TUFFA TANKS AdBlue 1350SLBFSAD Owner's manual

TUFFA
ADBLUE®
STATIONS
Installation, Operation and Servicing Manual Version 2.0.0
Models:
1350SLBFSAD | 2500HBFSAD | 3500VBFSAD | 6000VBFSAD | 10000VBFSAD | 15000VBFSAD


1
1. Introduction 2
2. Conditions of use 2
3. Safety 3
4. Product description 4
4.1 Productidentication 4
4.2 Productspecication 5
4.3 Product footprint 6
5. Transport & storage 9
6. Installation & commissioning 10
6.1 Installationguidelines 10
6.2 Systeminstallation 10
6.3 Systemlocation 10
6.4 Electricalrequirements 11
6.5 Electricalwiringdiagram 11
7. Operation of the system 13
7.1 Usingthesystem 13
7.2 Summaryofmainparts1350/2500 13
7.3 Summaryofmainparts3500/6000/10000/ 15000 14
7.4 FillingAdBlue®Station 15
7.5 DispensingAdBlue®intovehicle 15
7.6 Equipmentcomponents 16
8. Maintenance of the TUFFA TANKS 26
8.1Systemmaintenancetasks 26
8.2 Inspection by competent person 27
8.3Internalexaminationandcleaning 27
8.4Troubleshooting 28
8.5Tankmaintenancerecord 30
8.4AdBlue®deliverylog 32
9. Warranty 34
10. Contact 35
11. Guarantee registration 35
CONTENTS PAGE

2
1. Introduction
Thismanualcontainsspecicinstructionsandinformationrelatingtotheinstallation,
operationandmaintenanceofTuaTankssystems.
2. Conditions of use
• Readthismanualbeforeinstallingthissystem.
• TuaTanksacceptsnoliabilityforpersonalinjuryorpropertydamageresultingfrom
workingonoradjustingtheequipmentincorrectlyorwithoutauthorisation.
• TuaTanksacceptsnoliabilityfordirect,indirect,incidental,special,or
consequentialdamagesresultingfromfailuretofollowanywarnings,instructions,and
proceduressetoutinthismanual.
• TuaTanksreservestherighttochangethespecicationsofitsproductsorthe
informationinthismanualwithoutnecessarilynotifyingitsusers.
• VariationsininstallationandoperatingconditionsmayaecttheTuaTanksystems
performance.TuaTanksmakesnorepresentationsorwarrantiesconcerningthe
performanceofthetanksystemundertheoperatingconditionsprevailingatthe
installation.
• OnlypartssuppliedbyorapprovedbyTuaTanksmustbeusedandno
unauthorisedmodicationstothehardwareorsoftwareshouldbemade.Theuseof
non-approvedpartsormodicationswillvoidallwarrantiesandapprovalsandcould
leadtohazardoussafetyconditions.
• Unlessotherwisenoted,referencestobrandnames,productnames,ortrademarks
constitutetheintellectualpropertyoftheownerthereof.
1. INTRODUCTION | 2. CONDITIONS OF USE

3
3. Safety
PLEASE READ THIS MANUAL CAREFULLY BEFORE USE & COMPLY WITH ALL
INSTRUCTIONS BELOW.
THIS MANUAL SHOULD BE KEPT WITH THE EQUIPMENT AT ALL TIMES.
1.Themajorhazardinvolvedwithinstallingandoperatingtheunitiselectricalshock.
Thishazardcanbeavoidedifyouadheretotheproceduresinthismanualandexercise
allduecare.
2.Installationanduseofthisproductshouldonlybecarriedoutbyproperlytrainedand
approvedpersonnel.
3.PleaserefertostoragemediaMSDSwhichshouldbesuppliedbytheproprietorofthis
systemwhichwilldetailthePPErequiredforhandlingandemergencyprocedures.
4.Theuserofthisproductisresponsibleforthesafeandcorrectuseofthisproduct.
5.Thisproductisonlysuitableforstorageand/ordispensingoftheliquidmediarefer-
encedatthepointofsale.
3. SAFETY

4
4. Product description
TuaAdBlue®StationsaredesignedsolelyforstorageanddispensingofAdBlue®.
ThestaticbundedsystemsenablesafeAdBlue®storageanddispensinginanoutdoor
environment.Thehighstandardofspecicationensuresoptimumsafetyandfunctionality.
Thisproduct’sstandardspecicationisnotapprovedfortheresaleofAdBlue®.
4.1 Productidentication
Theidenticationplateislocatedwithinthecabinetofeachsystemandwilldetailthe
capacity,serialnumber,modelnumberandyearofmanufacture.
4. PRODUCT DESCRIPTION

5
4.2Productspecication
1350SLBFS
AdBlue®
2500HBFS
AdBlue®
3500VBFS
AdBlue®
6000VBFS
AdBlue®
10000VBFS
AdBlue®
15000VBFS
AdBlue®
Capacity 1350litres 2500litres 3500litres 6000litres 10000litres 15000litres
Length 2680mm 2840mm - - - -
Width 870mm 1520mm - - - -
Diameter - - 2034mm 2580mm 2890mm 2860mm
Height 1665mm 1630mm 2520mm 2610mm 2600mm 3500mm
Cabinet depth - - 600mm 600mm 600mm 600mm
Weight (approx.) 220kgs 300kgs 350kgs 430kgs 500kgs 700kgs
Bund material LowerLinearDensityPolyethylene
Inner tank
material LowerLinearDensityPolyethylene
Description BundedAdBlue®FuelStation
Fill point 2”stainlesssteeldrybreakcoupling
Voltage 230V
Ventilation 2x2”screenedvents
Flow rate 40lpm(approximately)
Flowmeter Digitalbatteryoperatedturbinemeter(accuracy+/-1%)
Delivery hose 6 metres
Hose reel
(optional) N/A Hosereelavailable
8 metres - 19mm bore
Nozzle Automaticshutonozzle
4.PRODUCT DESCRIPTION

6
4.3 Product footprint
1350SLBFS AdBlue®
2500HBFS AdBlue®
4. PRODUCT DESCRIPTION

7
3500VBFS AdBlue®
6000VBFS AdBlue®
4.PRODUCT DESCRIPTION

8
10000VBFS AdBlue®
15000VBFS AdBlue®
4. PRODUCT DESCRIPTION

9
5. TRANSPORT & STORAGE
5. Transport & storage
DO NOT TRANSPORT WITH LIQUID INSIDE THE TANK
1. Duringtransportationtheiplidandcabinetdoorsaresecuredby1xRclip.TheR
clipmustbeinstalledpriortotransportation.
2. Loadingando-loadingmustbecarriedoutbyacompetentpersonusingsuitable
ratedandmaintainedequipment,eitheraforkliftwithextendedforks/tinesoracrane.Iflifting
slingsareused,theymustbeattachedtotheliftingpointsasshowninthepicturesbelow
usingasteelliftingeyeinsert.Ifliftingfrombelowuseasuitableratedforkliftwithextended
forks.Ifliftingfromaboveuseasuitableratingliftingslings/chains.
3. 1350SLBFSAD/2500HBFSAD-Liftwithmainliftingeyehighlightedinredinthe
imagebeloworforkliftfromtheside.
4. 3500VBFSAD/6000VBFSAD/10000VBFSAD/15000VBFSAD-Liftwithx4equal
spacedliftingbracketsashighlightedinredintheimagebeloworforkliftfromonesideusing
aratchetstraptosecurethetanktotheforkliftmast.
5. TuaAdBlue®Stationsmustneverbepushedorrolled.
6. Duringtransportandstorage,theiplidorcabinetdoorsmustbeclosedandsecured.
7. Loading,transportandstorageareasmustbesmoothandfreeofsharpedges.

10
6. Installation & commissioning
6.1 Installation guidelines
TheproprietoroftheTuaAdBlue®Stationisresponsibleforcomplyingwithalllegalrequire-
mentsrelatingtotheinstallationanduseofthisproduct,aswellastheguidelinesissuedby
localreghtingauthoritiesandenvironmentalauthorities.
OncetheTuaAdBlue®Stationhasbeenreceivedonsite,checkthatnodamagehasoc-
curredwhileintransit.Locatethetankinthedesiredlocationusingeithercrane,forkliftor
rollers.
6.2 System installation
System foundation
Thesystemmustbeinstalledandfullysupportedonasmoothlevelledconcretebasebuiltin
accordancewithgoodbuildingstandardsandengineeringprinciples.Itisrecommendedthat
tanksbeinstalledonaconcretebaseatleast100mmthick.Pleaserefertodiagrambelow:
6.3 System location
Thelocationofthesystemshouldbepositionedbyaroadorpassingwithsucientwidth,
andloadingcapacitytoaccommodateatankerdeliveringAdBlue®.ProvisionfortheU-turnof
atankershouldbeconsidered.Potentialobstaclesintheformoftreebranches,highvoltage
lines,orparkedvehiclesmustbeminimized.
Thespacearoundthesystemshouldallowfreeandcollision-freemovementofservedvehi-
cles.
Provisionshouldbemadetoprotecttankfromimpactdamage.
6. INSTALLATION & COMMISSIONING

11
6.4 Electrical requirements
Onlyasuitablyqualiedelectricianaccordingtoapplicableregulationsmayworkontheelec-
tricwiringinstallation.Thesystemcomponentsunderservice,maintenance,andrepairwork
mustbedisconnectedfromthepowersupplybeforeanyworkinundertaken.
System power requirements:
• 220-240Volts,50Hz+/-10%
• 20ampcircuitbreakerrecommended
• Powercablerecommendation:3Core2.5mmexcable
6.5 Electrical wiring diagram
6.5.11350SLBFSAdBlue®/2500HBFSAdBlue®–KeySwitch
6. INSTALLATION & COMMISSIONING

12
6.5.2 3500VBFSAdBlue®/6000VBFSAdBlue®/10000VBFSAdBlue®/
15000VBFSAdBlue®–KeySwitch
6. INSTALLATION & COMMISSIONING

13
7. Operation of the system
ThesystemanditscomponentsareintendedforAdBlue®onlyandforthepurposesde-
scribedbelow.Useofthissysteminameansotherthandescribedbelowisregardedas
mis-useofthesystem,theuserofthesystemwillbeliableforanydefectsthatoccurdueto
its unintended use.
7.1 Using the system
Theoperationandmaintenancepersonnelmustbesuitablytrainedtousethesystem,the
usermustmakesuretheyfullyunderstandtheoperationandmaintenancesectionsofthis
manual.
7.2 Summary of main parts 1350 / 2500
7. OPERATION OF THE SYSTEM

14
7.3 Summary of main parts 3500 / 6000 / 10000 / 15000
7. OPERATION OF THE SYSTEM

15
7.4 Filling AdBlue® Station
1. Fillingshouldbeperformedonlyunderconstantsupervisionofanauthorisedperson.
2. Thistankcanonlybelledbyatankerequippedwitha2”femaledrybreakcoupling.
3. On3500/6000/10000/15000modelsbeforellingthetankwithAdBlue®,please
checkthelevelofthetankandmakenoteofthetanklevelbeforellingandensurethe
highlevelalarmindicatorfunctionscorrectly.
4. Fittankerdeliveryhoseto2”drybreakllcouplingontank.
5. Engagetankerpumpandbegintoll.Stopllingwhendesiredamounthasbeen
dispensedintotank,orwhenhigh-levelalarmsounds.
6. Duringthetankerllalwaysobservetanklevelgaugethroughoutthedurationofthe
llingprocess.Thetankerdrivermustobservethetankbeinglledatalltimesduringthis
process.
7. Oncecompletedisconnectdeliveryhosefromtankcoupling.
7.5 Dispensing AdBlue® into vehicle
1. Resettheowmetertotalizerto0
2. Activatepumpusingoneofthefollowing:Rockerswitch,keyswitch,auto-operational
nozzleholster
3. RemovenozzlefromnozzleholsterandinsertthenozzlecompletelyintotheAdBlue®
tankllerneck
4. PulltriggeronthenozzletoallowAdBlue®toowintothevehicleAdBlue®tank
5. Atthistimetheowmetercounterwillstartrecordingtheow,continuerefuelinguntil
thedesiredamountisreachedorwhenthevehicleAdBlue®tankisfull
6. WhentheAdBlue®isfullthenozzlewillautomaticallyswitcho
7. Releasethetriggerofthenozzleandreplacebackintotheholster
8. Deactivatepumpwithrockerswitch/keyswitch/autooperationalnozzleholster
7. OPERATION OF THE SYSTEM

16
7.6 EQUIPMENT COMPONENTS
7.6.1 FMS GAUGE LEVEL (3500 | 6000 | 10000 | 15000)
TheFuelLevelMonitoringSystemisa240vcombineddigitaltank
levelindicatorandbundandhigh-levelalarmthatisdesignedto
providebothvisualandaudiblealarmswheneverapredetermined
levelinastoragetankisreached.TheFMSgivesacontent
readoutinbothlitresandapercentage.
A. FULL ALARM
Activationofthisalarmindicatesthatthetankisfull.Thisalarmis
shownthroughvisualLED’sandaudiblesiren.Note:Thisaudible
andvisualalarmwillremaintriggeredforashortperiodoftime
afteritsounds.Theaudiblecanbemutedusingthemutebutton
onthekeypad.THEPUMPWILLCONTINUETODISPENSEIN
THISALARMMODE.
B. HIGH LEVEL ALARM
Activationofthisalarmindicatesthetankhasreachedahigh
capacityandcloseattentionmustbepaidtothedieselinside
thetank.ThisalarmisshownthroughvisualLED’sandaudible
siren.Note:Thisaudibleandvisualalarmwillremaintriggered
forashortperiodoftimeafteritsounds.Theaudiblecanbe
mutedusingthemutebuttononthekeypad.THEPUMPWILL
CONTINUETODISPENSEINTHISALARMMODE.
C. LOW LEVEL ALARM
Activationofthisalarmindicatesthetankhasreachedalow
level.ThisalarmisshownthroughvisualLED’sandaudiblesiren.
Note:Thisaudibleandvisualalarmwillremaintriggeredfora
shortperiodoftimeafteritsounds.Theaudiblecanbemutedus-
ingthemutebuttononthekeypad.THEPUMPWILLCONTINUE
TODISPENSEINTHISALARMMODE.
D. EMPTY ALARM
Activationofthisalarmindicatesthetankisemptyandneeds
lling.ThisalarmisshownthroughvisualLED’sandaudiblesiren.
Note:Thisaudibleandvisualalarmwillremaintriggeredfora
shortperiodoftimeafteritsounds.Theaudiblecanbemutedus-
ingthemutebuttononthekeypad.THEPUMPWILLCONTINUE
TODISPENSEINTHISALARMMODE.
E. BUND ALARM
Activationofthisalarmindicatesthatthereisproductinthebund
cavity.ThisalarmisshownthroughvisualLED’sandaudible
siren.Note:Thisaudibleandvisualalarmwillremaintriggered
constantlyuntilmutedoruntiltheproductisremoved.Theaudible
canbemutedusingthemutebuttononthekeypad.Intheeventof
thisitisadvisedthebundcavityischeckedanddrainedassoon
aspracticable.
F. FMS WIRING DIAGRAM
7. OPERATION OF THE SYSTEM

17
7.6.2 NOZZLE & INTEGRATED FLOWMETER (1350 | 2500)
A. INSTALLATION
Theautomaticnozzlesaresuppliedreadyforuse.
ThenozzlefeaturesaSWIVELhose-endtting(completewithO-ring)
usefulforconnectingtothesupplyhose.
TOENSUREPERFECTOPERATION,THEDEVICEMUSTBEUSED
TODISPENSEFLUIDSWITHCHARACTERISTICSFALLINGWITHIN
THEFOLLOWINGPARAMETERS:
-Qmin.:15l/min-Qmax:45l/min
-Pmin.:1,5bar-Pmax:3,5bar
Attention
During installation, use adequate sealants, being careful no residues
remain inside the hose.
Soasnottonegativelyaectproductoperation,couplethehose-end
ttingwiththehosewithoutusingtoolssuchaspliers,etc
Assemblywillbeeasieriftheswivelhose-endttingisalreadyttedon
thenozzle.
Makesurethehosesandthesuctiontankarewithoutthreadingscaleor
residueswhichcoulddamagethenozzleandtheaccessories
Warning
Apply adequate sealants on the male threads of the connections and
swivels
DonotuseTeontape
B. USE MODALITY
B1. MECHANICAL CHARACTERISTICS
Themainfeatureofthesenozzlesisthattheyareeasytouse.
Twooperatingmodesareavailable:
1 - Assisted Mode
Dispensebyoperatingthenozzlelever.Tointerruptdispensingmanually,
releasethelever.
2 - Automatic Mode
Usetheopeningleverlockdeviceforautomaticdispensing.
Tocontinuedispensingafterautomaticstop,thelevermustbefully
releasedbeforeproceedingtooperateitagain.
Tointerruptdispensinginmanualmode,presstheleveragain,thereby
releasingthedevice,andthenrelease.
Attention
DO NOT USE THE NOZZLE OUTSIDE THE PARAMETERS INDICATED
ON THE ”TECHNICAL SPECIFICATIONS” CHART
Dispensingisautomaticallyinterruptedthankstotheshut-o
device, which operates when the level of the liquid reaches the end
of the spout.
B2. ELECTRONIC CHARACTERISTICS
Attention
Theusercanchoosebetweentwodierentoperatingmodes:
1 - Normal Mode
ModewithdisplayofPartialandTotaldispensedquantities
2 - Flow rate Mode
ModewithdisplayofFlowRate,aswellasPartialdispensedquantity.
Note:Themeterfeaturesanon-volatilememoryforstoringthedispensing
data,evenintheeventofacompletepowerbreakforlongperiods.The
measurementelectronicsandtheLCDdisplayarettedinthetoppart
ofthemeterwhichremainsisolatedfromtheuidbythemeasurement
chamberandsealedfromtheoutsidebymeansofacover.
C. MISFILLING
Premise
ModewithdisplayofPartialandTotaldispensedquantities
Operation
The“magnetswitch”isamagneticeldwithinthellernecksofthe
nozzle.Thisopensthemagnetswitchinthespout,soitisonlypossibleto
dispensefromthetankwherethemagnetadaptorisinstalled.
Attention
Nozzlesequippedwith“magnetswitch”workonlyincombinationwith
the“magnetadapter”.The“magnetadapter”isanoptiontobebought
separately.
D. PRELIMINARY CHECK
Warning
Checkthecorrectoperationofthelockdevice,accordingtothefollowing
procedure:
1.Takeagraduatedreceptaclewithacapacityof20
litres(5gal)
2.Begindispensingintothereceptacle,setting
theleverintheminimumowposition,untilthe
receptacleisfull.
3.Keepingtheleveropen,makesurethespoutis
submergedbyabout5cm(2inches).
4.Thenozzlemuststop,withaclickofthelever
5.Repeatthesameoperationswiththeleverin
medium-owand
maximum-owposition.Checkthecorrectoperation
ofthestopdeviceasdescribedabove.
6.Ifthenozzlestopsduringdispensing,checkand
reducetheow.
7.Iftheshut-odevicedoesnotbegintooperate,
checktheminimumowrateofthesystemor
replacethenozzle.
E. INITIAL START UP
Onlystartdispensingaftermakingsurethatassemblyandinstallationhave
beencorrectlyperformed.
Attention
Itisgoodpracticetoonlyoperatethenozzleleveraftermakingsurethe
spouthasbeenproperlyinsertedinthemouthofthetanktobelled.
Note
Whenusingforthersttimeandeverytimethenozzleisused,following
theconnectionofthesupplyhose,gentlyoperatethelevertoenabletheair
toescapefromthecircuit,untilnormaloperationisachieved.
Attention
Checkthecorrectoperationoftheautomaticstopdeviceoncethetankis
full.
THE FAULTY OPERATION OF THIS DEVICE COULD CAUSE THE
SPILL OF LIQUIDS THAT ARE HAZARDOUS FOR PEOPLE AND THE
ENVIRONMENT.
F. WHAT IT LOOKS LIKE
The“LCD”oftheMETERfeaturestwonumericalregistersandvarious
indicationsdisplayedtotheuseronlywhentheapplicablefunctionso
requires.
1.Partialregister(5gureswithmovingcommaFROM0.1to99999)
indicatingthevolumedispensedsincetheresetbuttonwaslastpressed
2.Indicationofbatterycharge
3.Indicationofcalibrationmode
4.Totalsregister(6gureswithmovingcommaFROM0.1to999999),that
canindicatetwotypesofTotal:
7. OPERATION OF THE SYSTEM

18
7. OPERATION OF THE SYSTEM
1.GeneralTotalthatcannotbereset(TOTAL)
2.Resettabletotal(ResetTOTAL)
5.Indicationoftotalmultiplicationfactor(x10/x100)
6.Indicationoftypeoftotal,(TOTAL/ResetTOTAL);
7.IndicationofunitofmeasurementofTotals:
L=LitresGal=Gallons
8.IndicationofFlowRatemode
9.IndicationofunitofmeasurementofPartial:
Qts=QuartsPts=Pints
L=LitresGal=Gallons
F1. USER BUTTONS
TheMETERfeaturestwobuttons(RESETandCAL)whichindividually
performtwo
mainfunctionsand,together,othersecondaryfunctions.
Main functions performed
-fortheRESETkey,resettingthepartialregisterandResetTotal
-fortheCALkey,enteringinstrumentcalibrationmode
Secondary functions
Usedtogether,thetwokeyspermitenteringcongurationmodewhere
thedesiredunitofmeasurementcanbeset.
Legend
CALIBRATEMEANSPERFORMINGACTIONSONTHEMETERKEYS.
BELOWISTHELEGENDOFTHESYMBOLSUSEDTODESCRIBE
THEACTIONSTOBEPERFORMED
F2. BATTERY HOUSING
K24ispoweredbytwo1.5Vstandardtypebatteries(sizeAAA).The
batteryhousingiseasilyaccessibleandisclosedbyacoverwithseal.
Everythingiseasilyremovablebytakingotherubberprotectionaround
thenozzleandlooseningthescrewswhichsecurethecover.
G. DAILY USE
Theonlyoperationsthatneedtobedonefordailyusearepartialand/
orresettabletotalregisterresetting.Theusershoulduseonlythe
dispensingsystemofK24.Occasionallythemetermayneedtobe
conguredorcalibrated.Todoso,pleaserefertotherelevantchapters
Belowarethetwotypicalnormaloperationdisplays.Onedisplaypage
showsthepartialandresettotalregisters.Theothershowsthepartial
andgeneraltotal.Switchoverfromresettabletotaltogeneraltotal
displayisautomaticandtiedtophasesandtimesthatareinfactoryset
andcannotbechanged.
Note:
6digitsareavailableforTotals,plustwoiconsx10/x100.The
incrementsequenceisthefollowing:
0.0->99999.9->999999->100000x10->999999x10->100000x
100->999999x100
G1. DISPENSING IN NORMAL MODE
Normalmodeisthestandarddispensing.Whilethecountismade,the
partialandresettabletotalaredisplayedatthesametime(resettotal).
Warning: Shouldoneofthekeysbeaccidentallypressedduring
dispensing,thiswillhavenoeect.
Standby
Afewsecondsafterdispensinghasended,onthelowerregister,the
displayswitchesfromresettabletotaltogeneraltotal:thewordreset
abovethewordtotaldisappears,andtheresettotalisreplacedbythe
generaltotal.Thissituationiscalledstandbyandremainsstableuntilthe
useroperatestheK24again.
G1.1 PARTIAL RESET (NORMAL MODE)
Thepartialregistercanberesetbypressingthe
resetkeywhenthemeterisinstandby,meaning
whenthedisplayscreenshowstheword“TOTAL”.
Afterpressingtheresetkey,duringreset,the
displayscreenrstofallshowsallthelit-updigits
andthenallthedigitsthatarenotlitup.
Attheendoftheprocess,adisplaypageisrstof
allshownwiththeresetpartialandtheresettotal
and,afterafewmoments,theresettotalis
replacedbythenonresettableTotal.
G1.2 RESETTING THE RESET TOTAL
Theresettotalresettingoperationcanonlybe
performedafterresettingthepartialregister.The
resettotalcaninfactberesetbypressingthereset
keyatlengthwhilethedisplayscreenshowsreset
totalasonthefollowingdisplaypage:
Schematically,thestepstobetakenare:
1.Waitforthedisplaytoshownormalstandby
displaypage(withtotalonlydisplayed)
2.Presstheresetkeyquickly
3.Themeterstartstoresetthepartial
4.Whilethedisplaypageshowingtheresettotalis
displayed
Presstheresetkeyagainforatleast1second
5.Thedisplayscreenagainshowsallthesegments
ofthedisplayfollowedbyalltheswitched-o
segmentsandnallyshowsthedisplaypagewhere
theresetResetTotalisshown.
G2. DISPENSING WITH FLOW RATE MODE
DISPLAY
Itispossibletodispenseuid,displayingatthesame
time:
1.Thedispensedpartial
2.TheFlowRatein[PartialUnit/minute]asshownon
thefollowingdisplaypage:
Procedure for entering this mode:
1.WaitfortheRemoteDisplaytogotoStandby,meaningthedisplay
screenshowsTotalonly
2.QuicklypresstheCALkey.
3.Startdispensing
Theowrateisupdatedevery0.7seconds.Consequently,thedisplay
couldberelativelyunstableatlowerowrates.Thehighertheowrate,
themorestablethedisplayedvalue.
ATTENTION
Theowrateismeasuredwithreferencetotheunitofmeasurementof
thePartial.Forthisreason,incaseoftheunitofmeasurementofthe
PartialandTotalbeingdierent,asintheexampleshownbelow,it
shouldberememberedthattheindicatedowraterelatestotheunit
ofmeasurementofthepartial.Intheexampleshown,theowrateis
expressedinQts/min.
Theword“Gal”remainingalongsidetheowratereferstotheregisterof