7
Unovent®plug and check that the fan runs. (If the fan
does not run, a cable connection has been incorrectly
done –each connection must consistently be red or white
marked cables to red marked sockets.)
16. If the fan runs on the
Unovent®room outlet, it is
now ready to be put in place
with its spring loaded clamps.
Put the clamps in the position
as shown in the photo to the
right, place edge of the
bottom part of the four clamps against the edge of the
hole by equal amounts (about 5mm overlap each also
ensuring that the plug+socket assembly is upper most to
ensure that inlet tube is pointing slightly downwards to
assist water drainage) then in one quick movement of the
whole room outlet, while maintaining a square-on
alignment, push the Unovent®room outlet into the wall.
This will cause the clamps to flip over and pull the
surround edge up against the face of the wall lining. After
about 3 days, the voltage setting can be set at 9 volts or
7.5 volts to reduce air flow but reset to a higher voltage if
the air flow proves insufficient for the reduction of
condensation on windows in the winter.
17. After final positioning of the Unovent®room outlet and
certainty that it is all working correctly, take steps to
waterproof and fill the spaces around the outer part of the
Unovent®room outlet and the external house cladding to
fully ensure that there will be no water ingress into the
external wall structure. The external cowl can then be
fixed to the inlet tube section of the Unovent®room outlet