TUV GR-2110/ST User manual

923211006_09_001
Page 1 from 4
SELF TESTING MAINTAINED EMERGENCY LUMINARY
GENERAL
o
These luminaires are used indoors (ta 40 C) where emergency
light is needed.
Each luminaire must be permanently connected to mains power
supply. In normal operation the illumination LEDs are lit as well
as the green indicating charge LEDs when the battery is
charging. In case of a mains power supply failure, the luminaire
enters in emergency mode and will light automatically. When the
mains power supply is restored the device turns to normal
operation.
INSTALLATION
To install the luminaire follow the installation instructions on page
3.
Battery Charging
The battery charging procedure is controlled by the processor,
thus maintaining its best possible preservation, as it extends its
duration.
Battery Cut-off
The luminaire enters this mode when the mains power supply
fails and battery has lost all its energy. During this operation the
luminaire enters the idle state and battery consumption is
negligible, in order to be protected from deep discharge.
Manual Operational Test
This test can be done by pressing the test
button. The light source and the emergency circuit of the device
are monitored for 3 sec. The manual test can be conducted only
if the mains power supply and the battery are connected. During
this test period all indication LEDs are OFF.
Automatic Operational Test
This test includes all the operations of the manual test and is
conducted automatically every 15 days. In order to be
performed, the mains power supply and the battery should be
connected.
Automatic Autonomy Test
The Automatic Autonomy Test measures the device’s back up
operation and emergency duration. This test is conducted
automatically every 6 months. In order to be performed, the
mains power supply and the battery should be connected and
fully charged. If the battery is not fully charged, the test is
postponed until the battery is completely charged. If during this
test, the autonomy is less than nominal, the battery fault led turns
on continuously and the battery must be replaced.
Emergency Operation
The autonomy duration of battery during emergency mode is at
least 90 or 180 minutes, depending on the model. During
emergency mode, a light source test is also performed.
Resetting Errors
Push the Test button for more than 10 seconds, to delete all the
indicated LED errors. Then the device enters regular operation
mode.
Indication LED status (with connected mains power supply).
Charge (Green LED)
Blink: Battery is charging.
On: Good charge condition.
Οff: No battery (No charging current
or disconnected battery).
Fault (Red LED)
Οn : Faulty LED strip (must be replaced) or emergency circuit
(must be checked by an authorized personnel).
Blink (With Charge LED ON): Autonomy or low battery problem
(the battery must be replaced).
Οff: LED strip and battery ok.
Connection to module
This luminaire can be connected to any of the following modules:
Remote module, address module, wireless module and fault
relay module. If you connect it to a module that supports inhibit
or rest mode, you should know that these commands can be
cancelled only during normal mode (ie. not in emergency). For
installation refer to step 5 of the istallation procedure in page 3.
Also refer to the user’s manual of each module for additional
information.
GR-2110/ST
Thank you for your trust in our products
Olympia Electronics - European manufacturer
220-240V AC/50-60Hz
3 h1.5 h
24 h16 h
IP30
3.6V/1.5Ah3.6V/600mAh
3.3W / 3.6VA
EN 60598-1, EN 60598-2-22, ΕΝ 55015, ΕΝ 61547, ΕΝ 61000-3-2, ΕΝ 61000-3-3
5 to 40 C
o
up to 95%
ABS/PC,PC
544gr.463gr.
292 x 111 x 54 mm
100lm / 100lm
22m
12 White LEDs
TECHNICAL CHARACTERISTICS (for LED MODULE Specs. see page 2)
OPERATION TEMPERATURE RANGE
RELATIVE HUMIDITY
EXTERNAL DIMENSIONS
CONSTRUCTION MATERIALS
TYPICAL WEIGHT
GUARANTEE
OPERATION VOLTAGE
MAXIMUM POWER CONSUMPTION
BATTERY (Ni-Cd)
CHARGING TIME
INDICATIONS - CONTROLS
MINIMUM AUTONOMY DURATION
DEGREES OF COVER PROTECTION
PRODUCED IN ACCORDANCE WITH
ILLUMINATION (230V AC / emergency)
VEWING DISTANCE
ILLUMINATION SOURCE
Battery and charge Fault indication LEDs, TEST button
3 years (1 year for the battery)
GR-2100/ST/M GR-2110/ST/M

923211006_09_001
Page 2 from 4
ΑΤΤΕΝΤΙΟΝ!!!
1. Operations for installation, maintainance or testing must be
done by authorized personnel only.
2. The device must be connected to the mains power supply
through a fuse dependent by the total amount of the line’s power
load.
t i
in battery recycling
points. Do not incinerate.
NOTE: LED= Light Emitting Diode
LABELING EXPLANATION:
X: Self contained
1: Maintained (*)
A: Including test device
F: Automatic test gear complying with IEC 61347-2-7 denoted
EL-T
*90: 1.5 hour duration
180: 3 hours duration
(*) Maintained operation: The luminaire lights its illumination
source, when it is powered by the mains power supply or not.
Non Maintained operation: The luminaire lights its illumination
source, only in power supply’s failure.
Battery replacement.
It can be done only by a competent person and after the mains
interruption.
1. Dismantle the device (step 1 of the installation instructions).
2. Disconnect the connector and remove the old battery.
3. Connect the new battery with the same type (step 4 of the
installation instructions) and place it in the position of the old one.
4. Follow the step 6 of the installation procedure and power the
device.
3. In case of inactive use for a period greater than 2 months,
disconnect the battery by pulling out the battery’s connector.
4. I s not allowed to discard batteries in to common trash
bins, they must be discarded only
LED MODULE CHARACTERISTICS
Manufacturer
Model Number
Voltage Range
Connections
Nominal Power
Temperature (tc)
Olympia Electronics S.A
45 °C max. across the board
Non reversible connection between main pcb and led module
8.7-10.8VDC
780mW
3105165
GR-2100/ST/M GR-2110/ST/M

923211006_09_001
Page 3 from 4
Figure 1
1. To instal the device you have to dismantle carefully the device with a flat screwdriver as
shown on figure 1.
2. Pass the mains cables through the hole (point 1 on figure 2). The luminaire must be
connected to a permanent electrical installation to ensure the immobilization of the cable.
3. Mount the base plastic on the wall by using the included mounting accessories in points 2
and 3 on figure 2.
4. Connect the battery`s cable with the appropriate terminal (figure 3).
5. Connect the mains cables to the respective detachable terminal block. Ν for neutral, L for live
wire and L1 for the maintained operation. The L1 wire can be connected to an external switch
to control the maintained or non maintained operation of the luminaire. For permanent maintained
operation use two wires to power the luminaire, Ν for neutral and L for live wire, and link the L and
L1. (figure 3) Minding the
correct polarity. Depending on the module that will be used, the cables that will be used, have
different names. In A, signal +L, C are also connected, while signals -L, NC/NO in the terminal B.
6. Refit with care the removed plastic parts and power on the luminaire.
If you use a module pass the 2 signal cables on the A, B terminals
Controled operation
of the illumination source
NOTE!!
After finishing the installation you must power the luminaire at least for 24 hours for battery charging to perform the nominal
autonomy.
INSTALLATION INSTRUCTIONS
2
3
Figure 2
Figure 4
1
N
N
L
L
External
switch
Link
Permanent
operation of the illumination source
N N
LL L1L1
Battery’s
connector
Figure 3
Α
Β

923211006_09_001
Page 4 from 4
The light source contained in this luminaire shall only be replaced by the manufacturer, or his agent, or a similar qualified person.
NOTE! The light source is non-user replaceable.
WARRANTY
Olympia Electronics guarantees the quality, condition and operation of the goods. The period of warranty is specified in the official catalogue of
Olympia Electronics and also in the technical leaflet, which accompanies each product. This warranty ceases to exist if the buyer does not follow
the technical instructions included in official documents given by Olympia Electronics or if the buyer modifies the goods provided or has any repairs
or re-setting done by a third party, unless Olympia Electronics has fully agreed to them in writing. Products that have been damaged can be
returned to the premises of our company for repair or replacement, as long as the warranty period is valid.
Olympia Electronics reserves the right to repair or to replace the returned goods and to or not charge the buyer depending on the reason of
defection. Olympia Electronics reserves the right to charge or not the buyer the transportation cost.
HEAD OFFICE
72nd km. O.N.R. Thessaloniki-Katerini
P.C. 60300 P.O. Box 06 Εginio Pierias Greece
www.olympia-electronics.gr
This manual suits for next models
2
Table of contents
Popular Lantern manuals by other brands

Sealite
Sealite SL-125 Series Installation & service manual

HOLOPHANE
HOLOPHANE MILWAUKEE LANTERN Installation and maintenance manual

NORDEON
NORDEON VIKING installation instructions

Saxby Lighting
Saxby Lighting 75271 Instruction leaflet

Heath Zenith
Heath Zenith 4395 Installation and operating instructions

WAGNER
WAGNER METALLICA manual