UFM KATflow 210 User manual

Integrated Clamp-On Ultrasonic Flowmeter

Operating Instructions
© Copyright Katronic Technologies Ltd. 2 19 | Katronic® and KATflow® are registered trademarks of Katronic AG & Co. KG.
Subject to changes without prior notice. All rights reserved. | Soware version: 5. 5-7565 | Issue: OI_KF21 _V2 EN_1911
Official Katronic distributor for Benelux :
U-F-M B.V.
Argon 24
4751 XC Oud Gastel
The Netherlands
T +31 (0)165 855 655
www.u-f-m.nl

TABLE OF CONTENTS
TABLE OF CONTENTS
1 SAFETY INSTRUCTIONS, LEGAL REQUIREMENTS,
WARRANTY, RETURN POLICY 4
1.1 Symbols 4
1.2 Safety instructions 4
1.3 Warranty 5
1.4 Return policy 5
1.5 Legislative requirements 5
2 INTRODUCTION 6
2.1 Clamp-on transit-time flowmeter 6
2.2 Measuring principle 6
3 INSTALLATION 7
3.1 Unpacking and storage 7
3.1.1 Unpacking 7
3.1.2 Storage 7
3.1.3 Identification of components 8
3.2 Clamp-on sensor installation 9
3.2.1 Acoustic propagation 9
3.2.2 Straight pipe lengths 9
3.3 Installation location 1
3.4 Pipe preparation 12
3.5 Sensor mounting configurations
and separation distance 13
3.5.1 Reflection Mode 13
3.5.2 Diagonal Mode 13
3.5.3 Transducer separation distance 13
3.6 Flowmeter installation 14
3.6.1 Outline dimensions 14
3.6.2 Electrical connections 15
3.7 Clamp-on sensor mounting 15
3.7.1 Acoustic coupling gel 16
3.7.2 Correct positioning of the sensors 16
3.7.3 Sensor mounting with fixtures
and chains 17
4 OPERATION 18
4.1 Switching On/O 18
4.2 Battery charging 18
4.3 Keypad and display 19
4.3.1 Keypad key functions 19
4.3.2 Display icons and functions 21
4.4 Quick Setup Wizard 22
4.5 Measurement 25
4.5.1 Main process value display 25
4.5.2 Three-line display 25
4.5.3 Diagnostic display 25
4.5.4 Totaliser 26
4.5.5 Data logger 26
5 COMMISSIONING 27
5.1 Menu structure 27
5.2 Output configuration 35
5.2.1 Serial interface 36
5.2.2 Modbus RTU 36
5.2.3 HART® compatible output 37
5.2.4 Analogue current output /4 ... 2 mA 37
5.2.5 Analogue voltage output ... 1 V 38
5.2.6 Analogue frequency output (passive) 38
5.2.7 Digital open-collector output 38
5.2.8 Digital relay output 39
5.3 Input configuration 4
5.3.1 Pt 1 inputs 4
5.3.2 Analogue current input /4 ... 2 mA 4
5.4 Temperature compensation 41
5.5 Heat quantity measurement 41
5.6 Sound velocity measurement 41
5.7 Wall thickness measurement 41
5.7.1 Wall Thickness Gauge Wizard 42
5.8 Scope function 42
5.9 KATdata+ soware 42
6 MAINTENANCE 43
6.1 Service/Repair 43
7 TROUBLESHOOTING 44
7.1 Measurement diiculties and error messages 44
7.2 Data download diiculties 46
8 TECHNICAL DATA 47
8.1 Sound speed of selected pipe materials 47
8.2 Technical data of selected fluids 48
8.3 Dependence between temperature
and sound speed in water 51
9 SPECIFICATION 54
9.1 General 54
9.2 Flowmeter 54
9.3 Quantity and units of measurement 55
9.4 Internal data logger 55
9.5 Communication 55
9.6 KATdata+ soware 55
9.7 Process inputs 56
9.8 Process outputs 56
9.9 Clamp-on sensor: K1N 57
1 INDEX 58
11 APPENDIX A – Certificate of Conformity 59
12 APPENDIX B – Customer Return Note (CRN) 6
Operating Instructions KATflow 21 3/6

SAFETY INSTRUCTIONS, LEGAL REQUIREMENTS, WARRANTY, RETURN POLICY
1 SAFETY INSTRUCTIONS, LEGAL REQUIREMENTS, WARRANTY, RETURN POLICY
1.1 Symbols
Danger
This symbol represents an immediate hazardous situation which could result in serious
injury, death or damage to the equipment. Where this symbol is shown, do not use the
equipment further unless you have fully understood the nature of the hazard and have
taken the required precautions.
Attention
This symbol indicates important instructions which should be respected in order to
avoid damaging or destroying the equipment. Follow the precautions given in these in-
structions to avoid the hazard. Call our service team if necessary.
Call service Where this symbol is shown call our service team for advice if necessary.
Note This symbol indicates a note or detailed setup tip.
Operator key Operator keys are printed in bold typeface.
1.2 Safety instructions
•Do not install, operate or maintain this flowmeter without reading, understanding and following these operating in-
structions, otherwise injury or damage may result.
•Study these operating instructions carefully before the installation of the equipment and keep them for future refer-
ence.
•Observe all warnings, notes and instructions as marked on the packaging, on the equipment, and detailed in the oper-
ating instructions.
•Do not use the instrument under wet conditions with the battery cover removed or opened.
•Follow the unpacking, storage and preservation instructions to avoid damage to the equipment.
•Install the equipment and cabling securely and safely according to the relevant regulations.
•If the product does not operate normally, please refer to the service and troubleshooting instructions, or contact
Katronic for help.
4/6 Operating Instructions KATflow 21
ESC

SAFETY INSTRUCTIONS, LEGAL REQUIREMENTS, WARRANTY, RETURN POLICY
1.3 Warranty
•Any product purchased from Katronic is warranted in accordance with the relevant product documentation and as
specified in the sales contract provided. This is subject to the condition that it has been used for the purpose for which
it has been designed and operated as outlined in these operating instructions. Misuse of the equipment will immedi-
ately revoke any warranty given or implied.
•Responsibility for suitability and intended use of this ultrasonic flowmeter rests solely with the user. Improper installa-
tion and operation of the flowmeter may lead to a loss of warranty.
•Please note that there are no operator-serviceable parts inside the equipment. Any unauthorised interference with the
product will invalidate the warranty.
1.4 Return policy
If the flowmeter has been diagnosed to have a problem, it can be returned to Katronic for repair using the Customer Re-
turn Note (CRN) attached to the Appendix of this manual. Katronic regret that for health and safety reasons we cannot ac-
cept the return of the equipment unless accompanied by the completed CRN.
1.5 Legislative requirements
CE Marking
The flowmeter is designed to meet the safety requirements in accordance with sound
engineering practice. It has been tested and has le the factory in a condition in which it
is safe to operate. The equipment is in conformity with the statutory requirements of the
EC directive and complies with applicable regulations and standards for electrical safety
EN 61 1 and electromagnetic compatibility EN 61326. A CE Declaration of Conformity
has been issued in that respect, a copy of which can be found in the Appendix of these
operating instructions.
WEEE Directive
The Waste Electrical and Electronic Equipment Directive (WEEE Directive 2 12/19/EU)
aims to minimise the impact of electrical and electronic goods on the environment by
increasing re-use and recycling and by reducing the amount of WEEE going to landfill. It
seeks to achieve this by making producers responsible for financing the collection, treat-
ment, and recovery of waste electrical equipment, and by obliging distributors to allow
consumers to return their waste equipment free of charge. Katronic oers its customers
the possibility of returning unused and obsolete equipment for correct disposal and re-
cycling. The dustbin symbol indicates that when the last user wishes to discard this
product, it must be sent to appropriate facilities for recovery and recycling. By not dis-
carding this product along with other household-type waste, the volume of waste sent to
incinerators or landfills will be reduced and natural resources will be conserved. Please
use the Customer Return Note (CRN) in the Appendix for return to Katronic.
RoHS Directive All products manufactured by Katronic are compliant with the relevant aspects of the
RoHS Directive.
Operating Instructions KATflow 21 5/6

INTRODUCTION
2 INTRODUCTION
2.1 Clamp-on transit-time flowmeter
The KATflow 21 is a portable, battery operated ultrasonic flowmeter employing clamp-on sensors for the measurement
of liquids in full, enclosed pipes. Flow measurements can be undertaken without interruption of the process or interfer-
ence with the integrity of the pipeline. The clamp-on sensors are attached to the outside of the pipes. The KATflow 21
uses ultrasonic signals for measurement of the flow, employing the transit-time method.
Picture 1: Clamp-on ultrasonic flowmeter configuration
2.2 Measuring principle
Ultrasonic signals are emitted by a transducer installed on a pipe and received by a second transducer. These signals are
emitted alternately in the direction of flow and against it. Because the medium is flowing, the transit time of the sound sig -
nals propagating in the direction of flow is shorter than the transit time of the signal propagating against the direction of
flow. The transit-time dierence ∆t is measured and allows the determination of the average flow velocity along the path
of acoustic propagation. A profile correction is then performed to obtain the average flow velocity over the cross-sectional
area of the pipe, which is proportional to the volumetric flow rate.
Picture 2: Transit-time measuring principle
6/6 Operating Instructions KATflow 21

INSTALLATION
3 INSTALLATION
3.1 Unpacking and storage
3.1.1 Unpacking
Care should be taken when opening the box containing the flowmeter, any markings or warnings shown on the packaging
should be observed prior to opening. The following steps should then be taken:
•Unpack the flowmeter in a dry area.
•The flowmeter should be handled with care and not le in an area where it could be subject to physical shocks.
•If using a knife to remove packaging care should be taken not to damage the flowmeter or cables.
•The flowmeter package and contents should be checked against the delivery note supplied and any missing items re-
ported immediately.
•The flowmeter package and contents should be checked for signs of damage during transport and any problems re-
ported immediately.
•The vendor accepts no responsibility for damage or injury caused during the unpacking of the instrumentation sup-
plied.
•Excess packing materials should be either recycled or disposed of in a suitable way.
3.1.2 Storage
If storage is necessary, the flowmeter and sensors should be stored:
•in a secure location,
•away from water and harsh environmental conditions,
•in such a way as to avoid damage,
•small items should be kept together in the bags and small plastic boxes provided to avoid loss.
Operating Instructions KATflow 21 7/6

INSTALLATION
3.1.3 Identification of components
The following items are typically supplied (please refer to your delivery note for a detailed description):
•KATflow 21 portable flowmeter,
•Fuse (removed for transport),
•Clamp-on sensors (usually one or two pairs depending on pipe sizes to be measured),
•Sensor extension cable(s) (optional),
•Sensor mounting accessories,
•Coupling component,
•Measuring tape,
•Operating instructions,
•Calibration certificate(s) (optional),
•Temperature measurement probe(s) (optional),
•Wall thickness measurement probe (optional),
•Connector lead for process inputs and outputs (optional).
8/6 Operating Instructions KATflow 21

INSTALLATION
3.2 Clamp-on sensor installation
The correct selection of the sensor location is crucial for achieving reliable measurements and high accuracy. Measure-
ment must take place on a pipe in which sound can propagate (see Section 3.2.1 Acoustic propagation) and in which a ro-
tationally symmetrical flow profile is fully developed (see Section 3.2.2 Straight pipe lengths).
The correct positioning of the transducers is an essential condition for error-free measurements. It ensures that the sound
signal will be received under optimal conditions and evaluated correctly. Because of the variety of applications and the
dierent factors influencing the measurement, there can be no standard solution for the positioning of the transducers.
The correct position of the transducers will be influenced by the following factors:
•diameter, material, lining, wall thickness and general condition of the pipe,
•the medium flowing in the pipe,
•the presence of gas bubbles and solid particles in the medium.
Aer the sensor location has been selected, make sure that the supplied cable is long enough to reach the flowmeter
mounting location.
Check that the temperature at the selected location is within the operating temperature range of the transducers
(see Chapter 9).
3.2.1 Acoustic propagation
Acoustic propagation is achieved when the flowmeter is able to receive suicient signal from the transmitted ultrasonic
pulses. The signals are attenuated in the pipe material, the medium and at each of the interfaces and reflections. External
and internal pipe corrosion, solid particles and gas content in the medium contribute heavily to signal attenuation.
3.2.2 Straight pipe lengths
Suicient straight lengths of pipe on the inlet and outlet of the measuring location ensure an axi-symmetrical flow profile
in the pipe, which is required for good measurement accuracy. If insuicient straight lengths of pipe are available for your
application measurements are still obtainable, but the certainty of the measurement can be reduced.
Operating Instructions KATflow 21 9/6

INSTALLATION
3.3 Installation location
Select an installation location following the recommendations in Table 1 and try to avoid measuring:
•in the vicinity of deformations and defects of the pipe,
•near welding seams,
•where deposits could be building up in the pipe.
For a horizontal pipe:
Select a location where the transducers can be mounted on the side of the pipe, so that the sound waves emitted by the
transducers propagate horizontally in the pipe. In this way, the solid particles deposited on the bottom of the pipe and
the gas pockets developing at the top will not influence the propagation of the signal.
For a free inlet or outlet pipe section:
Select the measuring point at a location where the pipe cannot run empty.
For a vertical pipe:
Select the measuring point at a location where the liquid flows upward to ensure that the pipe is completely filled.
Table 1: Recommendations for sensor mounting location
Look for a sensor installation location with suicient straight pipe to obtain accurate measurements. Please refer
to Table 2 as a guideline for recommended distances from disturbance sources.
1 /6 Operating Instructions KATflow 21

INSTALLATION
Disturbance source: 9 °-elbow
Inlet
L ≥ 1 D
Outlet
L ≥ 5D
Disturbance source: 2 x 9 °-elbow in one plane
Inlet
L ≥ 25D
Outlet
L ≥ 5D
Disturbance source: 2 x 9 °-elbow in dierent planes
Inlet
L ≥ 4 D
Outlet
L ≥ 5D
Disturbance source: T-section
Inlet
L ≥ 5 D
Outlet
L ≥ 1 D
Disturbance source: diuser
Inlet
L ≥ 3 D
Outlet
L ≥ 5D
Operating Instructions KATflow 21 11/6

INSTALLATION
Disturbance source: reducer
Inlet
L ≥ 1 D
Outlet
L ≥ 5D
Disturbance source: valve
Inlet
L ≥ 4 D
Outlet
L ≥ 1 D
Disturbance source: pump
Inlet
L ≥ 5 D
Table 2: Recommended distances from disturbance sources
3.4 Pipe preparation
•Clean dirt and dust from around the area of the pipework where the sensors are to be placed.
•Remove loose paint and rust with a wire brush or file.
•Firmly bonded paint does not necessarily need to be removed provided the flowmeter diagnostics indicate
suicient signal strength.
12/6 Operating Instructions KATflow 21

INSTALLATION
3.5 Sensor mounting configurations and separation distance
3.5.1 Reflection Mode
The most common clamp-on sensor mounting configuration is the Reflection Mode, sometimes known as V-Mode (see
Picture 3, sketch 1). Here, the ultrasonic signal passes twice through the medium (two signal passes). The Reflection Mode
is the most convenient mounting method as the transducer separation distance can be measured easily and the sensors
can be accurately aligned. This method should be used whenever possible.
Picture 3: Clamp-on sensor mounting configurations and sensor spacing
3.5.2 Diagonal Mode
An alternative mounting configuration (see Picture 3, sketch 3) is the Diagonal Mode (Z-Mode). The signals travel only once
through the pipe. This method is oen used for larger pipes where greater signal attenuation might occur.
Further variation of the Reflection and the Diagonal Modes are possible by altering the number of passes through the pipe.
Any even number of passes will require mounting the sensors on the same side of the pipe, while with an odd number of
passes, the sensors must be mounted on opposite sides of the pipe. Commonly, for very small pipes, sensor mounting
configurations such as four passes (W-Wrap Mode) or three passes (N-Wrap Mode) are used (see Picture 3, sketch 2).
3.5.3 Transducer separation distance
The transducer separation distance A is measured from the inside edges of the sensor heads as shown (see Picture 3). It is
automatically calculated by the flowmeter based on the parameter entries for pipe outside diameter, wall thickness, lining
material and thickness, medium, process temperature, the sensor type and the selected number of signal passes.
A negative separation distance A < can occur for mounting configurations on small pipes where Diagonal Mode
operation has been selected (see Picture 3, sketch 3). Negative separation distances may be suggested for Reflec-
tion Mode installations, but are not possible. In these cases, use Diagonal Mode or a larger number of passes.
Operating Instructions KATflow 21 13/6

INSTALLATION
3.6 Flowmeter installation
3.6.1 Outline dimensions
The KATflow 21 is a portable, battery operated device with the following outline dimensions (Picture 4).
Picture 4: Outline dimensions KATflow 21
130°C
-30 to
1334
K1N
ODU
Picture 5: K1N type transducers
14/6 Operating Instructions KATflow 21
ENTER
ON
ESC
OFF
LIGHT
ENTER
ON
ESC
OFF
LIGHT
ON
OFF
T
E
X
1 2
87
pqrs tuv
54
M
ghi j l
U
X
Q
abc
-
Q
N
Q
P
S
3
9
T
0
wxyz
6
mno
R
E
C
I
D
def
+
Q
D
I
ENTER
ON
ESC
OFF
LIGHT

INSTALLATION
3.6.2 Electrical connections
Picture 6: Electrical connection diagram KATflow 21
3.7 Clamp-on sensor mounting
Before the sensors can be mounted
•the installation location should have been determined,
•a sensor mounting method should be chosen,
•the flowmeter batteries must be suiciently charged,
•the sensors must be connected to the transmitter.
Depending on which sensor mounting method is being used, the clamp-on sensors are either mounted on the same side
of the pipe (Reflection Mode) or on opposite sides of the pipe (Diagonal Mode). The sensor spacing is calculated by the
flowmeter from the pipe parameters entered (see Section 3.5).
Operating Instructions KATflow 21 15/6

INSTALLATION
3.7.1 Acoustic coupling gel
In order to obtain acoustical contact between the pipe and the sensors, apply a bead of acoustic coupling gel
lengthwise down the centre of the contact area of the sensors.
Picture 7: Application of acoustic coupling gel
3.7.2 Correct positioning of the sensors
Always mount the transducer pair so that the free front edges of the sensors face each other. There is a dierent
engraving on the top of each transducer. The transducers are mounted correctly if the engravings on the two
transducers form an arrow. The transducer cables should point in opposite directions. Later, the arrow, in con-
junction with the indicated measured value, will help to determine the direction of flow (see Section 3.3).
The sensor separation distance is automatically calculated by the flowmeter based on the parameter entries for
pipe outside diameter, wall thickness, lining material and thickness, medium, process temperature, the sensor
type and the selected number of signal passes. The sensor positioning screen (see Section 4.4) allows fine adjust-
ment of the sensor location.
Picture 8: Correct positioning of the sensors
16/6 Operating Instructions KATflow 21

INSTALLATION
3.7.3 Sensor mounting with fixtures and chains
•Insert the retaining clip into the groove on the top of the transducer and secure it using the screw knob.
•Apply some acoustic coupling component to the contact surface of the transducer.
•Place the transducer on the side of the pipe or alternatively up to 45 degrees from the horizontal plane
through the pipe. This is advisable to establish the best acoustic contact since on top of the pipe air pockets
could develop and deposits could accumulate at the bottom of the pipe.
•Take the spring end of the chain in one hand and insert the last ball element in the vertical slot of the retain-
ing clip. Mount the chain around the pipe.
•Pull the chain firmly around the pipe and fasten it in the lateral slot of the retaining clip. There should be no
air pockets between the transducer surface and the pipe wall.
•Mount the second transducer the same way.
•Using a measuring tape, adjust the sensor separation distance as suggested by the flowmeter. When the
sensor positioning screen is displayed, the middle bar allows fine adjustment of the sensor location.
Picture 9: Sensor mounting with clips and chains
Picture 1 : Sensor mounting clip
Operating Instructions KATflow 21 17/6

OPERATION
4 OPERATION
4.1 Switching On/O
The flowmeter is switched on by holding the key for more than two seconds continuously. Equally it can be switched
o by pressing the key for more than two seconds.
When switching on, the flowmeter will perform a hardware and soware check, including the data logger space. Progress
will be indicated by a series of dashes above and a black bar below.
4.2 Battery charging
The internal batteries can be recharged with the external battery charger supplied.
Important: Ensure that only Nickel Metal Hydride (NiMH) AA size rechargeable batteries are installed – attempting
to recharge other battery types is dangerous and may cause damage.
Connect the battery charger to the charging socket of the flowmeter and to the mains supply 1 ... 24 V AC, 5 /6 Hz.
The battery charger mains plug is supplied for specific countries as shown in the order code.
The red mark on the plug aligns with the mark on the socket. Remove plug by sliding the outer casing away from the
socket to release the latch.
During the charging process, the battery icon will blink. For a fully charged battery all segments of the battery icon will be
filled. Battery charge level is also shown in the diagnostic displays.
-
+
Picture 11: Battery charging
18/6 Operating Instructions KATflow 21

OPERATION
4.3 Keypad and display
Picture 12: Keypad and display KATflow 21
Customer-specific settings for data to be displayed can be achieved by using the appropriate menu items.
4.3.1 Keypad key functions
! " #$%$&#$'()& ) $)" &$)"%$&#$
1 (1 short key stroke)
, (2 short key strokes)
. (3 short key strokes)
_ (4 short key strokes)
Show * available item
A
B
C
2
/
+ = Start/reset totaliser function
Adjust screen brightness/contrast (long
key stroke)
D
E
F
3
?
Show next ,lay
Operating Instructions KATflow 21 19/6

OPERATION
! " #$%$&#$'()& ) $)" &$)"%$&#$
G
H
I
4
<
+-= Reset negative total value
J
K
L
5
>
–
M
N
O
6
$
+. = Reset positive total value
P
O
R
S
7
–
T
U
V
8
*
+ = Stop totaliser function
W
X
Y
Z
9
, access to trend plot
(␣Space character)
+
=
#
–
Move menu/list selection item UP Character entry:
← (backspace) clear
Move menu/list selection item , Character entry:
- (minus sign)
. (decimal point) Switch LCD backlight on/o
ESCape menu item Abort entry without saving
Switches the instrument o if pressed
for more than 2 s
ENTER menu item Confirm entry with saving
Switches the instrument on if pressed
for more than 2 s
Table 3: Keypad key functions
2 /6 Operating Instructions KATflow 21
Other UFM Measuring Instrument manuals