Upsen Queen Star Series User manual

USER MANUAL
Queen Star Series Online UPS 6K-20KVA

1
Contents
1. Brief introduction.......................................................................1-6
1.1 System and model description.............................................................1
1.2 Description of commonly used symbols.............................................2
1.3 Appearance.......................................................................................2-5
1.4 Product specification and performance............................................5-6
2. Safety Instruction..........................................................................7
3. Installation................................................................................8-14
3.1 Unpacking and inspection...................................................................8
3.2 Input and output power wiring and protective earth ground
installation....................................................................................8-10
3.3 Operating procedure for connecting the long backup time model UPS
with the external battery.............................................................10-11
3.4 Parallel operation.........................................................................11-14
4. Operation and Operating mode............................................15-22
4.1 Operation......................................................................................15-16
4.2 Operating mode............................................................................16-22
5. Battery maintenance...................................................................23
6. Notes for battery disposal and battery replacement................24
7. Troubleshooting.....................................................................25-26
Appendix 1 Description of Display panel.................................27-28
Appendix2 Indicator and alarm...............................................29-30
8. Chapter Operation (LCD model) ........................................31-42
8.1 Operation Display Panel....................................................................31
8.2 Operation Mode...........................................................................32-36
8.3 Operating Instructions..................................................................36-38
8.4 Checking UPS function.....................................................................38
8.5 Setting the output voltage and frequency.....................................38-39
8.6 Troubleshooting...........................................................................39-42

2
1.Briefintroduction
1.1 System and model description
The On-Line-Series is an uninterruptible power supply incorporating
double-converter technology. It provides perfect protection specifically for
strict load. The double-converter principle eliminates all mains power
disturbances. A rectifier converts the alternating current from the socket
outlet to direct current. This direct current charges the batteries and powers
the inverter. In the event of power failure, the maintenance-free batteries
power the inverter. Thus the inverter generates a sine wave AC power,
which permanently supplies the loads.
Designed with the proven on-line, double conversion architecture, this
series of UPS offers the greatest degree of availability in power protection
and provides continuous high-quality AC power to connect strict load,
especially for the basic equipments in some areas as: finance,
communication, government, traffic, manufacture, education and so on.
This manual is applicable to the following models:
Type Model Input Battery
Standard 6KVA 6K Single phase + N Inbuilt
10KVA 10K Single phase + N Inbuilt
Long back
up time
6KVAL 6KL Single phase + N External battery bank
10KVAL
10KL Single phase + N External battery bank
10KVAL
31 10KL
Three-phase + N + PE
External battery bank
12KVAL
31 12KL
Three-phase + N + PE
External battery bank
15KVAL
31 15KL
Three-phase + N + PE
External battery bank
20KVAL
31 20KL
Three-phase + N + PE
External battery bank

3
1.Briefintroduction
1.2 Description of commonly used symbols
The following symbols will be used in this manual and may appear during
the course of your practical applications. Therefore, all users should be
familiar with them and understand their meanings.
1.3 Appearance
Notation and Explanation
Notation
Explanation Notation
Explanation
Alert you to pay special
attention Protective ground
Caution of high voltage
Alarm silence
Turn on the UPS
Overload indication
Turn off the UPS
Battery check
Idle or shut down the UPS
Recyclable
Alternating current source (AC)
Do not dispose w
ith
ordinary trash
Direct current source (DC)
Battery

4
BACK VIEW OF 6K
1.Briefintroduction
BACK VIEW OF 6KL
BACK VIEW OF 10K

5
1.Briefintroduction
BACK VIEW OF 10KL
BACK VIEW OF 31 10KL

6
1.Briefintroduction
BACK VIEW OF 31 12KL/31 15KL/31 20KL
1.4 Product specification and performance
●General specification
Power Rating
Model
Frequency
(Hz)
Input Output Dimensions
(L*W*H)mm
Weight
(kg)
Voltage (VAC)
Current
Voltage
Current
6KVA/4.8KW
6K 50
(120-274)
32Amax
220VAC
27A
560x260x717
61.5
6KVA/4.8KW
6KL 50
(120-274)
32Amax
220VAC
27A
533x260x501
21
10KVA/8KW
10K 50
(120-274) 50Amax
220VAC
45A
560x260x717
67.5
10KVA/8KW
10KL
50
(120-274) 50Amax
220VAC
45A
533x260x501
23
10KVA/8KW
31 10KL
50
(120-274) 50Amax
220VAC
45A
533x260x501
24
12KVA/9.6KW
31 12KL
50
(120-274) 80Amax
220VAC
54A
560x260x717
39.5
15KVA/12KW
31 15KL
50
(120-274) 80Amax
220VAC
68A
560x260x717
39.5
20KVA/16KW
31 20KL
50
(120-274) 100Amax
220VAC
91A
560x260x717
39.5
Note: Output voltage can be set: 200V/208V/220V/230V/240V.
Frequency can be set as 60Hz.

7
1.Briefintroduction
●Electrical performance
Input
Model Voltage Frequency
Power Factor
6K(L)/10K(L) Single-phase(220VAC/230VAC)
50/60Hz >0.99(Full load)
31 10KL/31 12KL/
31 15KL/31 20KL
Three-phase (380VAC/220VAC、
380VAC/230VAC) 50/60Hz >0.95(Full load)
Output
Voltage
regulation
Power
factor
Frequency Distortion
Overload capacity
Current
crest ratio
±1% 0.8 lag
Line mode:
(1)、Synchronized 46
~ 54Hz;
(2)、50Hz (Line 40~
46 and 54~ 60Hz)
Battery mode: 50Hz
THD<2%
Full load
(Linear
load)
105%-125%load
transfers to bypass
mode after 1 minutes;
125-135% load
transfers to bypass
mode after 30second
3:1
maximum
●Operating environment
Temperature Humidity Altitude Storage temperature
0℃-40℃<95% <1000m 0℃-40℃
Note: If the UPS is installed or used in a place where the altitude is above
than 1000m, the output power must be decrease in use, please refer to
the following:
Altitude(M) 1000
1500
2000
2500
3000
3500
4000
4500
5000
Load 100%
95%
91%
86%
82%
78%
74%
70%
67%

8
2.SafetyInstruction
●Even if the interruptible Power System (UPS) is not connected to utility
power, the output socket of the UPS may still present 220V/230V output
voltage.
●If it is necessary to replace the external battery cord or power cord, please
purchase the original material from the service center or distributor of
our company so as to avoid overheat or spark resulting in fire due to
insufficient capacity.
●Do not let battery or batteries get close to any heating source and do not
incinerate battery or batteries, they may explode.
●Do not open or mutilate the battery or batteries, released electrolyte is
highly poisonous and harmful to the skin and eyes.
●Do not short the positive and negative of battery electrode. Otherwise, it
may cause electric shock or fire.
●To avoid the risk of being shocked, please do not attempt to open the
case of the UPS.
●A battery can present a risk of electric shock and high short circuit
current.
●Do not plug household appliance such as hair dryers to UPS.

9
3.Installation
3.1 Unpacking and inspection
1) Unpack the packaging and check the package contents. The shipping
package contains:
●A UPS
●A user manual
●A communication cable
2) Inspect the appearance of the UPS to see if there is any damage during
transportation. Do not turn on the unit and notify the carrier and dealer
immediately if there is any damage or lacking of some parts.
3.2 Input and output power wiring and protective earth ground
installation
3.2.1 Notes for installation
1) The UPS must be installed in a location with good ventilation, far away
from water, inflammable gas and corrosive agents.
2) The UPS should not be tilted. The air inlet port at the lower part of the
front panel and the fan outlet port on the rear panel should not be
blocked so as to ensure good ventilation (Allow at least 0.5m of space on
each side).
3) In case if the UPS is unpacked, installed and used at very low
temperatures, condensation of water drops may appear. It is necessary
to wait until the UPS is fully dried inside out before proceeding to
installation and use. Otherwise, there may be a risk of electric shock.
3.2.2 Installation
Installation and wiring must be performed in accordance with the local
electric code and the following instructions by professional personnel. For
safety, please cut off the mains power breaker before installation. The
battery breaker also needs to be cut off if it is a long backup time model.
1) Open the terminal block cover located on the rear panel of the UPS
(please refer to the appearance diagram).
2) For 6K(L) UPS, it is recommended to select the UL1015 10AWG (6mm 2)
wire or other insulated wire which complies with AWG Standard for
the UPS input and output wirings.

10
3.Installation
3) For 10K(L)/31 10KL UPS, it is recommended to select the UL1015
8AWG (10 mm2) wire or other insulated wire which complies with
AWG Standard for the UPS input and output wirings.
4) For 31 12KL/31 15KL/31 20KL UPS, it is recommended to select the
UL1015 6AWG (25mm2) wire or other insulated wire which complies
with AWG Standard for the UPS input and output wirings.
Note: Do not use the wall receptacle as the input power source for the
UPS, as its rated current is less than the UPS’s maximum input
current. Otherwise the receptacle may be burned and destroyed.
(Please refer to section 1.4)
5) Connect the input and output wires to the corresponding input and output
terminals according to the following diagram.
Note: You must make sure that the input and output wires and the input and
output terminals are connected tightly.
6) The protective earth ground wire refers to the wire connection between
the equipment which consumes electro-equipment and the ground wire.
The wire diameter of protective earth ground wire should be at least as
above mentioned for each model and green wire or green wire with
yellow ribbon wire is used.
7) After having completed the installation, make sure the wiring is correct.
8) Please install the leak current protective breaker at the output power
distribution panel of the UPS if necessary.
9) To connect the load with the UPS, please turn off all the loads first, then
perform the connection and finally turn on the loads one by one.
10) No matter the UPS is connected to the utility power or not, the output
of the UPS may have electricity. The parts inside the unit may still have
hazardous voltage after turning off the UPS. To make the UPS have no
output, power off the UPS, and then disconnect the utility power
supply.
11) Suggest charging the batteries for 8 hours before use. After connection,
turn the input breaker in the “ON” position, the UPS will charge the
batteries automatically. You can also use the UPS immediately without
charging the batteries first, but the backup time may be less than the
standard value.

11
3.Installation
12) If it is necessary to connect the inductance load such as a monitor or a
laser printer to the UPS, the start-up power should be used for
calculating the capacity of the UPS, as its start-up power consumption
is too big when it is started.
Input and Output Terminal Block wiring diagram of 6K(L)/10K(L)
Input and Output Terminal Block wiring diagram of
31 10KL/31 12KL/31 15KL/31 20KL
3.3 Operating procedure for connecting the long backup time
model UPS with the external battery
3.3.1 The nominal DC voltage of external battery pack is 192VDC. Each
battery pack consists of 16 pieces of 12V “maintenance-free” batteries in
series. To achieve longer backup time, it is possible to connect
multi-battery packs, but the principle of “same voltage, same type” should
be strictly followed.
3.3.2 For 6KL/10KL/31 10KL/31 12KL/31 15KL/31 20KL, the procedure
of installing battery bank should be complied with strictly. Otherwise you
may encounter the hazardous of electric shock.

12
3.Installation
1) A DC breaker must be connected between the battery pack and the
UPS. The capacity of breaker must be not less than the data specified
in the general specification as follow.
Model
6K 6KL 10K 10KL
31 10KL
31 12KL
31 15KL
31 20KL
Battery
voltage
192VDC
192VDC
192VDC
192VDC
192VDC
192VDC
192VDC
192VDC
Battery
current
34A max.
34A max.
56A max.
56A max.
56A max.
62A max.
78A max.
104A max.
Note: 240VDC battery voltage can be choose for 6K(L)/10K(L).
2) Set the battery pack breaker in “OFF” position and connect the 16
pieces of batteries in series.
3.3.3 To complete the connection by plugging the connector of the external
battery cable into the external battery socket of the UPS. Do not attempt to
connect any loads to the UPS now. You should connect the input power
wire to the right position first. And then set the breaker of the battery pack
in the “ON” position. After that set the input breaker in the “ON” position.
The UPS begins to charge the battery packs at the time.
3.4 Parallel operation
3.4.1 Brief introduction of the redundancy
N+X is currently the most reliable power supply structure. N represents the
minimum UPS number that the total load needs; X represents the redundant
UPS number, i.e. the fault UPS number that the system can handle
simultaneously. The bigger the X is, the higher reliability of the power
system is. For occasions where reliability is highly required, N+X is the
optimal mode. As long as the UPS is equipped with parallel cables, up to 3
of them can be connected in parallel to realize output power sharing and
power redundancy.
3.4.2 Parallel installation
1) Users need to opt a standard 25-pin communication cable, which should
have 25 cores, corresponding stitches and shield, as the UPS parallel
cable. The length of the parallel cable is appropriate to be less than 3 m.
2) Strictly follow the stand-alone wiring requirement to perform the input
wiring of each UPS.

13
3.Installation
3) Connect the output wires of each UPS to an output breaker panel first,
and then connect the wiring to the load via the breaker panel.
4) The parallel UPS must be equipped with battery individually.
5) Please refer the figure followed to see the wiring of parallel operation.
The capacity of the breaker must be not less than the specification as
follow.
Model No.
Capa
city of breaker
6K(L)
≥40A/250VAC
10K(L)/3
1
10KL
≥60A/250VAC
3
1
1
2
KL
/
3
1
15KL/3
1
20KL
≥100A/250VAC
*The requirement of the output wiring is as follows:
●When the distance between the UPSs in parallel and the breaker panel is
less than 20 meters, the difference between the wires of input & output
of the UPSs is required to be less than 20%;
●When the distance between the UPSs in parallel and the breaker panel is
greater than 20 meters, the difference between the wires of input &
output of the UPSs is required to be less than 10%.
3.4.3 Operation and maintenance
1) To perform the general operation, follow the stand-alone operating
requirement.
2) Start up: The units transfer to INV mode simultaneously as they start up
sequentially in utility power mode.
Shutdown: the units shut down sequentially in INV mode. When the last
one completes the shutdown action, each unit will shut down the inverter
simultaneously and transfer to bypass mode.
3) To perform the maintenance, follow the stand-alone requirement.

14
3.Installation

15
3.Installation

16
4. OperationandOperatingmode
It is easy to operate the equipment, with no previous training. You just need
to read through this manual and operate according to the instructions in it.
The meaning of the LED indicators, please refer to the appendix 1 “Display
panel”.
4.1 Operation
4.1.1 Turn on the UPS with utility power supplied
1) After you make sure that the power supply connection is correct, set the
input breaker in the “ON” position first. At this time the fan rotates and
the UPS supplies power to the load via the bypass. The UPS operates in
Bypass mode.
2) To power on the UPS by simply pressing the “ON” button continuously
for more than 1 second.
3) When being powered on, the UPS will perform self-diagnosis, with the
load/battery level LEDs turned on and then off one after another in
ascending order. A few seconds later, the INV LED is turned on, the
UPS is already running in Utility Power mode. If the utility power is
abnormal, the UPS will operate in battery mode without output
interruption of the UPS.
4.1.2 Turn on the UPS with no utility power supplied
1) Press the “ON” button continuously for more than 1 second to power on
the UPS. For long back up time model (“L” model), please make sure
that the battery breaker is in “ON” position.
2) During the course of starting up, the UPS has the same action as if it is
connected to utility power except that the utility power LED is not turned
on and the battery LED is turned on instead.
4.1.3 Turn off the UPS with utility power supplied
1) Press the “OFF” button continuously for more than 1 second to turn off
the inverter of the UPS immediately.
2) When being powered off, the UPS will perform self-diagnosis, the
Load/Battery level LEDs will be turned on and then off one after another
in ascending order, then the INV LED will be turned off and Bypass

17
4. OperationandOperatingmode
LED will be turned on. The UPS is working in Bypass mode.
3) Upon completion of the above to turn it off, output of electric current of
the UPS is still present. In order to cut off the output from the UPS,
simply cut off the utility power supply and the UPS will perform
self-diagnosis, finally not any display is shown on the display panel and
no voltage output is available from the UPS output.
4.1.4 Turn off the UPS with no utility power supplied
1) Press the “OFF” button continuously for more than 1 second to power
off the UPS.
2) When being powered off, the UPS will perform self-diagnosis, the
Load/Battery level LEDs will be turned on and then off one after
another in ascending order. Finally not any display is shown on the
display panel and no voltage is available from the UPS output.
Suggestions:
Please turn off the connected loads before turning on the UPS and turn on
the loads one by one after the UPS is working in INV mode. Turn off all of
the connected loads before turning off the UPS.
4.2 Operating mode
4.2.1 Normal power mode
In the normal mode, the display on the front panel is shown in the
following diagram. The utility power indicator and the Inverter indicator
are turn on.
The load/battery capacity indicator will be turned on in accordance with the
load capacity connected.
1. If the utility power indicator blinks, it indicates that there are problems
with reversed polarity (L, N) of site wiring or disconnect with ground
that may result in shock hazard. UPS is still working in normal mode. If
the battery indicator is turn on at the same time, it shows that the voltage
or frequency of the utility power is out of the normal input range of the
UPS. The UPS works in battery mode.

18
4. OperationandOperatingmode
Figure 4-1 Normal Mode
2. If output overloaded, the load level indicators will be turned on and
alarm will beep every second. You should get rid of some unnecessary
loads one by one to decrease the loads connected to the UPS less than
95% capacity of the UPS.
3. If the battery indicator blinks, it indicates that no battery is connected to
the UPS or battery voltage is too low. You should check if battery is
properly connected to the UPS, and press function button more than 5
seconds to start the battery self-diagnosis. If the connection between
battery and UPS is confirmed without any problem, it may be due to the
defect or aging of the battery, please refer to the “troubleshooting” in
chapter 7 to solve the problem accordingly.
Note:Connection to the power generator should be made according to the
following steps:
Activate the power generator and wait until the operation is stable
before connecting the output of the power generator to the UPS (be
sure that the UPS is in idle mode). Then, turn on the UPS according to
the startup procedure. After the UPS is turned on, the loads are
connected one by one.
It recommended that the capacity of the AC generator chosen should
double that of the UPS.
4.2.2 Battery mode
In battery mode the display on the front panel is shown in the following
diagram. The battery indicator and the inverter indicator are turn on. If the

19
4. OperationandOperatingmode
utility power indicator blinks at the same time, it shows that the utility
power is abnormal. The load/battery capacity indicators will be turn on in
accordance with the battery capacity. Please note that the load/battery
capacity indicator in normal mode will indicate the battery capacity in
battery mode.
1. When the UPS is running in battery mode, the alarm will beep every 4
seconds. If the “Function” key is pressed for more than 5 seconds, the
alarm will not beep (silence function). Press the “Function” key more
than 5 seconds again to resume the alarm function.
Figure 4-2 Battery Mode
2. When the battery capacity decreases, the number of load/battery capacity
indicators turned on will decrease. If the battery voltage drops to the
pre-alarm level (capable of maintaining the backup time for more than 2
minutes), the alarm will beep every second to remind the user of
insufficient battery capacity.
4.2.3 Bypass mode
When operating in bypass mode set up through UPSilon software, the
display on the front panel is show in the following diagram. The utility
power indicator and the bypass indicator are turn on. The load/battery
capacity indicator will be turned on in accordance with the load capacity
connected.
1. If the utility power indicator blinks, it shows that the voltage or
frequency of the utility power is out of the input range of the UPS or
there are problems with reversed polarity (L/N) of site wiring or
Other manuals for Queen Star Series
1
This manual suits for next models
4
Table of contents
Other Upsen UPS manuals
Popular UPS manuals by other brands

CyberPower
CyberPower LE850G user manual

SurgeX
SurgeX SX-DS-154 DEFENDER SERIES MULTIPAK quick start guide

Sola HD
Sola HD S3K Series instruction manual

Vertiv
Vertiv LIEBERT PSA itON-SOHO user manual

Toshiba
Toshiba 1600XP SERIES Quick installation guide

Jansen Medicars
Jansen Medicars Mobile Power System user manual