Upsen ES33 Series User manual

3Phase HF UPS 10-120kva USER Manual
Page1
User Manual
ES33 Series Online HF UPS10-120kva
(380/400/415Vac)

3Phase HF UPS 10-120kva USER Manual
Page2
Contents
Section I: PW series Product System Overview ................................................................................. 3
1.1 Introduction ........................................................................................................................... 3
1.2 PW Series product features .................................................................................................. 4
1.2.1 Product specific parameters ........................................................................................ 4
Section II Installation of Single Machine System ............................................................................... 7
2.1 Introduction ........................................................................................................................... 7
2.2 Inspecting and Unpacking the UPS Cabinet ....................................................................... 7
2.3 Storage .................................................................................................................................... 8
2.4 Link (Connection) ................................................................................................................. 8
2.4.1 Incoming mode ............................................................................................................. 9
2.4.2 Power cable ................................................................................................................... 9
2.5 Control cable and communication ..................................................................................... 10
2.5.1 Features of the monitoring panel .............................................................................. 10
2.5.1Input interface of emergency power off .................................................................... 10
2.5.3 Temperature detection interface of the external battery ........................................ 11
2.5.4 Serial port RS232 ....................................................................................................... 12
2.5.5 SNMP card interface .................................................................................................. 12
Section III: Installation of Battery..................................................................................................... 13
3.1 Introduction ......................................................................................................................... 13
3.2 Safety .................................................................................................................................... 13
3.3 Battery cabinet .................................................................................................................... 14
3.3.1 Introduction ............................................................................................................. 14
3.3.2 Environmental temperature ................................................................................... 14
3.3.3 Temperature pickup of battery .............................................................................. 15
3.3.4 Cable incoming ......................................................................................................... 15
3.3.5 Structural map of battery configuration ................................................................ 15
Note: Please pay high attention to the battery connection ,regarding the Negative Pole”-“ ,
the Positive Pole”+” and the Neutral”N”,. ............................................................................ 15
(1) Standard model with internal battery. .................................................................. 15
Please refer the below sketch Diagram 17-1 ...................................................................... 15
3.4 Power cable of battery .......................................................................................................... 16
3.4.1 Installation of battery ................................................................................................ 16
3.4.2 Battery connection .................................................................................................. 17
Section IV Installation of Parallel System ......................................................................................... 17
4.1UPS single machine of parallel system ................................................................................ 17
4.2 Hot backup system ................................................................................................................ 19
Section V: Installation Diagram ......................................................................................................... 21
5.1 External structure ................................................................................................................. 21
5.2 Internal view ........................................................................................................................ 21
Section VI: Operation Procedure ...................................................................................................... 23
Section VII: Operational & Controlling Display Panel ................................................................... 25
7.1Introduction ........................................................................................................................... 25
7.1.1 LCD and menu key ................................................................................................. 27
7.1.2 Parameter Setting .................................................................................................... 28

3Phase HF UPS 10-120kva USER Manual
Page3
Section I: PW series Product System Overview
1.1 Introduction
PW is a high-performance and fully digital UPS utilizing the double DSP control
technology with the power factor correction function. Its performance indexes reach the
leading level of the industry and the power grade contains 15-80 KVA. PW UPS is
connected between the commercial power and the important load to supply the
high-quality power to the load. It adopts the high-frequency double conversion pulse
width modulation(PWM) and fully digital control technology, the output voltage is not
influenced by the change and interference of the input voltage and frequency of the
utility.
As shown in diagram 1, the utility is inputted from CB1, the rectifier converts the
utility to DC .The PFC converts the low DC to high DC ( DC busbar ) and supplies
power to the DC/DC battery charger (charge the battery at any time) and the inverter. The
inverter converts the DC power to AC power to supply the load. When the utility is
interrupted, the battery supplies the back-up power to the load through the battery switch,
PFC and inverter. When inverter is fault or overload time is finished, the external bypass
supplies power to the load through the input switch CB2 and static bypass. In addition,
for the maintenance and repair of the UPS, UPS will supply the power to the load through
the internal maintenance bypass. When the UPS is in normal mode, all switches are
closed except the maintenance bypass switch.

3Phase HF UPS 10-120kva USER Manual
Page4
Diagram 1, frame of the single machine system
1.2 PW Series product features
1.2.1 Product specific parameters
Figure 1: Performance parameters
Capacity
10,15,2
0
,3
0,
4
0
,5
0
,6
0,
8
0
,100,120
kVA
Main input
I
nput voltage
380
V/
40
0
/415
V
(
line voltage
)
Input mode
T
hree
-
phase
five
-
wire
Power factor
>0.99
Total Harmonic Distortion,
Harmonic current
<3%
V
oltage range
(
line voltage
)
–20%~+25%
Frequency range
40~
70HZ
Bypass
input
I
nput voltage
380
V/
40
0
/415
V
(
line voltage
)
I
nput voltage
range
–15%~+25%( settable)

3Phase HF UPS 10-120kva USER Manual
Page5
Input mode
Three
-
phase
five
-
wire
Frequency range
40~70HZ
(can be set)
Output
Steady
s
tate
v
oltage precision
(balanced load)
±0.5%
D
ynamic voltage transient
±2%(0~100% load variation)
V
oltage distortion
THDU
(linear load)
THD<0.5%
(
phase voltage
)
V
oltage distortion
THDU
(non-linear load)
THD<3%
(
phase voltage
)
Power factor
0.9 (lagging)
Frequency
t
racking
range
50
/60
Hz±3Hz
Frequency precision
(
battery
inversion)
±0.01%
T
hree
-
phase separation
120±0.5°
F
requency tracking rate
A
djustable
be
tween
0.5Hz/s
and
5Hz/s
Inverter
overload capacity
105%<load<125% load, convert to bypass
output after 10min
125%< load, convert to bypass output
after 10S
>150% load, convert to bypass output
after 200ms
Load between 105%~150%, close the
inverter according to the overload curve
Bypass overload
capacity
1
25
%
load, run for a long time
125%<load< 150%, 10 mins
load>150%, 1s
Normal switching time
0
System
O
verall
w
orking efficiency
the maximum is
9
4
%
ECO mode is 98%

3Phase HF UPS 10-120kva USER Manual
Page6
Display
LCD+LED
EMI
IE
C62040
-
2
EMS
IEC61000
-
4
-
2(ESD)
IEC61000-4-3(RS)
IEC6100-4-4(EFT)
IEC6100-4-5(Surge)
Noise (1m)
<58dB
I
nsulation resistance
>2M(500VDC)
I
nsulation strength
(Input and output ground)
2820Vdc
;
leakage current is lower than 3.5mA,
1min without flashover
Surge protection
Meet the Ⅳinstallation location
requirement of IEC60664-1, that is, the
ability of bearing 1.2/50us+8/20us
combination wave is not lower than
6KV/3KA
Protection degree
IP20
Batte
ry number
32/36/38/40 cells of
12V
battery
Installation
Connection mode
bottom incoming and outgoing

3Phase HF UPS 10-120kva USER Manual
Page7
Section II Installation of Single Machine System
2.1 Introduction
This section introduces the necessary UPS requirements of the UPS sitting and
routing.
Because each site possesses its particularity, this section does not introduce the
detailed installation steps but support the instructional general installation steps and
methods to the installation engineer. The installation engineer should handle according to
the specific situation of the site.
Notes:
Connect the UPS with the power after the agreement of the commissioning engineer.
The UPS installation should be implemented by the qualified engineer according to
the description of this section. All other equipment are not referred in this manual
will be accompanied by its detailed mechanical and electrical installation data when
shipping.
The standard PW UPS system can connect with the three-phase four-wire (earthing)
system TN,TT and IT alternating current power distribution network and support the
transformer optional parts of transferring three-wire to four-wire. If it used for the IT
alternating current power distribution network, a four-grade circuit breaker should be
equipped to the input referring to the relevant IT system standard.
Be careful to the installation of the battery. When connect the battery, the voltage of
the battery terminal will exceed 400Vdc, which possess mortal danger. Please wear
the eyes protecting cap to avoid the damage of the eyes from the accidental electric
arc. Take off the ring, watch and other metal adornment. Use the tool with the
insulated handle and wear the rubber glove. If the electrolyte of the battery leaks or
the battery is damaged, change the battery and put it in vessel with against sulphuric
acid. Handle it according to the local regulation. If the skin touches the electrolyte,
wash with water immediately.
2.2 Inspecting and Unpacking the UPS Cabinet
The cabinet is shipped bolted to a wooden pallet and protected with preservative bag.
The UPS cabinet is heavy. If unpacking instructions are not closely followed, the
cabinet may tip and cause serious injury.

3Phase HF UPS 10-120kva USER Manual
Page8
1. Carefully inspect the outer packaging for evidence of damage during transporation.
Do not install a damaged cabinet. Report any damage to the carrier and contact service
representative immediately.
2. Use a forklift or pallet jack to move the packaged cabinet to the installation site,
before unpacking. Insert the forklift or pallet jack’s forks between the pallet supports
and the bottom of the unit. Do not tilt the UPS cabinet more than 10° from vertical or the
cabinet may tip over.
3. Set the pallet on a firm, level surface, allowing a minimum clearance of 3m (10 ft)
on each side for removing the cabinet from the pallet.
4. Remove the protective covering from the cabinet.
5. Remove the packing material, and dispose them in a responsible manner.
6. Visual inspection: whether there is any transporting damage happened to the UPS,
including the internal and external of the battery. If yes, report to the carrier immediately.
7. Check up the product label and confirm the correctness of the equipment. The
equipment label is fixed behind the door of the equipment .And information such as
UPS model , capacity and main parameters is written in the label.
2.3 Storage
Keep UPS indoor with well air ventilation to avoid the over-wetting or
over-temperature environment.
2.4 Link (Connection)
After the complete position of the equipment, link the power wire referring to the
connection diagram in the Section V and according to the following steps:
Completely cut all input distribution switches and the internal power switches the
UPS. Stick the warning mark in these switches to avoid other people to operate them.
Open the UPS door and take down the under part protection cover, and the copper
bar of the connection power cable can be at your sight.
Connect the protection ground and other necessary earthing cable to the eathing
copper bar of the bottom in the UPS power supply equipment. All UPS cabinets should
be connected with the user’s earthing device.
Note: The connection of the ground wire and the midline should comply to the local
and the state’s relevant regulation.

3Phase HF UPS 10-120kva USER Manual
Page9
2.4.1 Incoming mode
PW series UPS adopts the bottom incoming, uncover the rubber grommet at the
bottom of the equipment when connect and the incoming hole can be seen.
2.4.2 Power cable
Design the external connection cable according to the description of this section and
the local connection regulation and considering the environment condition (temperature
and physical support media). The maximum stable alternating current and the direct
current of each model:
Figure 3: Input & output rated current of each capacity model
UPS rated power
(kVA)
Rated current (A)
I
nput current/phase
O
utput current/ phase
Discharge current
10 22 15 28
15 33 22 42
20 43 30 60
30 61 46 85
40
80
61
115
50 100 78 140
60 120 92 170
80
160
125
230
100 200 156 280
120
240
183
345
2.4.3 Public input connection
For the bypass and rectification sharing the same circuit of the commercial power
input(same AC source), connect the alternating current input cable to the UPS input
terminal (main path R-S-T, input N). Make sure of the correctness of the phase sequence.
2.4.4 Separate bypass connection
For the bypass and rectification from two different circuits of the commercial power
input(same AC source), connect the rectification input cable to the rectifier input terminal
(main path R-S-T) and connect the bypass power supply input cable with the bypass input
(bypass R-S-T) terminal. Make sure of the correctness of the phase sequence.
Note: For the system of the bypass and rectification input using two circuits of the
commercial power input, remove the short ribbon wire between the bypass and the
rectification input. Connect the midline of the bypass input and main path input together.

3Phase HF UPS 10-120kva USER Manual
Page10
2.4.5 System output connection
Connect the system output cable between the UPS output terminal (output U-V-W-
N)and the important load. If the load is not ready to accept the power when the
installation engineer reaches the site, properly handle the terminal’s safe insulation of the
system output cable.
2.4.6 External battery connection
1)Connect the battery cable(+\n\-)between the battery terminal of the UPS and the
battery switch. Pay attention to the polarity of the battery cable.
Note: For the connection of the cable between the battery terminal and the battery
switch, firstly connect from the switch terminal.
2)Reinstall all protection cover.
2.5 Control cable and communication
2.5.1 Features of the monitoring panel
According to the specific requirement of the site, auxiliary connection is required for
UPS realizing the function of management of the battery system (including the external
battery switch and temperature pickup of the battery), communication of personal
computer, warning signal to the external device or remote emergency power off. These
functions are realized through the monitoring panel in the back of the UPS front door and
the monitoring panel supports the following interfaces:
SNMP CAN RS232 NC TXNO BAT.TEMP.
AS400
RX
RS485
EPO
Diagram 15: Schematic diagram of the monitoring panel interface
2.5.1Input interface of emergency power off
UPS supports the emergency power off (EPO) function. It is realized through the
EPO press-button in the UPS control panel or the remote contact supported by the user.
EPO press-button is protected by the articulated plastic cover.
See in diagram 15,

3Phase HF UPS 10-120kva USER Manual
Page11
EPO
User's Switch
1 2 3 4
1-2 Connected,UPS operate EPO function,3-4 Open
EPO
User's Switch
1 2 3 4
Connect 1-2 with short cable to keep it always connected
,
3-4 open UPS operate EPO function
Figure 5: Description of the remote EPO interface
Note: All auxiliary cables should be the double insulation twisted cable and the sectional
area is 0.5~1.5mm2 when the longest connection distance is 25~50m.
2.5.2 AS400
Except for the communication protocol as mentioned above, this series UPS has
AS400 card (an optional accessory) for AS400 communication protocol . Please
contact your local distributor for details. The following is the pin assignment and
description of DB-9 connector in AS400 card.
Pin #
Description I/O
1 UPS Fail Output
2 Summary Alarm
Output
3 GND Input
4 Remote Shutdown
Input
5 Common Input
6 Bypass Output
7 Battery Low Output
8 UPS ON Output
9 Line Loss Output
2.5.3 Temperature detection interface of the external battery
Figure
16.2
: DB
-
9 Interface of AS400
communication protocol

3Phase HF UPS 10-120kva USER Manual
Page12
BAT. TEMP. Port is the battery temperature pickup interface. Temperature pickup of the
battery is usually connected with the external battery cupboard.
2.5.4 Serial port RS232
RS232 supplies the serial data to use as the interface of the background monitoring
software.
RS232 supplies the serial data to use as debugging and maintenance interface of the
authorized debugging and maintenance personnel and the switching of the SNMP card.
2.5.5 SNMP card interface
PW UPS supplies the communication interface of the SNMP card to install the
communication option SNMP card (optional) on site.
2.5.6 RS485 is this series inside RS485 communication card。
2.5.7 CAN is used for inside communication between LCD and UPS

3Phase HF UPS 10-120kva USER Manual
Page13
Section III: Installation of Battery
3.1 Introduction
UPS assembled battery is configured by several piles of batteries connected in series to
provide the rated DC input voltage for UPS inverter. The required battery backup time
(duration of load power supply when the utility is interrupted) is restricted by the ampere
hours of battery. So for longer back up time, it requires to connect several packs
batteries(same rated DC voltage) in parallel.
The provided battery cupboard has the following forms:
1. Complete set containing battery case, battery and protection components;
2. Containing battery case and protection components-no battery;
3. Only contains battery case-no battery and switch
It may need to disconnect the battery and UPS when maintain or repair the equipment.
The switch of the battery can be disconnected or shut off manually. The switch off
control can be realized through the under-voltage coil of battery switch or release??.
3.2 Safety
The operation of the battery of PW UPS system shall be particularly careful, because the
voltage of the battery is deadly dangerous when connect all the single batteries. With
regards to safety, the external battery shall be installed in the cabinet with lock or special
designed battery chamber to separate from the personnel (except for the qualified
engineer)
Note: The note related to the use and maintenance of battery is instructed in the battery
manual provided by the manufacturer. The note relevant to battery safety mainly includes
the necessary events in the installation and designing process; it may be adjusted
according to the local situation.
Warning:
The user cannot operate the parts that needed the tools to open behind the protection lap,
only the qualified personnel is permitted to open this type of protection lap. Besides,
please disconnect the internal battery before operating the isolation terminals used for
connecting external battery.

3Phase HF UPS 10-120kva USER Manual
Page14
The following safety notes shall be paid highly attention to when use battery:
1. There is the electric shock when use battery. Large short circuit current can cause fire
danger.
2. The voltage of the assembled batteries is 432Vdc with deadly danger, so please
comply with the safety notes of high voltage operation.
3. Only the qualified personnel can install and maintain the battery.
4. Wear the eye shield to avoid the accidental injury of arc.
5. Take down the ring, watch, necklace, bracelet and other medal ornaments.
6. Use the tools with insulated handle.
7. Wear the rubber glove and apron when use battery.
8. The leaked or damaged battery shall be put in the sulfate resistant container, and it
shall be disposed as scrap according to local regulations.
9. Immediately clean the skin if it contacts the electrolyte.
10. Scrap disposal of the battery shall comply with the local environment laws.
11. The quantity of new battery and old one shall be the same when replace the
battery.
3.3 Battery cabinet
3.3.1 Introduction
This battery cupboard can be used together with other machine cabinets, so that it can
contain more batteries to provide the system longer backup support time.
If there are two or more battery cupboards, which shall be installed side by side and
mutually connected. Besides, it suggests connecting the batteries in the general output
end in series after paralleling the air switch output end of battery cupboards.
3.3.2 Environmental temperature
Valve control lead accumulator is very sensitive to temperature, so the valve control
battery shall be used within the temperature of 15℃~25℃. When the temperature is
below 25℃, the environmental temperature increases 1℃, the battery capacity will
increase 1%. Therefore, use the battery above the temperature of 25℃ will shorten its

3Phase HF UPS 10-120kva USER Manual
Page15
service life.
If the battery and UPS are installed in one room, the maximum design environmental
protection shall be determined by the battery, not UPS. That is to say, if use the valve
control battery, the indoor temperature shall be within 15℃~25℃, not 0℃~40℃ (it is
the regulated working temperature range of main equipment). The temperature is allowed
the deviation in a short time; On the premise that the average temperature should
exceed 25℃.
3.3.3 Temperature pickup of battery
The temperature plate of the battery can be installed in the highest temperature position
of battery cupboard (generally at the top), and it is connected directly to UPS control
system. If use the control panel of the battery switch, connect UPS control system
through the control panel of battery switch. This function can regulate the float charge
voltage of battery to make it inversely proportional to battery cupboard/room temperature.
So the battery can be protected from over charge under high temperature enviroment.
3.3.4 Cable incoming
The incoming of battery is from bottom. When the incoming is from bottom, take off the
bottom shielding piece of the equipment, and then you can see the incoming hole.
3.3.5 Structural map of battery configuration
Note: Please pay high attention to the battery connection ,regarding the Negative
Pole”-“ , the Positive Pole”+” and the Neutral”N”,.
(1) Standard model with internal battery.
Please refer the below sketch Diagram 17-1

3Phase HF UPS 10-120kva USER Manual
Page16
Diagram 17-1: Battery connection
(2)For long back up time model with external battery -----Battery quantity from
+/-14-20PCS settable on LCD screen
Please refer the Diagram 17-2: Battery connection as below:
Diagram 17-2: Battery connection
3.4 Power cable of battery
3.4.1 Installation of battery
1.Generally, the space between the vertical surface and the sides shall be at 1~10 mm,

3Phase HF UPS 10-120kva USER Manual
Page17
which can allow the surrounding air freely flow.
2.There shall be a certain space between battery top and the above barricade to facilitate
the monitoring and maintenance of battery.
3.The battery shall be installed from the bottom to the top to avoid the top-heaviness.
4. There shall be retained more than 1 meter’s space around the battery cupboard, which
can facilitate the maintenance and air flow.
3.4.2 Battery connection
1.When the battery cupboard is installed on the elevated floor, the power cable of battery
and the battery switch-controlled cable can enter UPS cabinet from the bottom. If UPS is
installed adjacently to the battery cupboard on the solid floor, these cables can pass
through the machine cabinet through the underside incoming hole of battery cupboard.
2.Generally, it suggests connecting the cables between the same-layer batteries first, and
then connecting the cables between the layers, finally connecting the battery switch and
battery terminals.
3.Install the insulating cover to the terminals after connecting the battery terminals.
4.Connect the switch end first when connect the battery terminal and cables between the
battery switches.
Section IV Installation of Parallel System
The installation of parallel machine shall comply with the installation procedures of the
single machine system and the requirements of this section.
4.1UPS single machine of parallel system
Put the single machine side by side and install these machines according to Diagram 18.It
suggests using external bypass cabinet to facilitate the maintenance and system testing.

3Phase HF UPS 10-120kva USER Manual
Page18
Diagram 18: Typical 1+N system principle
Note: The internal maintaining bypass switch CB3 must be taken off when the load
exceeds the capacity of single machine.
All the single machines must be connected with double insulated shielding parallel
controlled cable of 30m (longest).

3Phase HF UPS 10-120kva USER Manual
Page19
Diagram 19: Schematic diagram of parallel signal cable’s connection
4.2 Hot backup system
Put the single machine side by side and connect these machines according to the
following instruction.
The hot backup system is configured by two UPS single machines with same capacity,
connected in series and one is the host (subordinate UPS), the other is slave (superior
UPS). Besides, the host and slave are determined by the connection of power cable and
setting of allocation software. Normally, the host and slave are operated of inverted
supply mode, and the output of the slave UPS single machine connects to the bypass
input of the host UPS. The output of the host UPS is to be connected with the load, and
synchronize with slave UPS. When the inverter of host UPS connected with the load
happened with fault, power supply will be provided by the slave UPS for the load through
the bypass of host UPS. Moreover, the system can be set to make the host UPS run
alternatively with inverted supply and bypass modes, so that the two UPS can provide the
power supply for the load through alternative operation.
Note: As for the hot backup system, the first thing is to start up the host.

3Phase HF UPS 10-120kva USER Manual
Page20
Diagram 20: Schematic diagram of hot backup parallel machine (host and slave)
The wring of power cable is similar to single system machine, the different is to connect
the output of superior(host) UPS with the bypass input of the subordinate(slave) UPS in
the hot backup system, and the subordinate UPS supplies the load through its inverter or
bypass. Besides, the input power supply of the bypass and main path must use the same
neutral wire input terminal.
Table of contents
Other Upsen UPS manuals