebook/PC to theTTrig via the RJ-45 socket.
Step 2 Press the "Service" button on theTTrig to activate the service mode.
Step3 Open a web browser. The following URL establishes the connection to your sensor: http://192.168.77.1/ (see also
manual of the respective sensor)
Comments
Each record has a comment function with four comment lines.
They can be found in the web interface under the menu "Measurement" "Settings".
Lines 1 and 2 are freely available to the user.
Lines 3 and 4 are overwritten byTTrig.
The settings of the rotary encoders are queried once. Later adjustment has no eect on the measur-
ing intervals or the delay!
NOTICE

TTrig // Quick Guide
5
D04-05Aen201908 Quick GuideTTrig
TriOS Mess- und Datentechnik GmbH · Bürgermeister-Brötje-Str. 25 · D-26180 Rastede · Germany
In comment line 3 each measurement is assigned a consecutive number.
Failed measurements, e.g. due to service or power fail, are internally incremented inTTrig.
In this case, the number of the subsequent measurement is not consecutive.
Thenumberingof themeasurementsenablestheuser tosubsequently correctuctuations ofthe sensor-internalRTC(RealTime
Clock).
Comment line 4 contains additional event information suchas timeout, power fail, etc.
In the case of omitted measurements, their number can be read at "EVENT-SKIPPED #".
TTrig Reset
Reset resets theTTrig to its initial position.
Automatic measurement is stopped and the numbering of the measurements is reset to 1.
1. INTERVAL and 2. DELAY can now be recongured. By pressing the start button theTTrig takes over the settings of the rotary
encoders into the new automatic measurement.
All stored data of the sensor is retained!
Troubleshooting
Power fail:
Apowerfailoccurswhenthepowersupplyisnolongersucientforthenextmeasurement.TheredPOWERFAILLEDashesand
nomore measurement istriggeredin thefollowing12hours. Every12 hours,theTTrigwill automaticallycheck theperformance
of the power supply.
The start button can be used to trigger a manual check of the voltage source.
TheTTrig resumes automatic measurement when sucient power is available.
Sensor not found:
Check the connector and the cable of the sensor. Carry out a reset and press the start button again after one minute.
Sensor detected Measurements are carried out fully automatically.
Sensor not detected Connect to the G2 interface of the sensor and check the settings of the serial interface under the menu
"Peripherals".