Tyco Visonic POWERMAXPRO Assembly instructions

D-302541 PowerMaxPro Installer's Guide 1
POWERMAXPRO
Fully Supervised Wireless Alarm Control System
Installer Guide
TABLE OF CONTENTS
1. INTRODUCTION.......................................................3
2. SPECIFICATIONS.....................................................3
2.1 General Data ...............................................................3
2.2 RF Section...................................................................4
2.3 Electrical Data..............................................................4
2.4 Communication............................................................4
2.5 Physical Properties......................................................4
3. INSTALLATION.........................................................4
3.1 Unpacking the Equipment............................................4
3.2 Supplying Power to the Unit.........................................4
3.3 System Planning & Programming................................4
3.4 Mounting......................................................................4
3.5 Back Unit Mounting and Wiring ...................................5
3.5.1 Phone Wiring............................................................5
3.5.2 Zones and Sirens Wiring ..........................................6
3.5.3 Installing an Optional X-10 Siren ..............................6
3.5.4 Dual RS-232 Module Mounting.................................7
3.5.5 Audio Module Mounting............................................7
3.5.6 Power Cable Connection..........................................7
3.6 Front Unit Preparation .................................................8
3.6.1 Backup Battery Insertion...........................................8
3.6.2 X-10 Interface Module Connection................................8
3.6.3 Optional GSM/GPRS Module Mounting....................8
3.7 Final Closure................................................................9
4. PROGRAMMING.....................................................10
4.1 INTRODUCTION .......................................................10
4.1.1 General Guidance...................................................10
4.1.2 Entering an Invalid Installer Code................................10
4.1.3 Installer’s Menu.......................................................10
4.1.4 Setting a New Installer Code ..................................10
4.1.5 Setting a New Installer Code in PowerMaxPro that
has 2 Installer Codes.......................................................10
4.2 ENROLLING WIRELESS SENSORS AND KEYFOB
TRANSMITTERS.............................................................11
4.2.1 General Guidance...................................................11
4.2.2 Enrolling Type.........................................................11
4.2.3 Enroll/Delete Sensors................................................11
4.2.4 Enroll/DeleteKeyfobTransmitters.................................11
4.2.5Enroll/DeleteWirelessCommander...............................11
4.2.6 Enroll/Delete 2-Way Keypad / Keyprox....................11
4.2.7 Enroll/Delete Wireless Siren....................................11
4.2.8 Enroll/Delete Proximity Tags....................................11
4.3 DEFINING ZONE TYPES, NAMES, CHIME ZONES
& PARTITION ..............................................................13
4.4 DEFINING CONTROL PANEL PARAMETERS....14
4.4.1 Preliminary Guidance..............................................14
4.4.2 Entry Delays 1&2......................................................14
4.4.3 Exit Delay................................................................14
4.4.4 Bell Time.................................................................14
4.4.5 Abort Time ..............................................................14
4.4.6 Alarm Cancel ..........................................................14
4.4.7 Quick Arm...............................................................14
4.4.8 Bypass....................................................................15
4.4.9 Exit Mode................................................................15
4.4.10 Piezo Beeps..........................................................15
4.4.11 Trouble Beeps ......................................................15
4.4.12 Panic Alarm ..........................................................15
4.4.13 Swinger Stop ........................................................15
4.4.14 Cross Zoning ........................................................15
4.4.15 Supervision...........................................................15
4.4.16 NOT READY.........................................................15
4.4.17 AUX Button A........................................................15
4.4.18 AUX Button B 2-W-KF.............................................16
4.4.19 Jam Detect............................................................16
4.4.20 Latchkey............................................................... 16
4.4.21 “Not Active” .......................................................... 16
4.4.22 Back Light ............................................................ 16
4.4.23 Duress.................................................................. 16
4.4.24 Piezo Siren........................................................... 16
4.4.25 Reset Option ........................................................ 16
4.4.26 Tamper Option..................................................... 16
4.4.27 Siren On Line ....................................................... 16
4.4.28 Memory Prompt.................................................... 16
4.4.29 Disarm Option ...................................................... 16
4.4.30 Bell/Rep. Option................................................... 16
4.4.31 Low-Bat Ack......................................................... 16
4.4.32 Screen Saver ....................................................... 16
4.4.33 Confirm Alarm ...................................................... 17
4.4.34 AC FAIL REP ....................................................... 17
4.4.36 User Permission................................................... 17
4.4.38 Battery Type......................................................... 17
4.4.39 Key Zones Options (Optional).............................. 17
4.5 DEFINING COMMUNICATION PARAMETERS... 19
Preliminary Guidance...................................................... 19
4.5.1 PSTN / GSM (Fig. 4.5) ............................................ 19
4.5.2 GPRS / BB (Fig. 4.5).............................................. 19
4.5.3 C.S. Reporting (Fig. 4.5) ........................................ 20
4.5.4 Private Report (Fig. 4.5).......................................... 22
4.6 GSM Auto Detection.............................................. 25
4.7 PowerLink Auto Detection..................................... 25
4.8 DEFINING OUTPUT PARAMETERS ................... 25
4.8.1 Preliminary Guidance............................................. 25
4.8.2 Define PGM............................................................ 25
4.8.3 Defining INT/STRB................................................. 25
4.8.4 X-10 GENERAL DEF................................................ 25
4.8.5 X-10 UNIT DEFINE................................................. 25
4.9 DEFINE VOICE..................................................... 27
4.9.1 Record Speech ...................................................... 27
4.9.2 Speech Box Mode.................................................. 27
4.10 DIAGNOSTIC TEST............................................ 28
4.10.1 GPRS Communication Test................................. 28
4.10.2 LAN Connection Test........................................... 28
4.10.3 LAN Reset............................................................ 28
4.11 USER FUNCTIONS ............................................ 29
4.12 RETRIEVING FACTORY DEFAULTS................ 29
4.13 SERIAL NUMBER............................................... 29
4.14 CALLING UPLOAD/DOWNLOAD SERVER....... 29
4.15 ENABLING/DISABLING PARTITIONS............... 30
4.16 DEFINING THE ARMING STATION................... 30
4.16.1 Tamper Type........................................................ 30
4.16.2 Screen Saver ....................................................... 30
4.16.3 Show AC Failure .................................................. 30
4.16.4 Supervision .......................................................... 31
4.16.5 Exit-Entry Beeps................................................... 31
4.16.6 Sounder Volume .................................................. 31
4.16.7 Show Mem/Trbl.................................................... 31
4.17 WALK-TEST........................................................ 31
5. TESTING PROCEDURES ...................................... 31
5.1 Preparations.............................................................. 31
5.2 Diagnostic Test ......................................................... 31
5.3 Keyfob Transmitter Test............................................ 31
5.4 Appliance ON/OFF Test............................................ 32
5.5 Emergency Transmitter Test..................................... 32
6. MAINTENANCE ...................................................... 32
6.1 Dismounting the Control Panel.................................. 32
6.2 Replacing the Backup Battery................................... 32
6.3 Fuse.......................................................................... 32

2 D-302541 PowerMaxPro Installer's Guide
6.4 Replacing/Relocating Detectors.................................32
7. READING THE EVENT LOG ..................................32
APPENDIX A. Partitioning...........................................33
A1. Programming Partitions.............................................33
A2. Defining Zones ..........................................................33
A3. Enrolling Keyfobs and Keypads.................................33
A4. User Interface and Operation....................................34
A5. Common Areas .........................................................34
APPENDIX B. Detector Deployment & Transmitter
Assignments................................................................36
B1. Detector Deployment Plan.........................................36
B2. Keyfob Transmitter List..............................................36
B3. Emergency Transmitter List.......................................37
B4. Non-Alarm Transmitter List........................................37
APPENDIX C. X-10 Unit & PGM Output Assignments37
APPENDIX D. Event Codes........................................38
D1. Contact ID Event Codes............................................38
D2. SIA Event Codes.......................................................38
D3. 4/2 Event Codes........................................................38
D4. Understanding the Scancom Reporting Protocol Data
Format .............................................................................39
APPENDIX E. Programmable Zone Types .................39
E1. Delay Zones ..............................................................39
E2. Emergency Zones..................................................... 39
E3. Fire Zones................................................................. 39
E4. Flood Zone................................................................ 39
E5. Gas Zone.................................................................. 39
E6. Interior Zone ............................................................. 40
E7. Interior Follower Zones............................................. 40
E8. Home/Delay Zones................................................... 40
E9. Non-Alarm Zones...................................................... 40
E10. Perimeter Zones..................................................... 40
E11. Perimeter Follower Zones....................................... 40
E12. Temperature Zone.................................................. 40
E13. 24-Hour Zones........................................................ 40
E14. Key Zones (Optional).............................................. 40
E15. Guard Zones........................................................... 40
E16. Outdoor Zones........................................................ 40
APPENDIX F. PowerMaxPro Compatible Devices..... 40
F1 Compatible Detectors................................................. 40
F2 Compatible Transmitters............................................ 42
F3 Compatible WL Siren................................................. 43
F4. Compatible Speech Box............................................... 43
F5. Compatible GSM Modem.......................................... 43
F6. PowerLink ................................................................. 43
F7.ProxTag...................................................................... 43
MESSAGE TO THE INSTALLER
The PowerMaxPro control panel is supplied with 2 instruction manuals:
Installer Guide (this manual - for your exclusive use)
User’s Guide (for your use during installation only - Must be handed over to the master user after testing the system).
Appendices A.1 and A.2 will help you prepare an installation plan. Please take time to fill out the forms - your job will
become much easier and confusion will be prevented. Filling out the forms will also help you create a list of detectors and
transmitters that must be obtained for the particular application. Compatible detectors and transmitters are listed and
described briefly in Appendix E.
Remember - it is advisable to power up the control panel temporarily after unpacking and program it on the work bench, in
accordance with the installation plan.
The programming flow charts in the programming section show all options available for each parameter. Factory defaults
are marked with a dark box to their right, and other options (that can be selected instead) are marked by clear boxes. This
method allows you to put a checkmark in the appropriate clear box whenever you deviate from the factory defaults.
Most of the programming section paragraph numbers correlate with the programming menu numbers. For example,
paragraph 4.4.19 describes the "Jam detect", that exists in menu 4 (define panel), sub-menu 19 (Jam detect).
Although setting the correct time and date is one of the user tasks, we recommend that you set the time and date in the
course of programming. Access to the “User Settings” for the installer is possible through item 10 on the installer‘s menu or
through the user menu (see User’s manual section 7).
After programming, proceed to install the system as detailed in the Installation Instructions, from paragraph 3.4 onward.
The installer should verify line seizure. Be aware of other phone line services such as DSL. If DSL service is present
on the phone line, you must install a filter. It is suggested to use the DSL alarm filter model Z-A431PJ31X
manufactured by Excelsus Technologies, or equivalent. This filter simply plugs into the RJ-31X jack and allows
alarm reporting without breaking the internet connection. If the user has a Voice over IP phone system only, the
control panel will not be able to communicate with the central station via the PSTN telephone line. In this case, the
user will either need to install an additional telephone line, or connect a GSM module.

D-302541 PowerMaxPro Installer's Guide 3
1. INTRODUCTION
The PowerMaxPro is a user and installer-friendly, 30-zone
fully-supervised wireless control system. The system is
designed to function in a way that appeals to the user but
also offers features that make installers’ life easier than
ever before.
The PowerMaxPro includes an optional partition feature.
Partitioning allows you to have up to three independently
controllable areas with different user codes assigned to each
partition or one user code assigned to a combination of up to
3 partitions. Partitions can be armed or disarmed individually
or altogether in one operation. For example, you can define
the garage as partition 1, the basement as partition 2 and the
house as partition 3. Since each partition is independent of
other partitions, you can arm or disarm each partition as
desired without altering the states of the other partitions.
EASY TO INSTALL
Plug-in terminal blocks in "Zones", "Dual RS-232" and
"Phone" modules, can be wired while detached from the
unit.
Quick attach-detach TELCO sockets for telephone line
and X-10 controller. Includes a terminal block for
telephone line & set.
Special wall-mounted bracket permits installation without
having to open the unit’s plastic casing.
Optional plug-in dual RS-232 module that enables a
concurrent connection of a PowerLink or local computer
(only 2 simultaneous device connections).
EASY TO MAINTAIN
Status, alarm memory and trouble data are displayed
upon request.
Diagnostic test provides visual and audible indication of
the signal level of each detector.
Remote control and status verification from distant
telephones.
Event log stores and displays information on 100 most
recent events.
Upload / download from distant computer via telephone
line and modem.
QUICK PROGRAMMING
Multiple-choice selection of options for each parameter.
Unequivocal visual prompts and audible signals.
Installer access to the user menu.
2. SPECIFICATIONS
2.1 General Data
Zones Number: 28 wireless, 2 hardwired (zones 29 & 30).
Hardwired Zone Requirements: 2.2 kE.O.L. resistance
(max. resistance of wires 220
Zone Types: Interior follower, interior, perimeter, perimeter
follower, delay 1, delay 2, 24h silent, 24h audible, fire, non-
alarm, emergency, gas, flood, temperature and home /
delay.
User Codes: 8 codes, 4 digits each (9999 different
combinations). Code 0000 is not allowed.
Control Facilities:
- Integral keypad
- PowerCode / Code-Secure™ hand-held transmitters
- One-way / two-way keypads
-Optional Built-In Proximity Tag Reader
- Web interface via optional PowerLink module
- SMS commands via optional GSM/GPRS module
- Remote control by telephone
Display: Single line, Backlit 16-character LCD.
Arming Modes: AWAY, HOME, AWAY-INSTANT, HOME-
INSTANT, LATCHKEY, FORCED, BYPASS.
Alarm inhibited during a single arming period (swinger
stop) after: 1, 2, 3, alarm/tamper/fault, or not inhibited
(programmable / selectable).
Alarm Types: Silent alarm, siren alarm or sounder
(internal) alarm, in accordance with zone attributes.
Siren Signals: Continuous (intrusion / 24 hours / panic);
triple pulse - pause - triple pulse... (fire).
Siren (bell) Timeout: Programmable
Internal Sounder Output: At least 85 dBA at 10 ft (3 m)
Supervision: Programmable time frame for inactivity alert
Special Functions:
- Speech and sound control
- X10 - an international and open industry standard for
communication among electronic devices used for home
automation (up to fifteen X-10 units)
- Chime zones
- Diagnostic test and event log
- Local and Remote Programming over Telephone, GSM
/GPRS connections
- Calling for help by using an emergency transmitter
- Tracking inactivity of elderly, physically handicapped and
infirm people
- Message center (recording and playback)
- Two-way voice communication
Data Retrieval: Status, alarm memory, trouble, event log.
Real Time Clock (RTC): The control panel keeps and
displays time and date. This feature is also used for the log file
by providing the date and time of each event. In addition, it is
used for the Scheduler where activity of a device is performed
according to a specific time and date selection.
Compliance with U.S. Standards:
Meets FCC Part 15 and Part 68 requirements. UL1637,
UL1635, UL1023, UL985, ULC-S545-02, ULC C1023, SIA
CP01
Compliance with Canadian Standards:
Meets RSS 210, ULC S545-02, ULC C1023, CSA C22.2#205
Compliance with CE Standards:
EN 50131-3, EN301489-3,7, EN 50130-4, EN60950, Aka
ETSI TS 0210, ATS-3 En 50131-1, ATS4 (S1,I2)
classifications according to EN 50136-1-1, EN50136-2-1
certified byTelefication
Compliance with UK Standards: This product is suitable
for use in systems installed to conform to PD6662:2010 at
Grade 2 and environmental class 2. DD243 and BS8243
According to the European standard EN50131-1, the
PowerMaxPro security grading is 2 –"low to medium risk"
and environmental classification is II –"indoor general" and
the power supply type is A.
The PowerMaxPro is compatible with the RTTE
requirements - Directive 1999/5/EC of the European
Parliament and of the Council of 9 March 1999.
GSM standards:
Europe : Complies with CE standards 3GPP TS 51.010-1,
EN 301 511, EN301489-7
USA: FCC 47 Part 22 (GSM850) and Part 24 (GSM
1900).
EMC standard: FCC 47 Part 15.
SAR standards: FCC rule 2.1093, FCC Docket 96-326 &
Supplement C to OET Bulletin 65

4 D-302541 PowerMaxPro Installer's Guide
2.2 RF Section
Operating Frequencies (MHz): 315, 433 or 868.95
Receiver Type: Super-heterodyne, fixed frequency
Receiver Range: 600 ft (180 m) in open space
Antenna Type: Spatial diversity
Coding: PowerCode and/or CodeSecure™
2.3 Electrical Data
Power Supply: Internal switching power supply (see Fig.
3.1f), optional external power supply (see section 3.5.6 and
Figure 3.1g) 100VAC to 240VAC, 50/60 Hz, 0.5A / 12.5
VDC, 1.6A.
Maximum Output Ripple: 5%
Current Drain: Approx. 40 mA standby, 1400 mA at full
load and in alarm.
Site External Siren Current (EXT): 450* mA max @ 10.5
VDC minimum when powered by AC & DC (battery).
Site Internal Siren Current (INT): 450* mA max. @ 10.5
VDC minimum when powered by AC & DC (battery)
PGM Output Current: 100* mA max.
Wired Detectors (zones 29 & 30) Total (Sum) Current:
450* mA max.
High Current / Short Circuit Protection: All outputs are
protected (automatic reset fuse).
* Total PowerMaxPro output current (of INT & EXT sirens,
PGM output and detectors) cannot exceed 550 mA.
Backup Battery Options:
Backup
period
Maximum external devices current (1)
9.6V 1800 mAh
Battery Pack (2)
9.6V 2200 mAh
Battery Pack (3)
1 battery
pack (4)
2 battery
packs (5)
1 battery
pack
2 battery
packs (5)
4h
240mA
400mA
300mA
600 mA
8h
100mA
200mA
140 mA
260 mA
12h
55mA
120mA
80 mA
160 mA
24h
0mA
40mA
25 mA
70 mA
36h
(no
backup)
15mA
10 mA
36 mA
48h
(no
backup)
0mA
0 mA
18 mA
The backup periods, when the PowerMaxPro includes
internal PowerLink with 1 active camera, GSM and
proximity reader, with external load connected between
+12 / V+ terminal and GND terminal, is as follows:
Battery Pack
type
Battery pack
Quantity
Backup
period
external
load (1)
9.6V 1800 mAh
(2)
1
10h
30mA
2
20h
16 mA
9.6V 2200 mAh
(3)
1
12h
50 mA
2
24h
27 mA
1Devices that are connected between +12 / V+
terminal and GND of PowerMaxPro, that includes
internal GSM and proximity reader.
29.6V 1800 mAh, rechargeable NiMH battery pack,
p/n GP180AAM8YMX, manufactured by GP.
39.6V 2200 mAh, rechargeable NiMH battery pack,
p/n GP220AAH8BMX, manufactured by GP.
4Standard / UL installation
5Extended backup installation
Maximum battery recharge time: 72 hours
Battery Test: Once every 10 seconds.
2.4 Communication
Built-in Modem: 300 baud, Bell 103 protocol
Data Transfer to Local Computer: Via RS232 serial port
Report Destinations: 2 central stations, 4 private
telephones.
Reporting Format Options: SIA, Pulse 4/2 1900/1400 Hz,
Pulse 4/2 1800/2300 Hz, Contact ID, Scancom.
Pulse Rate: 10, 20, 33 and 40 pps - programmable
Message to Private Phones: Tone or voice
2.5 Physical Properties
Operating Temp. Range: 14°F to 120°F (-10°C to 49°C)
Storage Temp. Range: -4°F to 140°F (-20°C to 60°C)
Humidity: 85% relative humidity, @ 30°C (86°F)
Size: 10-13/16 x 8 x 2-1/8 in. (275 x 203 x 55 mm)
Weight: 990g (2.2 pounds) without batteries
Color: Silver or white
3. INSTALLATION
Note: The system must be installed in accordance with
Chapter 2 of the National Fire Alarm Code, ANSI/NFPA 72.
3.1 Unpacking the Equipment
Open the cardboard packing box and check whether all
items have been included. If you find out that an item is
missing, contact your vendor or dealer immediately.
3.2 Supplying Power to the Unit
Connect power to the PowerMaxPro as described in
Figure 3.1f for internal power supply or in Figure 3.1g for
external power supply. Alternatively, you may power up
from the backup battery, as shown in Figure 3.1h.
Disregard any “trouble” indications pertaining to lack of
battery or lack of telephone line connection.
For Europe Safety Compliance:
a. The model shall be installed according to the local
electrical code.
b. The circuit breaker shall be readily accessible.
c. The rating of the external circuit breaker shall be 16A
or less.
d. The cables for the AC mains connection shall have an
overall diameter of 13mm and 16mm conduit.
Please refer to "Back Unit Power Cable Connection" in
Figure 3.1f.
3.3 System Planning & Programming
It pays to plan ahead - use the tables in appendices A and
B at the end of this guide to register the intended location
of each detector, the holder and assignment of each
transmitter and the control plan for the X-10 units.
Gather up all transmitters and detectors used in the system
and mark each one in accordance with your deployment
plan.
Program the system now as instructed in the
programming section.
3.4 Mounting
Required tool: Philips screwdriver #2.
PowerMaxPro mounting process is shown in Figure 3.1a -
3.1k.

D-302541 PowerMaxPro Installer's Guide 5
3.5 Back Unit Mounting and Wiring
Required tools: Cutter and slotted screwdriver - 3 mm
blade.
PowerMaxPro wiring is shown in Figures 3.1b and c.
Locate the terminal block housed in the expander card
located on the upper left side of the back unit and make
the necessary connections.
1
2
5
Fasten the back unit with 5 screws
4
Drill 5 holes and insert wall anchors
Release
screws
3
Position the back unit on the desired
mounting location and mark 5 drilling points
on mounting surface
Back unit
Back unit
Separate
the back unit
from the
front unit
Figure 3.1a –Back Unit Mounting
3.5.1 Phone Wiring
1
Connect the receptacles of supplied flat cables
(2 - 5 cables according to options) to the back unit’s plugs.
The receptacles with strain relief clip are for the
front unit - do not connect to the back unit!
For all countries except north America:
Connect telephone cable to SET connector
and telephone line cable to LINE connector
(through the desired wiring cable entry).
2
Strain relief clip
PHONE WIRING USING RJ CONNECTORS

6 D-302541 PowerMaxPro Installer's Guide
PHONE WIRING USING TERMINAL BLOCK CONNECTORS (NORTH AMERICA)
RJ-31X
CORD
HOUSE
PHONES
RJ-31X
8-POSITION
RJ-31X PLUG
BROWN
GRAY
GRN
RED LINE
FROM
STREET
12 3 4
5
6
7
RJ-31X JACK
GRAY
BROWN
RED
GREEN
Figure 3.1b –Phone Wiring
Phone wiring in the UK: Line terminals must be connected to pins 2 and 5 of the wall jack.
For all installations: If DSL service is present on the phone line, you must route the phone line through a DSL filter
(refer to MESSAGE TO THE INSTALLER on page 2 for further details).
3.5.2 Zones and Sirens Wiring
Figure 3.1c –Zones and Sirens Wiring
Notes:
* Zone 29/GND and Zone 30/GND terminals can be
connected to a normally closed contact of a detector,
switch (for example a Tamper switch of any device),
or a pushbutton, via a 2.2 K
resistor. The 12V
terminal can be used to supply 12V (up to 450mA)
to wired detectors (if necessary).
** Both +12V terminals are identical (shorted together).
The EXT terminal can be used to trigger an external
siren.
The INT terminal can be programmed for an "internal
siren" or "strobe" (see DEFINE OUTPUTS - DEFINE
INT/STRB in par. 4.8).
The +12V and "GND" terminals can be connected to a
siren (for constant DC power supply) –not
applicable in North America.
IMPORTANT! Total PowerMaxPro output current (of INT &
EXT sirens, PGM output and detectors) cannot exceed 550
mA.
3.5.3 Installing an Optional X-10 Siren
If you need a “wireless” external siren, you may install an
X-10 siren module which is triggered by a signal transmitted
via the built-in electrical wiring of the protected site. This
siren can replace the regular external siren or complement
it without laying out additional wires. Of course, such a siren
can be used only in conjunction with an optional power-line
interface module.
The X-10 siren is ready to function upon connection to an
electrical power outlet, without re-programming the
PowerMaxPro. You only have to set the HOUSE CODE and
the UNIT CODE selectors on the X-10 siren as follows:
House Code: Set this selector to the letter that follows, by
alphabetical order, the letter that you programmed as a
house code for the protected premises. For example, if the
programmed house code is “J”, set the siren house code
selector to “K”.
Note: If the programmed house code letter is “P” (which is
the last programmable letter), select “A” for the siren.
Unit Code: The siren will function only if you set the unit
code selector to “1”.

D-302541 PowerMaxPro Installer's Guide 7
3.5.4 Dual RS-232 Module Mounting
The control panel can be equipped with an optional dual
RS-232 module for serial data interchange with a local
computer (see Figure 3.1d). The dual RS-232 module
permits any two simultaneous device connections such as:
internal PowerLink, Local PC programming, and External
GSM module.
WARNING! When an Internal GSM module is connected,
the CELL/PC port of the Dual RS-232 module cannot be
used for PC connection. In this case, either remove the
Internal GSM or use the PL/PC connector.
RJ-45 or
RJ-31X (USA)
Dual
RS-232
adapter
Back Unit
Figure 3.1d - Connecting to a Computer
3.5.5 Audio Module Mounting
The Audio module allows the connection of an external wired
Speech box module. The Speech Box is a wired remote
speaker and microphone sensor for indoor use, which
provides remote audio capability to enable two-way voice
communication, between the user and the central station or
private telephone, via the PowerMaxPro control panel.
Press the dual RS-232 and AUDIO modules into the
marked locations (see Figure 3.1e), until a click is heard.
1
2
Connector for
internal
POWERLINK
or PC
Connector for
GSM or PC
1. Dual RS-232 module.
2. Audio Module
Note: The Audio
Module terminal strip
should be wired to the
external Speech Box
terminal strip, according
to the markings on both
terminal strips.
Figure 3.1e - Other Optional Modules Mounting
3.5.6 Power Cable Connection
Connect the power cable and close the control panel as
shown in Figure 3.1f.
Socket-outlet shall be installed near the equipment and
shall be easily accessible.
The connection of the power supply to the PowerMaxPro
unit can be performed through two options, as follows:
Through connection of the power cable to the internal
power supply, as shown in Figure 3.1f.
-or-
Through direct connection of the 12.5 VDC power supply
to the expander card via the wall mounted switched AC/DC
power supply (supplied by Visonic), as shown in Figure
3.1g.
Extract either of
these cable clamps
for use in the next
step.
12
Remove the cable
entry knockout(s)
and enter the power
cable.
Power supply
safety cover
Power cable clamp options
Power
supply unit
For thin
cable For thick cable
(reversed clamp)
a) Insert the power cable through the desired wiring channel (see step 1) and
route it to the power supply unit.
b) Pull out the power supply safety cover.
c) Connect the two wires of the power cable to the power supply terminal block
with screwdriver.
d) Verify that the wires are tightly fastened by the screws of the terminal block.
e) Fasten the power cable by its clamp (see also step 2 - this clamp can be
reversed to fit thick/thin cable)
f) Close the safety cover.
3Remove
and use as
cable entry
cover(s)
4
Power supply
terminal strip
Slide the cable entry
cover along the slots
until it snaps into
place
5
Figure 3.1f - Back Unit Power Cable Connection

8 D-302541 PowerMaxPro Installer's Guide
POWER CONNECTION FOR USA ONLY
12.5VDC
100-240V
50/60Hz
Wall Mounted
Switched AC/DC
Power Supply
Figure 3.1g –Wall Mounted Switched AC/DC Power Supply Connection
3.6 Front Unit Preparation
3.6.1 Backup Battery Insertion
Open battery compartment cover (see Figure 3.1h). Insert
one 8-battery pack and connect its connector to the
PowerMaxPro receptacle.
For optional two 8-battery packs: Insert both battery
packs and connect one battery pack connector to either
receptacles and the second battery pack connector to the
other receptacle.
Front
unit
Figure 3.1h - Battery Insertion
3.6.2 X-10 Interface Module
Connection
Connect the X-10 interface module connector to the
PowerMaxPro receptacle. Route the cable through the
cable channel and connect to the X-10 interface module,
via the back unit.
The X-10 jumper should be in 1-W position (for 1-way
power line interface unit) or in 2-W position (for 2-way
power line interface unit).
To X-10 interface
module via
the back unit
Cable
channel
6-position
RJ-11 plug
Front
unit
X-10
Jumper
Figure 3.1i - X-10 Interface Module Connection
3.6.3 Optional GSM/GPRS Module
Mounting
Caution! Do not insert or remove the GSM module when
the PowerMaxPro is powered by AC power or by battery.
Note: Refer to the PowerMaxPro GSM 350 Installation
Instructions.
Aligh the two slots of the
GSM Module with the
two leads on the front unit
1
2Push downward on
the GSM Module to make
sure that the pins of the
GSM Module are connected
firmly with its connector
3
Fasten the
GSM Module
with the screw
slot
lead

D-302541 PowerMaxPro Installer's Guide 9
1
Slide top
cover
Lock cover
to close
6
SIM card insertion
IMPORTANT
1.Before inserting SIM
card, deactivate its
PIN code (by using a
cellular telephone).
2.Do not insert or
remove SIM card
when the PowerMax
Pro is Powered byAC
power or battery.
4
Slide SIM
card into
cover
5
Rotate cover
to close
2
Open
cover Align SIM
card in cover
(note cover
orientation)
3
Figure 3.1j - Optional GSM/GPRS Module Mounting
3.7 Final Closure
Connect the flat cables in their respective
connectors (2 - 5, according to options).
1
Front
unit
Back
unit
2
Close the panel and
fasten the 2 screws.
Figure 3.1k - Final Closure

10 D-302541 PowerMaxPro Installer's Guide
4. PROGRAMMING
4.1 INTRODUCTION
Your system is equipped with a partitioning feature (in a
PowerMaxPro Partition system) that can divide your alarm
system into three distinct areas identified as Partition 1
through 3. Partitioning can be used in installations where
shared security systems are more practical, such as a
home office or warehouse building. When partitioned, each
zone, each user code and many of your system's features
can be assigned to Partition 1 to 3.
Note: When partition is disabled, all zones, user codes, and
features of the PowerMaxPro will operate as in a regular
unit. When partition is enabled, all zones, user codes, and
features of the PowerMaxPro are automatically assigned to
Partition 1.
4.1.1 General Guidance
We recommend to program the PowerMaxPro on the work
bench before actual installation. Operating power may be
obtained fromthe backup battery or fromthe AC power supply.
The installer’s menu is accessible only to those who know
the installer’s 4-digit code, which is 9999 by factory default.
Note: Access to the installer menu, in PowerMaxPro that
has "User Permission" enabled (for example in UK) is
accessible only at the end of the user menu. This option
can be changed if necessary (see par. 4.4.36).
For PowerMaxPro that has 2 installer codes, the default
MASTER INSTALLER code is 9999 and the default
INSTALLER code is 8888.
The following actions can be done only by using the
master installer code:
Changing master installer code.
Resetting the PowerMaxPro parameters to the default
parameters,
Defining specific communication parameters, as
detailed in a note in Figure 4.5.
Obviously, you are expected to use this code only once for
gaining initial access, and replace it with a secret code
known only to yourself.
You will mainly use 5 control pushbuttons during the entire
programming process:
- to move one step forward in a menu.
- to move one step backward in a menu.
-to enter the relevant menu or confirm data.
- to move one level up in a menu.
- to return to the "OK TO EXIT" state.
The sounds you will hear while programming are:
- Single beep, heard whenever a key is pressed.
- Double beep, indicates automatic return to the
normal operating mode (by timeout).
-Happy Melody (- - - –––), indicates successful
completion of an operation.
-Sad Melody (–––––), indicates a wrong move
or rejection.
4.1.2 Entering an Invalid Installer Code
If you enter an invalid installer code 5 times, the keypad
will be automatically disabled for a pre-defined period of
time and the message WRONG PASSWORD will be
displayed.
4.1.3 Installer’s Menu
The installer's menu is shown in Figure 4.1a. The text in
rectangles represents the current PowerMaxPro display.
4.1.4 Setting a New Installer Code
To set an installer code, perform the actions that are
presented in Figure 4.1b. When you are instructed to enter
code, enter a 4-digit code.
4.1.5 Setting a New Installer Code in
PowerMaxPro that has 2 Installer
Codes
For PowerMaxPro with 2 installer codes, MASTER
INSTALLER code (default 9999) and INSTALLER code
(default 8888), set new codes as shown in figure 4.1c.
For details regarding the different authorization levels
when logging in with installer code and master installer
code, refer to the note inside Figure 4.5 (DEFINE COMM).
By using the master installer code, the menu enables
changing both master installer code and installer code. By
using the installer code, the menu enables changing the
installer code only.
(*) Applicable only when "USER PERMIT" function is enabled
(see par. 4.4.36 - USER PERMIT).
Figure 4.1a - Installer’s Menu

D-302541 PowerMaxPro Installer's Guide 11
(See fig. 4.1a)
1. NEW INSTL CODE
NEW INST. CODE
INST. CODE xxxx
[code]
Figure 4.1b - Setting a New Installer Code (see note)
By using
INSTALLER CODE
INST. CODE xxxx
NEW INST. CODE
[code]
1. NEW INSTL CODE
(see fig. 4.1a)
(see fig. 4.1a)
[code]
1. NEW INSTL CODE
NEW MASTER CODE
MASTER CODE xxxx [code]
INST. CODE xxxx
NEW INST. CODE
By using
MASTER INSTALLER CODE
Figure 4.1c - Setting a New Installer Code
in System with Inst. & Master Inst. Codes (see note)
Note: Installer Code should never be programmed as
“0000”. Doing so will lock the user out of the installer menu!
4.2 ENROLLING WIRELESS SENSORS AND KEYFOB TRANSMITTERS
4.2.1 General Guidance
The ENROLLING mode has the following sub-modes:
ENROLLING TYPE (wireless sensors)
ENROLL SENSORS (enroll wired magnetic contact or
any other contact in zones 29 & 30 / enroll wireless
detectors in zones 01-28).
ENROLL KEYFOB (multi-button CodeSecure
transmitters)
ENROLL WL 1WAY KP (wireless commander MCM-140+)
ENROLL WL LCD KP (wireless 2-way keypad
MKP-150/151/152 or wireless 2-way keyprox MKP-160)
ENROLL WL SIREN (wireless siren)
ENROLL PROX TAG (proximity tag)
Before beginning, gather all the sensors that you intend to
enroll and make sure they all have batteries installed.
Your control panel must recognize the unique identification
code (ID) of each such sensor in order to supervise them,
receive their signals and respond accordingly.
Attention! CodeSecure transmitters are mainly used for
arming/disarming and can not be enrolled to zones. For
enrolling to zones, use only non-CodeSecure
wireless sensors.
4.2.2 Enrolling Type
Here you determine whether to enroll a wireless sensor by
normal transmission or by sensor Tamper function
(opening its cover). Options: normal, or by tamper.
4.2.3 Enroll/Delete Sensors
Wired and wireless sensors can be enrolled into the
PowerMaxPro. To enroll / delete sensors, refer to Figure 4.2.
STOP
Before enrolling, the lens at the front of PIR
and dual-technology sensors should be
masked to prevent inadvertent transmission.
Make sure that magnetic contact transmitters are
together with their magnets, to prevent them from
sending out alarm transmissions.
4.2.4 Enroll/Delete Keyfob Transmitters
Keyfob transmitters are multi-button wireless CodeSecure™
transmitters. Eight system users use them for better,
quicker and safer control over various system functions.
To enroll / delete 1-way or 2-way keyfob transmitters, refer
to Figure 4.2.
4.2.5 Enroll/Delete Wireless Commander
The Wireless Commander (MCM-140+) is a remote control
unit that enables the user to remotely control the system.
To enroll / delete up to 8 wireless commanders, refer to
Figure 4.2 (Enroll WL 1-way KP).
4.2.6 Enroll/Delete 2-Way Keypad /
Keyprox
The 2-way keypad, type MKP-150/151/MKP-152, or 2-way
keyprox, type MKP-160, enables the user to remotely
control the system and also to receive data from the
system (status, alarm and trouble data). To enroll up to two
2-way keypads, refer to Figure 4.2.
4.2.7 Enroll/Delete Wireless Siren
The wireless siren is a remote siren that is activated upon
predefined events by the PowerMaxPro system. To enroll /
delete up to 2 wireless sirens, refer to Figure 4.2.
4.2.8 Enroll/Delete Proximity Tags
Proximity tags enable authorized people to enter restricted
areas. Presenting valid proximity tag, while the system is
armed, causes the system to disarm. Presenting valid
proximity tag, while the system is disarmed, causes the
system to be armed in AWAY (optional HOME) mode. To
enroll / delete proximity tags, refer to Figure 4.2.
Note: Proximity tags are used on control panels with
installed Proximity readers (not standard on UK versions).

12 D-302541 PowerMaxPro Installer's Guide
Figure 4.2 - Enrolling / Deleting Wireless Sensors / Keyfobs / Wireless Commanders / Wireless Sirens
* Keyfob & proximity tags enrolling can be performed by
the installer or by the user (via USER SETTINGS
menu).
** Black box in the display means that a device is
enrolled (the system has learned its ID). No black
box indicates that the device is not enrolled.
*** Initiate either normal transmission or the sensor
tamper function (see ENROLLING TYPE, Par. 4.2.2).
Note: This changes the RF range during enrolling only
and does not affect the performance of the sensor.
**** Select "higher" sensitivity for far wireless sensor,
"lower" for near sensors.

D-302541 PowerMaxPro Installer's Guide 13
4.3 DEFINING ZONE TYPES, NAMES, CHIME ZONES & PARTITION
This mode allows you to assign one of 15 zone types to
each of the system's 30 (wireless & wired) zones. You can
define zones as KEY ZONES, to enable arming/disarming
of the system by PowerCode transmitters (see appendix
D14). In addition, it also allows you to assign a name and
partition number (up to three) to each zone and determine
whether the zone will operate as a chime zone. When a
chime zone is triggered, chime melody or zone name is
heard (there are 3 selectable chime modes - Melody chime,
Zone Name Chime or Chime Off).
A list of factory defaults is printed in table 1. You may fill
out the blank columns even before you start and proceed
to program according to your own list.
Remember!
A delay zone is also a perimeter zone by definition.
Zone types are fully explained in Appendix D.
Note: Custom Zone Name text can be changed through
the DEFINE VOICE menu.
Figure 4.3 - DEFINE ZONES Flow Chart
* The currently saved option is displayed with a dark box at the right side. To review the options, repeatedly click
or button, until the desired option is displayed, then click (a dark box will be displayed
at the right side).
** Key ON/OFF is an optional function that enables you to arm or disarm the system via zones 21-28, 29 or 21-29, provided
that "non-alarm" was pre-defined for these zones.

14 D-302541 PowerMaxPro Installer's Guide
Before enabling Key Zones, the following procedures must be performed:
1. Go to the "2. ENROLLING" menu and enroll the transmitter (for further instructions, see section 4.2).
2. Go to the "4. DEFINE PANEL" menu and enter the "39. KEY ZONES OPT" sub-menu. Then, select the desired Key Zone
option. After making your selection, press the button on the keypad (for further instructions, see section 4.4).
*** Available and enabled only by customer request.
**** Zone Type Definitions:
Inter-follow –a zone that is located between entry/exit zone and the alarm system control panel
Perimeter –a zone that relies on detectors to protect doors, windows and walls
Perim-follow –a non-entry/exit zone
Delay 1/2 –a zone that has programmable exit and entry delays
24h silent –a zone that initiates a silent alarm (the sirens do not function)
24h audible –a zone that initiates a siren alarm
Fire –a zone that uses smoke detectors and is permanently active
Non-alarm –used mainly to perform auxiliary remote control tasks such as opening/closing a gate, activating/deactivating
courtesy light, etc.
Emergency –used to send an emergency call to the central station or to private telephones
Gas –a zone thatdetects a gas leak and is permanentlyactive
Flood –a zone that detects a flooad leak and is permanently active
Interior –a zone that allows free movement within the protected area without initiating an alarm (when armed HOME)
Temperature –a zone used to detect both indoor and outdoor temperatures and is permanently active
Home/Delay –a zone type which functions as a delay zone when the system is armed HOME and as a perimeter-
follower zone when the system is armed AWAY
Guard –a zone that functions like a 24-hour audible zone, except that following a short time period after an alarm, the
alarm is disabled (to allow access to a metal safe by a Guard)
Outdoor –a zone for outdoor areas where an activated alarm does not indicate intrusion into the house
For a detailed explanation of the Zone Types, refer to Appendix E.
4.4 DEFINING CONTROL PANEL PARAMETERS
4.4.1 Preliminary Guidance
This mode allows you to customize the control panel and
adapt its characteristics and behavior to the requirements
of the particular user. An illustrated process is shown in
Figure 4.4. In this illustration, each selected option is
displayed with a dark box at the right side. To review the
options, repeatedly click or button, until
the desired option is displayed, then click SHOW/OK
button.
4.4.2 Entry Delays 1&2
(Fig. 4.4, location 01, 02). Two different entry delays allow
the user to enter the protected site (while the system is in
the armed state) via 2 specific doors and routes without
causing an alarm.
Following entry, the user must disarm the control panel
before the entry delay expires. Slow-rate warning beeps
start sounding once the door is opened, until the last 10
seconds of the delay, during which the beeping rate
increases. Locations No. 1 (entry delay 1) and 2 (entry
delay 2) allow you to program the length of these delays.
Available options for each delay are: 00s, 15s, 30s, 45s,
60s, 3m and 4m.
4.4.3 Exit Delay
(Fig. 4.4 location 03). An exit delay allows the user to arm
the system and leave the protected site via specific routes
and doors without causing an alarm. Slow-rate warning
beeps start sounding once the arming command has been
given, until the last 10 seconds of the delay, during which
the beeping rate increases. Location No. 3 allows
programming of the exit delay length. Available options
are: 30s, 60s, 90s, 120s, 3m, and 4m.
4.4.4 Bell Time
(Fig. 4.4, location 04). Here you select the length of time
the bell (or siren) is allowed to function upon alarm. The
bell time starts upon activation of the siren. Once the bell
time expires, the siren is automatically shut down.
Available options are: 1, 3, 4, 8, 10, 15 and 20 minutes.
Note: Bell Time is defined for the entire alarm system and
not per partition.
4.4.5 Abort Time
(Fig. 4.4 location 05). Here you select the length of time
allowed by the system to abort an alarm (not applicable to
alarms from FIRE, 24H SILENT, EMERGENCY, GAS,
FLOOD and TEMPERATURE zones). The PowerMaxPro
is programmed to provide an “abort interval” that starts
upon detection of an event. During this interval, the buzzer
sounds a warning but the siren remains inactive and the
alarm is not reported. If the user disarms the system within
the allowed abort interval, the alarm is aborted.
Available options are: 00s, 15s, 30s, 45s, 60s, 2m, 3m
and 4m.
4.4.6 Alarm Cancel
(Fig. 4.4, location 06). Here you determine the ”cancel
alarm” period that starts upon reporting an alarm to the
central station. If the user disarms the system within that
time period, a “cancel alarm” message is sent to the
central station.
Available options are: 1, 5, 15, 60 minutes, 4hours and
also cancel inactive.
4.4.7 Quick Arm
(Fig. 4.4, location 07). Here you determine whether the
user will be allowed to perform quick arming or not. Once
quick arming is permitted, the control panel does not
request a user code before it arms the system.
The two options are: quick arm ON and quick arm OFF.

D-302541 PowerMaxPro Installer's Guide 15
4.4.8 Bypass
(Fig. 4.4, location 08). Here you permit either manual
bypassing of individual zones (through the USER
SETTINGS menu), or allow the system to "force arm"
(perform automatic bypassing) of open zones during the
exit delay. If desired, press the arming key again if you want
to eliminate the protest tone that sounds during forced
arming. If a zone is open and forced arming is not
permitted, “NOT READY” is displayed and the system does
not arm (the “Sad Melody” will sound). If "no bypass" is
selected, neither manual bypassing nor force arming is
allowed.
Options: manual bypass, force arm and no bypass.
Note: Force arm is not applicable in the UK.
4.4.9 Exit Mode
(Fig. 4.4, location 09). Here you determine exit mode
options. Three types of exit modes are available:
Restart Exit - Exit delay restarts when the door is
reopened during exit delay. The restart occurs once only.
Restarting the exit delay is helpful if the user re-enters
immediately after going out to retrieve an item that he left
behind.
Off by door - When the door is closed, the exit delay is
automatically terminated (even if the defined exit delay
was not completed).
Normal - The exit delay is exactly as defined, regardless
of whether the door is open or closed.
4.4.10 Piezo Beeps
(Fig. 4.4, location 10). Here you determine whether
warning beeps will sound or muted during exit and entry
delays. Additional options enable muting only the warning
beeps when the system is armed “HOME” or "AWAY". In
addition, during arming home the system arms in silence,
however, once armed, triggering a delay zone will activate
the entry beeps prompting the user to disarm the system.
Options (Partition disabled): enable beeps, off when home,
disable beeps, and off exit home.
Options (Partition enabled): (enable beeps), H(off when
home) and (disable beeps) and h (off exit home). The
pushbuttons , , and provide selection of
the corresponding partitions. Pressing each button
repeatedly will toggle between each option.
Note: When exit beeps are disabled toward the end of a
delay, the happy (success) melody will sound.
4.4.11 Trouble Beeps
(Fig. 4.4, location 11). Under trouble conditions, the
sounder emits a series of 3 short beeps once per minute.
Here you determine whether this special beeping
sequence will be active, inactive, or just inactive at night
(the range of “night” hours is defined in the factory). The 3
options are: enable beeps, off at night (8 PM through 7
AM) and disable beeps.
4.4.12 Panic Alarm
(Fig. 4.4, location 12). Here you determine whether the
user will be allowed to initiate a panic alarm by
simultaneous pressing either the two panic buttons (on the
keypad / wireless commander) or away + home (on a
keyfob transmitter). Audible panic activates the siren and
simultaneously transmits a message via telephone. Silent
panic only transmits a message via telephone. The options
are: silent panic, audible panic and disable panic.
4.4.13 Swinger Stop
(Fig. 4.4, location 13). Here you determine the number of
times each zone is allowed to initiate an alarm within a
single arming period (including tamper & power failure
events of detectors, PowerMaxPro, wireless siren, etc.). If
the alarms number from a specific zone exceeds the
programmed number, the control panel automatically
bypasses the zone to prevent recurrent siren noise and
nuisance reporting to the central station. The zone will be
reactivated upon disarming, or 48 hours after having been
bypassed (if the system remains armed).
Available options are: shut after 1, shut after 2, shut
after 3 and no shutdown.
Note: Swinger Stop is defined for the entire alarm system
and not per partition.
4.4.14 Cross Zoning
(Fig. 4.4, location 14). Here you determine whether cross
zoning will be active or inactive. Cross zoning is a method
used to counteract false alarms - an alarm will not be
initiated unless two adjacent zones are violated within a
30-second time limit.
This feature is active only when arming AWAY and only
with zone couples from zone No. 18 to 27 (18 and 19, 20
and 21, etc.). You may use any one of these zone couples
to create a “cross-zoned” area.
Note: If one of two crossed zones is bypassed (see Para.
4.4.8), the remaining zone will function independently.
Note: Every 2 crossed zones must be of the allowed zone
type (Interior, Perimeter, Perimeter follower).
The options are: cross zone ON and cross zone OFF.
Note: A common zone should not be defined as a cross
zone.
Cross zoning is not applicable in Entry/ Exit zones and
24h zones (Fire, Emergency, 24h audible, 24h silent).
4.4.15 Supervision
(Fig. 4.4, location 15). Here you determine the time limit for
reception of supervision reports from various supervised
wireless devices. If any device does not report at least
once within the selected time limit, an “INACTIVITY” alert
is initiated.
The options are: 1, 2, 4, 8, 12 hours and disable.
4.4.16 NOT READY
(Fig. 4.4, location 16). Here you determine if the system
will be in NOT READY status when there is a supervision
failure. In the "in supervision" mode, the system will be in
NOT READY status if during the last 20 minutes a
supervision message was not received. Options: normal
and in supervision.
4.4.17 AUX Button A
(Fig. 4.4, location 17). Here you select the function of the
AUX button/ button A on keyfob transmitters MCT-234,
MCT-237 and wireless commanders MCM-140+. Four
options are offered for each AUX button:
Status: Pressing the AUX button will cause the control
panel’s voice module to announce the system status.
Instant: Pressing the AUX button while the exit delay is in
progress will cause the system to arm “instant” (the entry
delay is canceled).
Skip exit delay: Pressing the AUX button will immediately
cause the system to arm “instant”.
PGM / X-10: Pressing the AUX button will activate the
PGM output or X-10 units (see further programming under
“DEFINE OUTPUTS”, par. 4.8).

16 D-302541 PowerMaxPro Installer's Guide
4.4.18 AUX Button B 2-W-KF
(Fig. 4.4, loc. 18). Applicable only for 2-way keyfob
MCT-237. Same as 4.4.17 but for AUX button B.
4.4.19 Jam Detect
(Fig. 4.4, location 19). Here you determine whether
jamming (interfering transmissions, on the radio channel
used by the system) will be detected and reported or not.
If a jam detection option is selected, the system does not
allow arming under the relevant jamming conditions.
Jam Detection Options
Option
Detection and Reporting when
UL (20/20)
(USA standard)
There is continuous 20 seconds of
jamming
EN (30/60)
(Europe standard)
There is an accumulated 30 seconds of
jamming within 60 sec.
class 6 (30/60)
(British standard)
Like EN (30/60) but the event will be
reported only if the jamming duration
exceeds 5 minutes.
Disabled
(no jamming detection and reporting).
4.4.20 Latchkey
(Fig. 4.4, location 20). Here you determine whether the
system can be armed in the latchkey mode. If the system
is armed this way, a “latchkey” message will be sent to
specific telephones upon disarming by a “latchkey user”
(users 5-8 or keyfob transmitters 5-8). This mode is useful
when parents at work want to be informed of a child’s
return from school. You can record a name for latchkey
users. The options are: Latchkey ON and Latchkey OFF.
4.4.21 “Not Active”
(Fig. 4.4, location 21). Here you determine the time limit for
reception of signals from sensors used to monitor the
activity of sick, elderly or disabled people. If no sensor
detects and reports movement at least once within the
defined time limit, a “not-active” alert is initiated.
Options: 3, 6, 12, 24, 48, 72 hours and no act disable.
4.4.22 Back Light
(Fig. 4.4, location 22). Here you determine whether the
keypad back lighting will remain on at all times or will come
on when a key is pressed and go off within 10 seconds if
no further keystrokes are sensed.
The two options are: always on and off after 10 s.
4.4.23 Duress
(Fig. 4.4, loc. 23). A duress alarm (ambush) message can be
sent to the central station if the user is forced to disarm the
system under violence or menace. To initiate a duress
message, the user must disarm the system with the duress
code (2580 by default). Here you can change the code digits
or enter "0000" to disable the duress feature. The system
does not allow the user to program the duress code
saved in this memory location as an existing user code.
4.4.24 Piezo Siren
(Fig. 4.4, location 24). Here you determine whether the
internal siren will sound or remain silent upon alarm
(according to the user preference). Options: piezo siren
on, piezo siren off.
4.4.25 Reset Option
(Fig. 4.4, location 25). (Not applicable in the USA)
Here you determine whether the system can be rearmed
(after an event) by the user or only by the installer.
Options: user reset or engineer reset or anti code reset.
If Engineer Reset is selected, the system can be rearmed
only by the installer; by entering and exiting the installer
menu, by entering and exiting the event log (see section 7),
or by remote telephone. To perform Engineer Reset via the
telephone, establish communication with the PowerMaxPro
(see user guide, Remote Control by Telephone, steps 1-5)
and continue as follows:
a. [*], [installer code], [#]
b. Wait for 2 beeps
c. [*], [1], [#]
d. [*], [99], [#]
Visonic uses Technistore anti code reset. Installers should
check with their central station for a code version (seed
code) which needs to be entered in menu 4.4.35.
4.4.26 Tamper Option
(Fig. 4.4, location 26). Here you determine whether zone
tamper will be reported or ignored. Available options are:
zone tamper ON and zone tamper OFF.
4.4.27 Siren On Line
(Fig. 4.4, location 27). Here you determine whether the
siren will be activated or not when the telephone line fails
during system armed state. Available options are: enable
on fail, disable on fail.
4.4.28 Memory Prompt
(Fig. 4.4, location 28). Here you determine whether the user
will receive indication that an alarm has been activated.
Available options are: enable and disable.
4.4.29 Disarm Option
(Fig. 4.4, location 29) (Not applicable in the USA)
Here you determine when it is possible to disarm the system:
A. Any time.
B. In AWAY mode, during entry delay, by using the
PowerMaxPro keypad or wireless device (keyfob).
C. In AWAY mode, during entry delay, by using a wireless
device (keyfob) only (this is set as a default in UK to
comply with DD423).
D.During entry delay, or by using the PowerMaxPro
keypad in AWAY mode.
Options: any time, on entry all, on entry wireless, or
entry + away kp.
4.4.30 Bell/Rep. Option
(Fig. 4.4, location 30). Here you determine whether an
alarm will be initiated (siren / report) when there is a
supervision / jamming failure during AWAY arming state.
Available options are: EN standard and other. When "EN
standard" is selected, if there is supervision / jamming
failure during AWAY arming, the siren is activated and the
events are reported as tamper events. When "Other" is
selected, there is no such activity during AWAY arming.
4.4.31 Low-Bat Ack
(Fig. 4.4, location 31). Here you determine whether the user
will hear or will not hear low battery sound when he tries to
disarm the system with a keyfob whose battery voltage is
low. Available options are: keyfob L-B on (the user has to
acknowledge the keyfob low battery message) or keyfob
L-B off (the user does not have to acknowledge the keyfob
low battery message).
4.4.32 Screen Saver
(Fig. 4.4, location 32). Here you can determine that if no
key is pressed during more than 30 seconds the display
will read “PowerMax” (to prevent a possible intruder of
knowing the system status). You can determine that
normal display will return after pressing the button
followed by entering user code (Refresh by Code/Text by
Code) or after pressing any key (Refresh by Key/Text by
Key). When partition is enabled, you can also determine
that if no key is pressed during more than 30 seconds the
date and time will appear on the display. You can
determine that normal display will return after pressing the
button followed by entering user code (Clock by
Code) or after pressing any key (Clock by Key).

D-302541 PowerMaxPro Installer's Guide 17
If Refresh by Key/Text by Key is selected, the first
pressing of any key (except Fire and Emergency) will cause
normal display return and the second press will perform the
key function. Regarding the Fire and Emergency keys, the
first key press will cause normal display return and also will
perform the Fire/Emergency function.
Options (Partition Disabled): scrn saver OFF, refresh by
code, refresh by key.
Options (Partition Enabled): scrn saver OFF, text by code,
text by key, clock by code, clock by key.
4.4.33 Confirm Alarm
(Fig. 4.4, location 33). Here you determine that if 2
successive alarms will occur during a specific period, the
second alarm will be considered as a confirmed alarm
(for confirmed alarm reporting, (see par. 4.5.3).
Options: disable 30 min., 45 min., 60 min., or 90 min.
4.4.34 AC FAIL REP
(Fig. 4.4, location 34). Here you determine the time interval
between AC power failure occurrence and the failure
reporting. Options: 5 minutes, 30 minutes, 60 minutes or
180 minutes.
4.4.36 User Permission
(Fig. 4.4, location 36). Here you determine whether the
access to the INSTALLER MODE requires user permission.
If you select ENABLE, the installer mode will be accessible
only through the user menu after entering the user code.
Options: Enable, Disable.
4.4.38 Battery Type
(Fig. 4.4, location 38). Here you determine which type of
battery pack is used, so that the system will supply proper
charge current.
Options: 7.2V or 9.6V.
4.4.39 Key Zones Options (Optional)
(Fig. 4.4, location 39). Here you determine whether or not
the system can be armed and disarmed by zones 21-28,
29-30 or 21-30, provided that for these zones "non-alarm
type" and "z-key enable" was predefined (see par. 4.3 and
Appendix D14).
Key zones can be wireless or wired zones.
When using wireless key zones, you can install and use
the following transmitters:
MCT-100
MCT-102
MCT-302
MCT-320
When using wireless key zones, only the MCT-100 and
MCT-102 transmitters are used. The right pushbutton on
the MCT-102 transmitter or input 2 of the MCT-100
transmitter is used for arming in AWAY mode. The left
pushbutton on the MCT-102 transmitter or input 1 of the
MCT-100 transmitter is used for disarming.
When using wired key zones an open circuit arms the
alarm system in AWAY mode and a closed circuit changes
the state of the alarm system from AWAY mode to Disarm.
(For information on how to connect to wired key zones,
see Fig. 3.1C Zones and Sirens Wiring.)
IMPORTANT! Enrolment of the MCT-100 or MCT-102
transmitter must be performed via the right pushbutton on
the MCT-102 transmitter or input 2 of the MCT-100
transmitter (see section 4.3).
If the area includes MCT-302 and MCT-320 transmitters, a
closed circuit (the magnet is placed near the transmitter)
arms the alarm system in AWAY mode and an open circuit
(the magnet is moved away from the transmitter) changes
the state from AWAY mode to DISARM.
Note: Key Zones does not comply with Belgium TO14A
and EN 50131-5-3.
Caution! Arming the system using a transmitter
assigned to zones 21 and 28, or via wired zones 29
and 30 compromises security. This function is,
therefore, only available in specific PowerMaxPro
versions according to the customer's request.
Options: disable option, z. 21-28 enable, z. 29-30 enable,
or z. 21-30 enable.

18 D-302541 PowerMaxPro Installer's Guide
Figure 4.4 - DEFINE PANEL Flow Chart

D-302541 PowerMaxPro Installer's Guide 19
4.5 DEFINING COMMUNICATION PARAMETERS
Preliminary Guidance
This mode allows you to adapt the telephone
communication parameters to the local requirements.
Note: Defining communications via GPRS is applicable to
PowerMaxPro versions 5.2.07 and above.
Compatible central station receivers are:
Osborne-Hoffman model 2000, Ademco Model 685,
FBII Model CP220, Radionics Model D6500, Sur-Gard
Model SG-MLR2-DG and Silent Knight Model 9500.
IMPORTANT: In telephone number locations and account
number locations, you may be required to enter
hexadecimal digits. In telephone number locations, these
digits are used as codes to control the dialer:
Hex.
Digit
Keying
Sequence
Code
Significance
A
<#>
<0>
Applicable only at the beginning of a
number - the dialer waits 10 seconds
or waits for dial tone, whichever
comes first and then dials.
D
<#>
<3>
Applicable only at the beginning of a
number - the dialer waits 5 seconds
for dial tone and goes on hook if none
is received.
E
<#>
<4>
Applicable only in the middle of the
number - the dialer waits 5 seconds
F
<#>
<5>
Not applicable in phone numbers
Note: A "+" can be entered at the beginning of the line by
pressing and then .
To enter a series of digits, use the following keys:
<Numeric keypad> - to enter the number
- moves the cursor from left to right
- moves the cursor from right to left
- deletes everything after the cursor (to the right).
4.5.1 PSTN / GSM (Fig. 4.5)
Area Code [Fig 4.5.1(1)]
Here you enter the system tel. area code (up to 4 digits).
Line Prefix [Fig 4.5.1(2)]
Here you enter the number that is used as a prefix to
access an outside telephone line (if exists).
Dial Method [Fig 4.5.1(3)]
Here you determine the dialing method used by the
automatic dialer built into the PowerMaxPro control panel.
The options are: Pulse and tone (dtmf).
GSM Keep Alive [Fig 4.5.1(4)]
Here you prevent the GSM service provider from
disconnecting the GSM line if the user has not initiated any
outgoing telephone calls during the last 28 days.
The options are: disable and every 28 days.
Note: A test message is sent to the first available SMS
number. If this does not exist then it makes a call to the
first private number.
4.5.2 GPRS / BB (Fig. 4.5)
The GSM/GPRS module is capable of communicating with
the Central Station receiver by GPRS, GSM Voice and
SMS channels. Each of the channels can be separately
enabled or disabled in order to allow or prohibit the module
from using it for the event reporting. If all channels are
enabled, the GSM/GPRS module will always try GPRS
first. If fails, it will try GSM Voice. If fails, it will try any other
possible method (PSTN, Broadband) and only then it will
try SMS. This is due to the fact that SMS is the most
unreliable option of communication. Disabling any of the
GSM Module channels will cause the module to use a
different sequence than the one described above.
GPRS Report [Fig 4.5.2(1)]
Here you determine whether the alarm system will report
events to the central station via the GPRS channel.
The options are: disable and enable.
GSM Report [Fig 4.5.2(2)]
Here you determine whether the alarm system will report
events to the central station via the GSM voice channel.
The options are: disable and enable.
SMS Report [Fig 4.5.2(3)]
Here you determine whether the alarm system will report
events to the central station via the SMS channel.
The options are: disable and enable.
GPRS APN [Fig 4.5.2(4)]
Here you enter the name of the APN (Access Point) used for
the internet settings for the GPRS (up to 40 digits).
GPRS Username [Fig 4.5.2(5)]
Here you enter the username of the APN used for GPRS
communications (up to 30 digits).
GPRS Password [Fig 4.5.2(6)]
Here you enter the password of the the APN used for GPRS
communications (up to 16 digits).
The following table provides a list of the keys used by the
PowerMaxPro editor for the GPRS APN, GPRS Username,
GPRS Password menus and Custom Zone Name option.
Key
Functionality
Moves the cursor from left to right.
Long press for speed.
Moves the cursor from right to left.
Long press for speed.
Scrolls upward the sequence of inserted digits.
Long press for speed.
Scrolls downward the sequence of inserted digits.
Long press for speed.
Places cursor to extreme right position of edit
string and shows the last 16 digits of edit string.
Reverts to previous or top menu without saving
the edit string.
Reverts to "<OK> TO EXIT" without saving the
edit string.
Saves and reverts to previous menu.
Clears all digits to the right of cursor.
Clears one digit by cursor.
Selects between uppercase or lowercase digits.
Note: The "Й" digit replaces the "@" digit which is not
included in the PowerMaxPro editor.
Antenna Select [Fig 4.5.2(7)]
Here you determine which antenna will be used for the GSM.
Note: Applies to GSM 200 unit only.
The options are: internal antenna or external antenna.
SIM PIN Code [Fig 4.5.2(8]
Enter PIN code of the SIM card installed in the
PowerMaxPro unit (up to 16 digits).
Force Home Network [Fig 4.5.2(9]
Here you determine whether to force the SIM card to use
the home network only and not to select another network in
case the home network cannot be found.
The options are: disable and enable.

20 D-302541 PowerMaxPro Installer's Guide
LAN Settings [Fig 4.5.2(10)]
Note: The LAN Settings menu appears only if a Broadband
Module exists in the PowerMaxPro alarm system.
Enable DHCP [Fig 4.5.2(10a)]
Here you determine whether to obtain an IP address
automatically using a DHCP server or to enter an IP
address manually.
Toggles between DHCP enable and DHCP disable.
Note: When DHCP is enabled, the last IP number will be
changed to 200. In other words, it will take the form
xxx.xxx.xxx.200.
Manual IP [Fig 4.5.2(10b)]
Here you manually enter LAN parameters.
IP address –the IP address of the Broadband Module.
Subnet mask –the subnet mask used with the IP
address.
Default GW –the default gatewayof the Broadband Module.
Note: If DHCP is set to enabled the above entries will be
ignored.
Transport Protocol (Applicable in the USA only)
[Fig 4.5.2(11)]
Here you select the type of protocol used by the control
panel to transfer data over the internet.
The options are: TCP and UDP.
Session Timeout [Fig 4.5.2(12)]
Here you determine whether the control panel will stay
continuously connected via GPRS communication, or,
temporarily connected to receive event reports only.
The options are: off on timeout and always ON.
4.5.3 C.S. Reporting (Fig. 4.5)
Report Events [Fig 4.5.3(1)] –see note in Fig. 4.5
Here you determine which types of event will be reported
to central stations. Due to lack of space in the display,
abbreviations are used: alarm is “alrm”, alert is “alrt”and
open/close is “o/c”. The asterisk () is a separator between
events reported to central station 1 and events reported
to central station 2.
Messages are divided by type into four groups:
No.
Group
Events Reported
1
Alarms
Fire, Burglary, Panic, Tamper
2
Open/close
Arming AWAY, Arming HOME,
Disarming
3
Alerts
No-activity, Emergency, Latchkey,
Gas, Flood, Temperature
4
Maintenance
Low-battery AC failure
"Alarm" group has the highest priority and "Alert" group
has the lowest priority.
The selectable options are as follows:
Plan name
Sent to center 1
Sent to center 2
all -o/c backup
All but open/close
All but open/close if
center 1 doesn’t
respond
all all
All
All
all-o/c all -o/c
All but open/close
All but open/close
all –o/c o/c
All but open/close
Open/close
all (–alrt) alrt
All but alerts
Alerts
Alrm all (–alrm)
Alarms
All but alarms
Disable report
Nothing
Nothing
all backup
All
All if cent. 1 doesn’t
respond
Note: “All” means that all 4 groups are reported and also
trouble messages - sensor / system low battery, sensor
inactivity, power failure, jamming, communication failure etc.
1st Report Method [Fig 4.5.3(2)]
Here you define the 1st priority of method used to report
events.
The options are: disable, cellular, broadband and PSTN.
2nd Report Method [Fig 4.5.3(3)]
Here you define the 2nd priority of method used to report
events. If the method defined to report events in the 1st
priority fails, the control panel will attempt to report using
the method defined in the 2nd priority (see notes in 1st
Report Method).
The options are: disable, cellular,broadband and PSTN.
3rd Report Method [Fig 4.5.3(4)]
Here you define the 3rd priority of method used to report
events. If the method defined to report events in the 2nd
priority fails, the control panel will attempt to report using
the method defined in the 3rd priority (see notes in 1st
Report Method).
The options are: disable, cellular, broadband and PSTN.
Dual Reporting [Fig 4.5.3(5)]
Here you determine whether to report events using PSTN
and cellular at the same time instead of waiting for the 1st
method to fail before trying the 2nd method.
The options are: disable,PSTN & broadband, PSTN &
cellular and broadband & cell.
Receiver 1 Account No. [Fig 4.5.3(6)] - see note in
Fig. 4.5
Here you enter the number that will identify your specific
alarm control system to the 1st central station. The number
consists of 6 hexadecimal digits.
Receiver 2 Account No. [Fig 4.5.3(7)] - see note in Fig.
4.5
Here you enter the number that will identify your system to
the 2nd central station. The account number consists of 6
hexadecimal digits.
PSTN/GSM RCVR1 [Fig 4.5.3(8)] - see note in Fig. 4.5
Here you program telephone number of the 1st central station
(including area code, 16 digit max) to which the system will
report the event groups defined in Report Events.
PSTN/GSM RCVR2 [Fig 4.5.3(9)] - see note in Fig. 4.5
Here you program telephone number of the 2nd central station
(including area code, 16 digit max) to which the system will
report the event groups defined in Report Events.
IP RCVR 1 [Fig 4.5.3(10)]
Here you enter the IP address of the IP receiver that is
located in the 1st central station.
IP RCVR 2 [Fig 4.5.3(11)]
Here you enter the IP address of the IP receiver that is
located in the 2nd central station.
SMS RCVR 1 [Fig 4.5.3(12)]
Here you enter the telephone number of the SMS receiver
that is located in the 1st central station.
SMS RCVR 2 [Fig 4.5.3(13)]
Here you enter the telephone number of the SMS receiver
that is located in the 2nd central station.
PSTN Report Format [Fig 4.5.3(14)] - see note in Fig.
4.5
Here you select the reporting format used by the control
panel to report events to central stations.
The options are: SIA text Contact-ID SIA 4/2
1900/1400 4/2 1800/2300 Scancom (see Appendix C
- code lists).
4/2 Pulse Rate [Fig 4.5.3(15)] - see note in Fig. 4.5
Here you select the pulse rate at which data will be sent to
central stations if any one of the 4/2 formats has been
selected in PSTN Report Format.
The options are: 10, 20, 33 and 40 pps.
Table of contents
Other Tyco Control System manuals
Popular Control System manuals by other brands

KW
KW DIAJEKT Assembly, installation and operation instructions

Franke
Franke DVS SH07-020 Installation & operating instructions

RadioLink
RadioLink AT9S PRO instruction manual

Roger
Roger MCT62E installation manual

West Mountain Radio
West Mountain Radio TARGETuner manual

Idex
Idex Knight ILCS EDGE installation manual

dani alu
dani alu Barrial A60e installation guide

Vestil
Vestil BOL-R Series instruction manual

DriSteem
DriSteem Vapor-Logic Installation and operation manual

Scania
Scania 2.1 Operator's manual

Heidolph
Heidolph Intelligent evaporation Hei-VAC Control operating instructions

tbs electronics
tbs electronics H64 Installation instructions & user manual