Uni-P Dry Uni-P Pro 120X Operation manual

Uni-P Pro 120X Dehumdifier
Installation, Operation & Service Instructions
Add: 2048 E. Francis St Ontario CA 91761
Tel: 888-994-0895
E-mail: sales@unipdry.com
READ AND SAVE THESE INSTRUCTIONS

Tel: 888-994-0895 Tel: 888-994-0895
Uni-P Pro 120X Dehumidifier Installation, Operation & Service Instructions Installation, Operation & Service Instructions
How it Works
Installation Requirements
Installation
Key Functions
Indicator Lights
Remote Control
Operating Instructions
Unit Diagram
Maintenance
Important Notes
Warranty Registration
Specifications
Dehumdifier Storage
Ducted Applications
Troubleshooting
Spare Parts 14
Warranty Information 15
13
12
12
9
9
8
7
6
4
4
3
3
3
2
2
Uni-P Pro 120X Dehumidifier
Important Notes
Install dehumidifier according to all applicable local,state,and national codes.
The use of any other type of wiring will void your warranty.
Warranty Registration
Your dehumidifier comes with an extensive warranty. To register your unit simply fill
out and return the warranty form provided in your dehumidifier box.
For future refereirce, write down the model, serial number, and date of purchase for
your delmnidfier. This information is necessary for seeking assistance in the future and
can be found on the data label on the sde of the unit.
Model Number:
Serial Number:
Date of Number:
For additional questions concerning your dehumidifier, contact your local installer or
call Unipdry at Tel: 888-994-0895.
Always connect your dehumidifier using a grounded, dedicated electrical connection
that is GFCI protected with at least 15 amp capacity.
Be sure to follow your GFCI maintenance instructions.you will typically need to test
the operation of the trip circuit monthly.
For ease of testing and operation, it may be helpful to put the test switch and indicator
lights in a convenient location.
Your dehumidifier should only be repaired by a qualified technician.
Do not insert objects or your fingers into the inlet or discharge.
Do not use water to clean the exterior of the dehumidifier. To clean unit, unplug from
power, then use a damp cloth to wipe the exterior.
Do not stand on dehumidifier or place objects on it.
Unless otherwise noted, all maintenance should be done with the unit poweroff..
1

Tel: 888-994-0895 Tel: 888-994-0895
Installation, Operation & Service Instructions Installation, Operation & Service Instructions
Uni-P Pro 120X Dehumidifier Uni-P Pro 120X Dehumidifier
Capacity@80℉/60%RH:120PintsPerDay
Operating Relative Humidity Range: 36%-90%
Amperage Usage: 8.3 Amps
Sound Level: 60 dBa
Airflow @ 0.0” SP: 290CFM
COP: 2.8 L/kWh
Power Supply: 115V/60Hz/Single Phase
Dimensions LxWxH: 23.6” x 13.8 x 15.7”
Operating Temp. Range: 33-105°F
Refrigerant: R410A
Outlet Requirement: 15 Amp, 3 Prong
ETL Listed: Yes
Specifications
Howitworks
Installation Requirements
Unipdry dehumidifiers use an integrated humidistat to monitor the conditioned
space. When the relative humidity goes above the selected setpoint, the
dehumidifier will energize. Air is then drawn across an evaporator coil, which is
cooler than the dew point of air. This means moisture will condense out of the air.
The air is then reheated through the condenser coil and distributed back into the
room.
If the unit is installed in a crawl space, all vents should be sealed.
The area where the dehumidifier is located should be sealed with a vapor
barrier.
For the best air diffusion, install the unit so that a side panel faces the wall.
For proper ventilation, neither the inlet or discharge should be positioned
against a wall. The inlet needs a minimum of 12” clearance and the discharge
requires a minimum of 36” clearance.
Unipdry dehumidifiers are only intended for operation when the unit
is upright and level with the feet on the ground (unless using a Unipdry
Hanging Kit).
Installation
• Do not place unit directly on vapor barrier. For example, use blocks or pavers to create
a level surface.
• If unit has been turned or flipped so that the compressor did not remain upright, place
the unit on a level surface and wait a minimum of 2 hours before proceeding.
1. Place dehumidifier on a level surface.
•
• Slide the side of hose with compression nut over the insert on the compression fitting
completely.
• Tighten compression nut.
Remove the compression nut and slide it over the end of the hose to be attached to unit.
2. Set up the drain line
3. Plug dehumidifier into a dedicated 15 amp GFCI protected outlet.
Key Functions
•
• Press once to turn machine on. You will hear two beeps and the light will
illuminate green (solid or flashing depending on mode).
• Press the power button a second time and you will hear one beepas the machine
shuts down. Note that there is a 1 minute fan delay.
Use this button to turn the dehumidifier on and off.
1.PowerKey
• Use the up and down arrows to set the desired humidity setpoint on the display
screen.
• The setpoint can be any number between 36%-90%. When theindoor humidity is
higher than the setpoint, the unit will operate.
• Keep in mind that the displayed humidity levels are approximate( +/-5%)
2.Arrow Buttons
2 3

Tel: 888-994-0895 Tel: 888-994-0895
Installation, Operation & Service Instructions Installation, Operation & Service Instructions
Uni-P Pro 120X DehumidifierUni-P Pro 120X Dehumidifier
•
key to set the humidity below 36%.
• The continuous light will illuminate green and the display will show“CO”
• To switch back to normal humidistat operation, use the arrow keys to move the setpoint above
36%.
To set the unit to run continuously regardless of humidity, simply use the down arrow
.
3.Continuous Mode
• If you need to store or move your dehumidifier, press the “Drain” button to remove water
from the integral pump’s reservoir.
4.Manual Drain Button
• If the pump reservoir level gets too high, the water sensor will activate to prevent overflow.
• When this occurs, the compressor will stop automatically, and the display will show “E4”.
After a 1 minute delay, the fan motor will turn off and the dehumidifier will not operate until the
problem has been resolved.
• Check to verify that the pump is functioning, then unplug the unit for. two minutes to reset the
error code.
5. Pump Trouble Warning
• The A5/A6 on the terminal strip can be used as a safety switch for an external float switch.
• It should be set to N/O (normally open) at the accessory float switch.
• If an E4 error occurs immediately , switch the wiring to N/C (normally closed) on external switch.
You may need to unplug the unit to reset the error code.
6. Auxillary Terminals A5/A6
Indicator Lights
• The display screen has two functions:
1. Humidity Display Screen
1. When the unit is powered on, it shows the humidity of the space.
2. When setting the desired humidity level, the screen will show the set point. After a brief
delay, it will revert to current humidity of the space.
•
• Always make sure the unit is “off” prior to performing any service, unless otherwise
indicated.
• If the humidity is above the setpoint, the light will be solid green and the machine will
operate.
• If the humidity is below the setpoint, the unit will be in standby mode and the light will
be flashing.
This light indicates that the unit is properly powered on and ready to operate.
2. Power Indicator Light
• When the light illuminates green, it indicates that the dehumidifier is set to continuous
operation mode.
• When the light illuminates red, it means the unit is in auto defrost mode and clearing
the evaporator coils of any ice buildup.
3.Continuous Mode/ Auto Defrost Light
• When the light illuminates red, it indicates the compressor has been initiated but is
currently warming up.
• Once the light switches to green, it means the compressor is currently in working status.
4.Compressor Light
54

Tel: 888-994-0895 Tel: 888-994-0895
Installation, Operation & Service Instructions Installation, Operation & Service Instructions
Uni-P Pro 120X DehumidifierUni-P Pro 120X Dehumidifier
Remote Control Instructions
Unipdry Dehumidifiers can be controlled using an optional remote accessory. The remote
connects to your dehumidifier via a 25’ CAT 5 cable, with the integrated sensor giving you
multiple options for monitoring surrounding conditions.
Example #1- Install the dehumidifier in the laundry room and duct it into the living room.
Mount the remote in the living room and use the remote sensor.
Example #2- Install the dehumidifier in your crawl space with the remote mounted in
your garage.
NOTE: The symbols indicated below only
show when the remote is powered on.
1.On/Off (Power) Button
Press the on/off button and the machine
will start running. Press the button again
to turn the machine off.
2.Up Button/ Down Button
Use the up and down arrows to
adjust the humidity level.
3.Mode
Use the mode button to switch between dehumidifier and a ductedapplication.
• The symbol on the display indicates the sensor on the remote
control is being utilized.
• The symbol on the display indicates the sensor on the dehumidifier
is being utilized.
4. Temperature
The T button changes the temperature reading on your remote. Theremote comes from the
factory in Celsius. Press this button once toswitch to Fahrenheit.
5. Continuous
Press this button to switch the unit into continuous mode. “CONT.” willappear on the
display screen.
6. Drain Pump
Use this button if the unit will not be used for an extended period of time.This button will
remove water from the pump reservoir.
Remote Control Instructions
1.Start the machine
• Press the power key to turn the dehumidifier on.
2.Adjust the settings
• Use the up and down arrow keys to adjust your desired setpoint (typically 50-55%)
3.Stop the machine
• Press the power button again and the dehumidifier will stop. Note that the fan will continue to
operate for 1 minute after the unit has shut off. DO NOT DISCONNECT THE POWER CORD
TO FORCE THE UNIT TO STOP.
4. Water Drainage
• The Unip Pro 120X has an integrated condensate pump.During normal operation, the
Pro 120X will automatically drain as required.
• If you would like to store or move your unit, press the drain button to drain water from the
pump reservoir. The drain will operate for 15 seconds each time the button is pushed. It may
be necessary to push the button more than once.
67

Tel: 888-994-0895 Tel: 888-994-0895
Uni-P Pro 120X Dehumidifier Installation, Operation & Service Instructions Uni-P Pro 120X Dehumidifier Installation, Operation & Service Instructions
Unit Diagram
Maintenance
**For more detailed instructions, visit www.unipdry.com**
WARNING: Always unplug the unit before doing any maintenance.
Cleaning the Machine Body
• Use a soft, damp cloth to clean the exterior of unit. Do not use any
soap or solvents
Coil Maintenance
Once per year, clean the coils with an approved coil cleaner. Thecoil cleaner should be a self-rinsing,
foaming, cleaner, such asWEB® Coil Cleaner.
Handle
Side Panel
Filter Cover
Control Panel
Pre-Filter
Discharge Grille
Power Cord
Auxiliary Terminals
Drain Hose
Connection
Cleaning the Filter
1. Unplug the unit.
2. For PreFilter:
Pump Maintenance
Your Unip Pro 120X is equipped with an integral condensate pump designed to pump
water from the dehumidifier out to the desired drain. The pump requires routine maintenance
that is not covered by the warranty.
a. Remove prefilter from inlet of machine.
b. Vacuum or wash with warm water (no soap).
3. For MERV-10/HEPA/Carbon Filters:
a. Replace as necessary- we recommend checking the filters
at least 1x/year
Electrical Access
•
• Remove the screw on the
control board cover.
Unscrew the 13 screws on the side panel.
Preventative maintenance is necessary to prevent issues from dirt andslime that may
accumulate in the drain system. This includes the drainpan, hose to the condensate pump,
pump reservoir, pump head assembly,and discharge tubing
Removing the Pump
1. Remove the 13 screws on the side panel and set panel aside.
2. Remove the screw holding the pump in place.
3. Undo the 3 pump electrical quick connects and 1drain quick connect
4. Insert a flat head screwdriver into the notch
on the side of the pump. This will allow you to
gently lift the pump off its reservoir (the reservoir
remains attached to the unit)..
89

Tel: 888-994-0895 Tel: 888-994-0895
Uni-P Pro 120X Dehumidifier Installation, Operation & Service Instructions Uni-P Pro 120X Dehumidifier Installation, Operation & Service Instructions
Basic Pump Cleaning
Complete about once per year, depending on environment
1. Remove filter(s) from inlet of unit. Remove screws (2/side) on filter door
to access drain tray. Press the drain button to drain the reservoir.
2. Disconnect power to the dehumidifier.
3. Mix a 16 ounce solution of bleach (1 oz bleach + 15 oz water) OR
vinegar (4 oz white vinegar + 12 oz water).
4. Pour the cleaning solution into the drain tray at the base of the coils.
If any cleaning solution gets on the coils, flush with water.
5. Allow solution to soak for 15 minutes.
6. Reconnect the dehumidifier to power.
7. Fill the reservoir with water (16-32 ounces) and flush/cycle
the pump at least 2x.
8. If the drain line is still filled with debris, repeat process. If drain line
still does not appear clean, move on to Advanced Cleaning.
Advanced Pump Cleaning
Complete as needed
1. Press the drain button to drain the water from the reservoir (a wet-dry
vacuum or towels can be used to remove any remaining water).
2. Unplug the dehumidifier and remove the cover so you have access
to the pump.
3. Remove the pump head from the reservoir by unscrewing the screw.
Wipe reservoir clean with a paper towel.
4. Reassemble pump.
5. Mix a 16 ounce solution of bleach (1 oz bleach + 15 oz water) OR
vinegar (4 oz white vinegar + 12 oz water).
6. Pour the cleaning solution into the drain tray at the base of the coils.
If any cleaning solution gets on the coils, flush with water.
7. Allow solution to soak for 15 minutes.
8. Reconnect the dehumidifier to power.
9. Fill the reservoir with water (16-32 ounces) and flush/cycle the pump
at least 2x.
Dehumidifier Storage
If the unit will be stored for an extended period of time, complete the
following steps:
1. Turn off the unit and allow it to dry.
2. Complete steps 1-3 in Advanced Pump Cleaning to clean out the
pump reservoir.
3. Wrap and secure the power cord.
4. Cover the filter mesh.
5. Store in a clean, dry space.
Ducted Applications
Ducting the dehumidifier allows the unit to be in one room while
conditioning an adjacent room. Both the inlet/return grille and the supply
grille are designed for 10” flex ducting
Ducting Installation Notes
• Be sure to secure the ducting with tie wrap.
• Maximum total length of duct run = 10’
• Inlet and outlet duct adapters are optional accessories
Duct Adapter Installatio
• Screw in the 4 screws on each duct
adapter.
Flex Duct Installation
• Slide ducting over adapter
and secure with tie wrap or
clamps
10 11

Tel: 888-994-0895 Tel: 888-994-0895
Uni-P Pro 120X Dehumidifier Installation, Operation & Service Instructions Uni-P Pro 120X Dehumidifier Installation, Operation & Service Instructions
Troubleshooting
Display is Blank
No Airflow
Error Code:E1
Error Code:E4
Error Code:LO
Error Code:HI
Tripped GFCI
Outlet or Breaker
Cause Solution
Poor Connection
Power Outage
Filter is dirty
Air Inlet or Outlet
is Blocked
Humidity Sensor or
Communication Error
Problem with Pump
Room Temperature
is below 33℉
Room Temperature
is above 105℉
Not a Dedicated Circuit
Defective GFCI Outlet
Dirt, Dust, or
Moisture on Outlet
Lightning or Externa
Electrical Surge
Possible Dehumidifier
Issue
Verify that both ends of the
cord are plugged in
Reset power
Clean the Filter
Clean the blockage
Check to ensure that the sensor wire
is connected at both ends. if no issues
are visible, the sensor may be faulty.
Verify that the pump is properly
installed and functioning. If so, unplug
the unit for two minutes,then restart.
Increase the room temperature so it is
within operating range (above 33℉). If
error still displays, check sensor.
Decrease the room temperature so it is
within operating range (below 105℉).
If error stille displays, check the
sensor
Identify all sources connected to outlet
and confirm source of trip.If it is
dehumidifier, contact technical
support. If not, move dehumidifier to
dedicated circuit for future use.
Replace Outlet
Clean or Replace Outlet as necessary
Reset or Replace Breaker/GFCI, as
necessary
If none of above options work, contact
technical support
Symptom
Pump Alarm- E4 Error Code
**UNIT WILL NOT FUNCTION UNTIL ERROR CODE IS CLEARED.
If E4 (pump alarm) is shown on the display, complete the following steps:
1. Reset the unit by unplugging the power cord and then reconnecting it.
2. Manually check to see if the pump is operational by pressing the drain button. Check
if the pump energizes and de-energizes properly. Additionally, check to see if any water
purged from the system.
3. If you haven’t cleaned the system recently, check the discharge line for an obstruction,
then clean as described in the Maintenance section.
4. Replace the hose and/or pump, if maintenance alone isn’t sufficient.
Spare Parts
Fan Components
Filter + External Components
Cables
Duct + Ventilation Accessories
N-100
N-101
N-102
N-1209
N-1206
N-1208
N-1207
Main Control Board
Display Board
RH/Temp. Sensor
Fan Motor
Complete Fan Assembly
Fan Capacitor
N-1210
N-1211
N-1205
N-1200
N-1201
N-1202
N-1203
N-125
Prefilter
MERV 8
HEPA
Carbon Filter
Foot adjustable
Display/Control
Inernal Components
N-120
N-121
N-122
Temp/RH Sensor Cable
Display Ribbon Cable
CaТ: 5 Port Internal Cable
N-1204 Supply Duict Collar
Assembly
Compressor
Compressor Capacitor
Coil Assembly
Condensate Pump
Assembly
12 13

Tel: 888-994-0895 Tel: 888-994-0895
Uni-P Pro 120X Dehumidifier Installation, Operation & Service Instructions Uni-P Pro 120X Dehumidifier Installation, Operation & Service Instructions
5 Years (From Date of Purchase):
Unipdry warrants the dehumidifier will operate free of defects in workmanship and
materials.At its discretion, Unipdry will repair or replace any malfunctioning components,
free of charge excluding transportation costs)
Customer Responsibilities:
In order to take advantage of the warranty service, the customer must do the following:
1. Customer must mail in warranty registration card to Unipdry. If no card is submitted, warranty
period will begin the day the shipment left the warehouse. Please be sure to record serial # and date
of installation in the spaces provided on page 2 of the manual. You will need this information to receive
an RA number.
2. If warranty service is necessary, customer must contact Unipdry Tech Support by phone
880-994-0895 to receive a Return Authorization (RA number).
3. Once an RA has been issued, it is the customer’s job to bring the unit to a certified repair center.
If this is not an option, shipping will be arranged to bring the unit back to the Unipdry warehouse (at
the expense of the customer).
4. After the unit has been received by Unipdry (whether at a repair center or the warehouse), an initial
inspection will be completed, if it is determined to be an invalid warranty claim (see exclusions below),
unit will only be completed after receiving payment from customer for all associated costs.
5. If unit is defective, the necessary parts will be repaired or replaced and the unit will be available
for pickup at certified repair center or returned via freight shipment (at customer’s expense). Keep in
mind that work is only done during normal working hours. After being repaired, all units are required to
go through a rigorous testing process prior to being returned to customer.
6. Once a part is repaired and the dehumidifier is returned, the original warranty period still applies
(no extensions)
Warranty Procedure:
Limited Warranty
Unipdry's
Unipdry
Unipdry
Warranty Exclusions
15
14
Table of contents