Uni-Line ASD-10QR User manual

ASD-10QR
smoke alarm using radio links
User Manual
Safety issues
Please follow the recommendations
•Loud test signal will sound during the function test (see Test mode). Keep safe distance of 50 cm
between your ear and the alarm.
•Do not paint the alarm.
•Do not locate smoke alarms in highly apourized premises such as bathrooms, saunas and kitchens
Features
•Q-label for higher quality
•Infinite number of smoke alarms can be radio interlinked with possibility to transmit Remote Alarm
and Remote low battery signals.
•Simple generation of the unique code and wireless interlinking
•Different sounding of Alarm and Remote Alarm modes
•Secure fire detection by intellectual sensiti ity calibration using integral microcontroller and
intellectual analysis of smoke chamber signal
•Drift compensation (including smoke chamber contamination). This mechanism automatically
adjusts sensiti ity of the smoke alarm to the factory le el during operation

•Audible indication of exceeding the threshold compensation le el (signal to cleaning the smoke
chamber from dust)
•New technical solutions were applied thanks to which influence of electromagnetic interferences
and temperature change has been reduced.
•Different ways of mounting (screws/adhesi e pads)
•Fluent sound olume increase (fade-in) in Alarm, Remote Alarm and Test modes
•Hush function – muting of local alarm signal for approx. 10 min. by pushing the Test button.
•
You will hear a sound signal of the last fault when remo ing the alarm from the base
•You will hear the rele ant sound signal in case of fault when remo ing the alarm from the base
•
Supports test RF remote control
Specifications
Standby current consumption ≤ 12 µА
Alarm current consumption ≤ 90 mА
RF frequency 868.100 (<1% duty cycle)
RF Codes 65535
RF Power +14 dBm max
RF range 100 meters min air free
Battery life at least 10 years under normal conditions
Battery type sealed, Lithium, AA, 3.0V
Hush time 10 ±2min.
Alarm and Remote Alarm sound le el > 85dB at 3 m
Light and sound indication
Standby mode, Alarm,
r
emote Alarm, low battery,
remote low battery, smoke chamber fault,
exceeding the ultimate compensation le el
(see Sound and Light signals table)
Operating temperature range 0 – 55° C
Operating humidity < 93% RH at 40° C
Dimensions Ø80 х 45 mm
Appro als
EN 14604, CE, VdS3131, VdS
3515
, DIN 14676
,
R&TTE
Audible and visual signals
Audible signal Red LED Function
No signal flashes e ery 320 sec
Standby mode,
periodical automatic self-diagnostics
Long intermittent
signal flashes e ery 0.5 сек. Alarm status
Long intermittent
signal
(different from the
latter)
off
Remote Alarm status.
One of the interlinked alarms went to Alarm
status

One short signal e ery
40 sec. off Low battery status.
You should replace the alarm
Two short signals
e ery 4 h off
Remote
low
battery
stat
us
.
One of the interlinked alarms should be
replaced (low battery)
Three short signals
e ery 40 sec. off Fault/ smoke chamber contamination
No signal flashes e ery 10 sec.
HUSH
mode (Alarm signal muting, sensiti ity
reduction)
Long intermittent
signal (Alarm) during
pushing the Test
button
flashes e ery 0.5 sec.
Test mode,
function test.
Smoke chamber and photo amplifier are
normal. All smoke alarms interlinked and
installed to the base shall go to Remote
Alarm status in 10..30 sec.
Three short signals
e ery 3 sec. during
pushing the Test
button
flashes e ery 3 sec.
Test mode,
function test.
Smoke chamber or photo amplifier are faulty
How to use the smoke alarm
Wireless interlinking of smoke alarms
The smoke alarm is a wireless de ice. To interlink a few smoke alarms the unique RF code
must be generated in one of them and set to the others interlinked alarms.
Follow the steps:
-remo e all smoke alarms from bases;
-
press and hold the test button for about 4 sec. on one of them (randomly chosen) and
release the button when the red LED will be lit. The red LED on the smoke alarm (first
one) will be lit until the interlink procedure is o er.
Note. This way the random RF code will be generated by the gi en smoke alarm within the range of
1..65535. This code will be recorded into non- olatile memory of the smoke alarm and will be actual till
the next procedure. The next procedure on the smoke alarm will generate a new RF code different from
the current one.
-in order to set the generated code to the other smoke alarms one by one push the Test
button on each of them. The successful setting of the code to the smoke alarm will be
accompanied with blinking of the red LED;
-exit the interlink procedure. Push the Test button on the smoke alarm where the red
LED is lit (the first alarm). The red LED will extinguish. The exit will be made
automatically after 2 min. or if the smoke alarm is installed to the base.
How to dislink a smoke alarm
If you need to dislink a smoke alarm carry out the unique RF code generation procedure for
the smoke alarm as described abo e.
How to add a smoke alarm

To add a new smoke alarm to the interlinked group carry out the Wireless interlinking of
smoke alarms for the new and all the other smoke alarms.
Verification of interlink between smoke alarms
Install all interlinked smoke alarms to bases. Press and hold on the Test button on one of
them (Test mode). After the period of 10 to 30 sec. all interlinked smoke alarms will go to the
Remote Alarm mode. Upon releasing the Test button, the other alarms will stay in the Remote
Alarm for 5..10 sec.
To use the alarm do the following
-interlink the smoke alarms
-fix the base where necessary
-install the detector to the base and twist it clock-wise until it clicks. You will hear the
tune.
To turn off the smoke alarm
-remo e the detector from the base, rotating it anti-clockwise as far as it goes.
Modes
Alarm
If smoke has been detected the smoke alarm gi es a loud and continuous alarm signal and
the red LED light will flash continuously until the smoke disappears. As soon as the smoke alarm
goes to the Alarm mode it will start transmitting alarm signals to all interlinked smoke alarms.
Within 20 sec. all interlinked smoke alarms will go to the Remote Alarm condition.
Remote Alarm
If one of interlinked alarms has gone to the Alarm status, then within 20 sec. all other
interlinked alarms will go to the Remote Alarm status. Only sound alarm indication is present in
the mode (no isual indication). Sound signal is retained within 5..10 more sec. after switching
off the Alarm status on the master alarm.
Hush mode (Reduced Sensiti ity)
Press the TEST/HUSH button for no longer than 2 sec.
The red LED light will now flash approx. e ery 10 seconds during approx. 10 min. This means
the smoke alarm is functioning properly and the smoke alarm will stay for approx. 10 minutes in
the HUSH mode.
NB. HUSH mode can be reset with Remote alarm
Test mode
Push and hold on the test button for at least 2 seconds.
If the sensor works properly then the smoke alarm will issue the alarm sound signal and then
the red LED will flash as long as the Test button is held on. In 10 sec. of holding the button the
alarm signal will be transmitted to all the interlinked smoke alarms and after that within 20 sec.
all the interlinked and installed to the base smoke alarms will go to the Remote Alarm status.

If the sensor is faulty then 3 short beeps will be emitted e ery 3 sec. and the red LED will blink.
Nuisance alarm
Push the [TEST/HUSH] to silence the alarm for approx. 10 min. (See HUSH mode)
Low battery
One beep signal e ery 40 seconds means the battery is almost empty. This signal is
transmitted to all interlinked alarms.
Remote low battery
The battery of an interlinked smoke alarm is low. The sound indication is present in the
mode - 2 short beeps e ery 4 h. After remo ing the detector with the low battery from the base
sound indication on the other alarms will stop.
Chamber fault
Three beep signals e ery 40 seconds mean a long term pollution of the smoke alarm as a result of
high dust concentration in the smoke chamber. In this case clean your smoke alarm of dust using a
acuum cleaner. To a oid false alarming during cleaning remo e the detector from the base.
Function test
When the smoke alarm is in the base press the Test button for at least 2-3 sec. If the de ice
operates properly the Alarm signal shall sound and the red LED shall flash e ery 0.5 sec.
Maintenance
The maintenance has to be carried out at least once a year as DIN14676 requires and should consist
of isual inspection, function test, and cleaning if necessary. The cleaning signal is 3 short beeps e ery 40
sec. (chamber fault mode).
To clean the smoke alarm apply a soft brush or a brush of your acuum cleaner to remo e dust and
spider web from side smoke entries.
Besides the maintenance described here you do not ha e to take any other actions to maintain the
de ice. Repairs should be carried out by the manufacturer if necessary.
All smoke detectors and especially optical de ices are sensiti e to ingress of dust and insects that
can cause false alarming. State-of-the-art ideas, materials and technological processes were used in
production of ASD-10QR to minimize influence of contamination. Howe er it's not possible to
completely eliminate influence of dust and insects. To ensure durable lifetime of your smoke alarms
you should make sure that the alarm is clean and there is no dust accumulation there. All insects or
spider web in the immediate proximity from the de ice must be remo ed right away.
In rare occasions under certain circumstances, e en when timely cleaning is pro ided, contamination
can be accumulated in the smoke chamber and cause the alarming. When it occurs the alarm should be
replaced. Contaminating substances are beyond the manufacturer's control as they are unpredictable
and are considered the natural deterioration.