US drives PHOENIX Series User manual

INSTRUCTION MANUAL
PHOENIX
SENSORLESS VECTOR AC DRIVE
7 1/2 TO 3500 HP

Thank You
We at US Drives would like to say thank
you for purchasing our product. We
believe the Phoenix AC Drive Series is
the most problem free product in the
market today. If you have any questions
or comments please feel free to call us.
On behalf of all of us here once again
thank you.
Recording Drive Information
It is a good idea to record all drive
nameplate information for future reference.
The nameplate is usually mounted on the
side of the drive. The following tables
should be filled in during starting or prior to
starting the drive.
Drive Part Number
P/N
Drive Serial Number
S/N
Software Revision Level
SRL
Free Software
Free software for setting and storing of
parameters is available to all owners of the
Phoenix AC Drive Series. Please fill out the
owners registration card and mail it in and
we will send one to you. You can also call
us if you need it quicker.
Safety Warnings
AC drives, like all electrical equipment in
industry, if not properly installed and operated
can cause personal injury. Always use
common sense when working around electrical
equipment. Make sure you read this manual
before any work on the drive begins. Never
work on this drive if you are tired or under the
influence of any drug. The drive must be
grounded and installed in accordance with
National Electrical Codes (NEC) and any local
codes. Make sure that all power is
disconnected, before working on the drive.
Always measure the incoming voltage at the
drive to make sure it is zero after disconnecting
the power. Make sure all air passages are
clear for proper cooling of the drive. After the
drive is energized lethal voltages are present.
Wait at least 5 minutes after disconnecting
power before working on the drive, since
high voltages will still be present. Call us if you
have any questions.
Branch Circuit Protection
Branch circuit protection must be provided by
the end user. In this manual you will find
recommended fuse sizes and types for each
Horsepower size.
Mounting Location Of The Drive
The drive should be installed in a well
ventilated, moisture free area. If there are:
fumes; vapors; dirt; lint;, liquids or gases
that can interact with the drive, then a clean
air supply must be provided. The ambient
temperature should not exceed the range of
14 F to 122 F (-10 C to 50 C). If the drive
will be subject to vibration then the
enclosure should be shock mounted.
Maintenance
If the enclosure is subject to foreign material,
clean the enclosure and check any filters for
build up of debris. If the inside of the enclosure
needs cleaning, a low pressure vacuum
cleaner is recommended. Do not use an air
hose because of the possible oil vapor in the
compressed air and its high pressure.

TABLE OF CONTENTS i
K:\Source Files\Phoenix Instruction Manual 4-20-00\PHOENIX USER MANUAL44.doc
SECTION TITLE PAGE
1.0 INTRODUCTION 1-1
1.1 Manual Objectives 1-1
1.1.1 Who Should Use this Manual 1-1
1.2 Safety 1-1
1.2.1 General Safety Precautions 1-1
1.3 Model Ratings 1-1
1.5 Specifications And Features 1-2
2.0 INSTALLATION AND WIRING 2-1
2.1 Safety Warning 2-1
2.2 Initial Checks 2-1
2.3 Determining Control Location 2-1
2.4 Mounting 2-1
2.5 AC Supply Source 2-4
2.5.1 Unbalanced Systems 2-4
2.5.2 Ungrounded Distribution Systems 2-4
2.5.3 Input Power Conditioning 2-4
2.5.4 Input Fusing 2-4
2.6 Input Devices 2-4
2.7 Electrical Interference (EMI/RFI) 2-5
2.7.1 Drive Immunity 2-5
2.8 Grounding 2-5
2.8.1 Grounding Sensitive Circuits 2-5
2.8.2 Motor Cable Grounding 2-5
2.8.3 Control Logic and Signal Grounding 2-6
2.9 Power Cabling 2-8
2.9.1 Lugs Kits 2-8
2.9.2 Motor Cables 2-11
2.9.2.1 Shielded Motor Cable 2-11
2.9.2.2 Conduit for Routing Motor Cables2-11
2.9.2.3 Motor Lead Lengths 2-11
2.10 Control and Signal Wiring 2-11
2.10.1 Signal Conduit Requirements 2-15
2.10.2 Signal Wire Requirements 2-15
2.10.3 2-Wire and 3-Wire Control 2-15
2.10.4 Wiring for Pre-Programmed I-O Setups 2-16
2.10.4.1 Hand-Off-Auto 2-16
2.10.4.2 Local/Remote Auto/Manual 2-16
3.0 REAL-TIME OPERATOR MODULE 3-1
3.1 ROM Description 3-1
3.2 Display Panel Key Descriptions 3-1
3.3 Control Panel Key and LED Descriptions 3-1
4.0 START-UP AND QUICK SETUP 4-1
4.1 Start-up Procedure for Running With
MOP or Speed POT 4-1
SECTION TITLE PAGE
4.1.1 Wiring Checks-Motor Disconnected 4-1
4.1.2 Drive Programming 4-2
4.1.3 Remove Power 4-2
4.1.4 Reconnect Motor 4-2
4.1.5 Check for Correct Motor Rotation 4-2
4.1.6 Check for Proper Operation 4-3
5.0 DRIVE PROGRAMMING 5-1
5.1 Power-up Display 5-1
5.2 Entering Security Codes 5-1
5.3 Advanced Drive Programming 5-2
5.3.1 Frequency Reference Definitions 5-2
5.3.2 V/Hz Curves 5-5
5.3.3 PWM Carrier Programming 5-8
5.3.4 Flycatcher (Catch a Spinning Motor) 5-8
5.3.5 Auto Restart 5-8
5.3.6 Motor Overload 5-9
5.3.7 Preset Speeds 5-11
5.3.8 MOP Function 5-11
5.3.9 Critical Speed Rejection 5-11
5.3.10 Input Contacts 5-12
5.3.10.1 Pre-Programmed Setups 5-12
5.3.10.2 Custom I-O 5-12
APPENDIX 6-1
2-Wire Start/Stop Set-Up Sheet 6-2
3-Wire start/stop Set-Up Sheet 6-3
Standard Drive with HOA Switch 6-4
Standard HVAC Drive with Bypass 6-5
VFD with Disconnect & Fuses Diagram 6-10
VFD Nema1 w/ Discon. & Fuses Mounting Info. 6-11
Mounting Info: Size 1 Nema 12 VFD Only 6-12
Mounting Info: Size 1 Nema 12 / Disconnect & Fuses 6-13
Mounting Info: Size 2 Nema 12 / Disconnect & Fuses 6-14
Process Signal Follower Programming 6-15
3-15 PSI Signal Follower Programming 6-16
Phoenix Option Board Connection Diagram 6-17
Drive to PC Serial Connection 6-18
Remote Keypad Connection Diagram 6-20
Remote Keypad Bezel Mounting Instruction 6-21
Drive Faults Description 6-22
Power Circuit Test Table 6-23

ii LIST OF FIGURES AND TABLES
FIGURE PAGE
2-1 Required Surrounding space 2-1
2-2a Phoenix Mounting Information:
Size 1 Through Size 2 Units 2-2
2-2b Phoenix Mounting Information:
Size 3 Through Size 4 Units 2-3
2-3 Recommended Power Wiring 2-7
2-4 Terminal Block Location for
Drive Control Board 2-13
2-5 Control Logic and Signal Wiring 2-14
2-6a “2-Wire” or “Maintained Contact” Control 2-15
2-6b “3-Wire” or “Momentary Contact” Control 2-15
2-7a HVAC HOA#1 H25 A34 Setup
3-Wire Hand / 3-Wire Auto Control 2-18
2-7b HVAC HOA#2 H25 A3 Setup
3-Wire Hand / 2-Wire Auto Control 2-18
2-7c HVAC HOA#3 H2 A34 Setup
2-Wire Hand / 3-Wire Auto Control 2-18
2-7d HVAC HOA#4 H2 A3 Setup
2-Wire Hand / 2-Wire Auto Control 2-18
2-7e HVAC L/R A/M#1 L25R34
3-Wire Local / 3-Wire Remote Control 2-19
2-7f HVAC L/R A/M#2 L25R3
3-Wire Local / 2-Wire Remote Control 2-19
2-7g HVAC L/R A/M#3 L2R34
2-Wire Local / 3-Wire Remote Control 2-19
2-7h HVAC L/R A/M#4 L2R3
2-Wire Local / 2-Wire Remote Control 2-19
3-1 ROM Front Panel 3-1
3-1 Control Wiring for ROM MOP Operation 4-1
5-1 Custom V/Hz Curve Parameter
Definition 5-5
5-2a Pre-programmed Curve 1 5-5
5-2b Pre-programmed Curve 2 5-6
5-2c Pre-programmed Curve 3 5-6
5-2d Pre-programmed Curve 4 5-6
5-2e Pre-programmed Curve 5 5-6
5-2f Pre-programmed Curve 6 5-7
5-2g Pre-programmed Curve 7 5-7
5-2h Pre-programmed Curve 8 5-7
5-2i Pre-programmed Curve 9 5-7
5-3 PWM Carrier Curve 5-8
5-4a Motor Thermal Continuous
Operation Zone 5-9
5-4b Thermal Curves for Various Classes for
Blower-Cooled (TENV) Motor 5-10
5-4c Motor Trip Thermal Curves for
General Purpose (TEFC) Motor 5-10
5-4d Motor Thermal Trip Curve for
Blower-Cooled (TENV) Motor 5-11
TABLE PAGE
1-1 Class 200 Drive Models(Typical
Voltage 208/230/240Vac) 1-5
1-2 Class 400 Drive Models(Typical
Voltage 380/415/480Vac) 1-6
1-3 Class 500 Drive Models(Typical
Voltage 525/575/480Vac) 1-7
2-1 Power Signal Description 2-8
2-2a Lug Kits for Class 200 Drives Models 2-8
2-2b Lug Kits for Class 400 Drives Models 2-9
2-2c Lug Kits for Class 500 Drives Models 2-10
2-3 Drive Main Control Board Terminal
Block Layout 2-12
2-4 Maximum Recommended Motor
Cable Lengths 2-13
5-2a Parameter List in Alphabetical Order 5-19
5-2b Parameter List in Numerical Order 5-21
5-3 Parameter Definitions 5-23

INTRODUCTION 1-1
1.0 INTRODUCTION
1.1 MANUAL OBJECTIVES
The purpose of this manual is to provide the user with
the necessary information to install, program, start-up
and maintain the PHOENIX Digital AC Drive. This
manual should be read thoroughly before operating,
servicing or setting up the PHOENIX Drive.
1.1.1 Who Should Use this Manual
This manual is intended for qualified service personnel
responsible for setting up and servicing the PHOENIX
AC Drive. You must have previous experience with
and a basic understanding of electrical terminology,
programming procedures, required equipment and
safety precautions before attempting and service on
the PHOENIX Drive.
1.2 SAFETY
1.2.1 General Safety Precautions
WARNING
Only personnel familiar with the PHOENIX Drive and
the associated machinery should plan or implement
the installation, start-up, and subsequent maintenance
of the Drive. Failure to comply may result in personnel
injury and/or equipment damage.
WARNING
An incorrectly applied or installed Drive can result in
component damage or a reduction in product life.
Wiring or application errors such as undersizing the
motor, incorrect or inadequate AC supply or excessive
ambient temperatures may result in damage to the
Drive or motor.
WARNING
This Drive contains ESD (Electrostatic Discharge)
sensitive parts and assemblies. Static control
precautions are required when servicing or repairing
this assembly. Component damage may result if ESD
control procedures are not followed. If you are not
familiar with static control procedures, please consult
with the factory.
1.3 MODEL RATINGS
The following tables 1-1 through 1-3 show the
PHOENIX model ratings for size 1 through size 4 for
class 200, class 400 and class 500 units.

1-2 INTRODUCTION
1.5 SPECIFICATIONS AND FEATURES
Electrical Specifications:
Rated Input Voltage: 200-250Vac, 380-500Vac, 500-600Vac
-10% of minimum, +10% of maximum.
Frequency Tolerance: 48-63 Hz
Number of Phases: 3
Displacement Power Factor: .95 or greater
Efficiency: 97% or greater at rated current
Max. Short Circuit Current Rating: 200,000A rms symmetrical, 600 volts ( when used with AC input line fuses
specified in tables 1-1 to 1-3).
Control Specifications:
Control Method: Sine coded PWM with programmable carrier.
Space Vector control.
Output Voltage: 0 to rated voltage.
Output Frequency Range: 0 to 400 Hz.
Frequency accuracy: Analog reference:0.1% of max frequency.
Digital reference: 0.01% of max frequency.
Frequency resolution: Analog reference:0.06Hz at 60Hz.
Digital reference: 0.0005Hz at 60Hz.
Accel/Decel: 0.1 to 3600 sec.
Drive overload: At Constant Torque: 150% of drive rated output for 2 minutes.
At Variable Torque: 120% of drive rated output for 2 minutes.
Inverse Time Overload: Programmable for class10, 20 and 30 protection with speed sensitive protection
to comply with N.E.C. Article 430
Current limit: Proactive current limit programmable in % of motor rated current.
Braking torque: Approximately 20%.
V/Hz curves: Custom curve programming plus 9 preprogrammed standard patterns.
Maximum connected motor: 2 times rated drive horsepower.
Control power ride-thru: 2 seconds or greater, depending on load.
Environmental Specifications:
Ambient Temperature: -10°C to 50°C (14°F to 122°F) Nema type 1 enclosed.
Storage Temperature: -40°C to 70°C (-40°F to 158°F) Nema type 1 enclosed.
Altitude: Sea level to 3000 Feet [1000m] without derating.
Humidity: 95% relative humidity non-condensing.
Vibration: 9.8m/sec2 (1.0G) peak.
Immunity: IEEE C62.41-1991 Category B (Formally known as IEEE 587)
Input R.F.I. Filter: standard on all models.
Physical attributes:
Mounting: Though hole or panel mount for size 1 to size 3 drives.
Size 4 drives are free standing enclosure.
Nema Rating: Type 1 (IP20) as standard, Type 12 (IP54) optional.
Construction: Steel construction ( reduces E.M.I.)

INTRODUCTION 1-3
Protective Features:
• Speed sensitive programmable motor overload protection to comply with N.E.C. Article 430.
• Drive overload protection to protect inverter.
• Motor stall protection at acceleration /deceleration and constant speed operation.
• Peak output current monitoring to protect against line-to-line shorts and line-to-ground shorts.
• Ground fault monitoring.
• Heatsink over-temperature monitoring.
• AC line overvoltage protection.
• DC bus over-voltage protection.
• DC bus under-voltage protection.
• Programmable stall protection.
• Control power ride-thru 2 seconds or greater, depending on load.
• Internal power supply monitoring.
• AC power loss detection.
• Critical speed rejection with programmable 3 points with bandwidth to avoid mechanical resonance.
• Flycatcher “catch a spinning motor”.
Control I/O:
• 8 Digital Inputs: 6 user programmable inputs and 2 dedicated inputs for “Reset” and “External Fault”
rated for 24Vdc logic control.
• 5 Digital Outputs: 3 programmable dry contacts rated 115Vac @ 5A; 30Vdc @ 3.5A.
2 open collector outputs rated 24Vdc @ 100mA. - programmable.
• 3 analog inputs: -10 to +10V (10 bits) with input impedance: 125KΩ, or 4-20 mA @ 250Ω- Programmable.
• 2 analog outputs: -10 to +10V (10 bits) @ 2 mA max; output impedance = 100Ω. - Programmable.
• 1 meter output: Use with 100µA movement analog meter - Programmable.
• 2 voltage references: +10Vdc reference and -10Vdc reference @ 5 mA max.
• 24Vdc source: Use to power operator pushbuttons and US Drives option boards: 24Vdc @ 100 mA max.
Standard Drives Features:
• Third generation IBGT.
• Nema type 1 (IP20) as standard for all models.
• 50°C ambient with standard Nema type 1 (IP20) enclosure.
• High voltage ratings: 250Vac+10% , 500Vac+10% models, and 600Vac+10% models
• Built-in power factor correction DC reactor for all models.
• Standard electrically isolated communications port: RS422/485.
• Input line suppression: Metal oxide varistors for line-to-line and line-to-ground voltage surge protection.
• Built-in radio frequency filter.
• Real Time Clock.
• Nonvolatile parameter storage.
• All parameters are saved in Battery backed R.A.M. and in EEPROM (nonvolatile).
• Digital chart recorder: eight independent channels with time/date stamp user programmable.
• Autologging fault history: twelve last faults recorded in order of occurrence (time/date stamped).
• Internal control diagnostics.
• Simple programming through the Real-time Operator module (R.O.M.) with all data entries and monitoring in
engineering units with English descriptions.
• Setpoint Control P.I.D.
• DC Braking.
• Critical speed rejection.
• Programmable autorestart.
• Fixed or variable carrier ( programmable).
• Two-real-time timers with alarms for customer use.
• Programmable “AC Power On Time” accumulator.
• Programmable “Total Drive Run Time” accumulator.
• Custom V/Hz programming plus 9 preprogrammed curves patterns.
• 2 levels of parameter security codes.
• User definable displays with programmable format and parameter scaling.
• 6 programmable digital inputs for custom setups. 2 inputs are dedicated: Reset, and external fault.

1-4 INTRODUCTION
• 9 preprogrammed I/O setups: 8 popular HVAC setups plus 1 Industrial setup.
• Metering: AC line voltage, motor current, motor voltage, DC Bus voltage, Carrier frequency, and more…
• 8 programmable preset speeds.
• M.O.P. function.
• Programmable PWM carrier frequency, fixed or variable.
Options Kits:
Process Signal Follower: provides wide range of reference signals from the outside world. The output to
the drive is electrically isolated. No external supply is required. This kit mounts
inside the drive enclosure
INPUT PROCESS
CURRENT PROCESS VOLTAGE
4 to 20 mA Up to 192 Vdc
OUTPUT 4 to 20 mA or 0 to 10Vdc
0 to 15 PSI Follower: gives the drive the ability to accept a pneumatic pressure source as a reference
signal. A 3/16 inch I.D. hose fitting is provided for customer connection.
The output to the drive can be either 4-20 mA or 0 to 10Vdc.
No external supply is required. This kit mounts inside the drive enclosure
115Vac Operator Interface: This board enables the customer to use 115Vac type operator interface.
Use this option. This kit mounts inside the drive enclosure.
External power 115Vac is required. This kit mounts inside the drive enclosure.
RS232 to RS 422 Converter: allows a standard PC to be connected to the serial port of the drive.
External power 115Vac is required. This kit mounts inside the drive enclosure
Remote Keypad (R.O.M.) kit: The standard R.O.M. can be mounted within 50 feet [15m], But with this kit the
ROM can mounted up 4000 feet from the drive. External power 115Vac is
required.
KW and Kwh Metering: Gives the ability to display Kw, Kwh and the cost of running the motor. The cost
of power is entered for this calculation. No external supply is required.
Drive Software: This software is used to configure, and save drive data using a standard PC. The
software is available to all customers who purchase a phoenix, free of charge,
as long as the drive registration card is filled out and returned.

INTRODUCTION 1-5
Table 1-1
Class 200 Drive Models (Typical Voltage 208/230/240 VAC)
200-250VAC (-10% to +10%)
Frame
Designation
NEMA 1
(IP20)
Catalog
Number
Motor HP1
Continuous2
OutputCurrent
(Amps)
Output
KVA3
Input Current
(Amps)
Input
KVA3
Maximum
Recommended
AC Line Fuses4
(Amps)
CT VT CT VT CT VT CT VT CT VT
SIZE 1
0200-0010-N1
7.5
10
22
28
9
12
20
25
8
10
40
0200-0015-N1 10 15 28 42 12 17 25 36 10 15 60
0200-0020-N1 15 20 42 54 17 22 36 50 15 21 70
0200-0025-N1 20 25 54 68 22 28 50 61 21 25 90
0200-0030-N1 25 30 68 85 28 35 61 79 25 33 100
0200-0030CT-N1 30 - 80 - 33 - 74 - 31 - 100
SIZE 2 0200-0040-N1 30 40 80 104 33 43 74 96 31 40 150
0200-0050-N1 40 50 104 130 43 54 96 120 40 50 200
0200-0060-N1 50 60 130 163 54 68 120 155 50 64 250
0200-0075-N1 60 75 145 192 60 80 140 186 58 77 300
0200-0100-N1 75 100 192 248 80 103 186 230 77 96 300
0200-0100CT-N1 100 - 248 - 103 - 230 - 96 - 300
SIZE 3 0200-0125VT-N1 - 125 - 312 - 130 - 290 - 121 400
0200-0125CT-N1 125 - 312 - 130 - 290 - 121 - 400
0200-0150VT-N1 - 150 - 360 - 150 - 335 - 139 500
0200-0150CT-N1 150 - 360 - 150 - 335 - 139 - 500
0200-0200VT-N1 - 200 - 480 - 200 - 446 - 186 600
0200-0200CT-N1 200 - 480 - 200 - 446 - 186 - 600
0200-0250VT-N1 - 250 - 602 - 250 - 560 - 233 800
0200-0250CT-N1 250 - 602 - 250 - 560 - 233 - 800
1 Horsepower based on 220-240 Vac Motors.
2Constant Torque (CT) overload rating is 150% for two minutes; Variable Torque (VT) overload rating is 120 % for two minutes.
3Output and Input KVA at nominal 240Vac
4UL Class T, J, and Semiconductor Fuses (preferred): Gould Shawmut A50Q, Bussmann FWH.
5Built-in as standard

1-6 INTRODUCTION
Table 1-2
Class 400 Drive Models (Typical Voltage 380/415/480 VAC)
380-500VAC (-10% to +10%)
Frame
Designation
NEMA 1
(IP20)
Catalog
Number
Motor HP1
Continuous2
Output Current
(Amps)
Output
KVA3
Input Current
(Amps)
Input
KVA3
Maximum
Recommended
AC Line Fuses4
(Amps)
CT VT CT VT CT VT CT VT CT VT
SIZE 1
0400-0015-N1
10
15
14
21
12
17
13
18
11
15
35
0400-0020-N1 15 20 21 27 17 22 18 24 15 20 40
0400-0025-N1 20 25 27 34 22 28 26 31 22 26 50
0400-0030-N1 25 30 34 43 28 36 31 38 26 32 60
0400-0040-N1 30 40 40 52 33 43 36 48 30 40 70
0400-0050-N1 40 50 52 66 43 55 48 56 40 47 90
0400-0060-N1 50 60 65 82 54 68 56 72 47 60 100
0400-0060CT-N1 60 - 77 - 64 - 67 - 56 - 100
SIZE 2 0400-0075-N1 60 75 77 97 64 81 67 83 56 69 125
0400-0100-N1 75 100 96 124 80 103 86 110 71 91 175
0400-0125-N1 100 125 124 156 103 130 110 139 91 116 200
0400-0150-N1 125 150 156 180 130 150 139 163 116 136 250
0400-0200-N1 150 200 180 240 150 200 167 223 139 186 350
0400-0200CT-N1 200 - 240 - 200 - 223 - 186 - 350
SIZE 3 0400-0250VT-N1 - 250 - 302 - 251 - 281 - 234 400
0400-0250CT-N1 250 - 302 - 251 - 281 - 234 - 400
0400-0300VT-N1 - 300 - 361 - 300 - 336 - 279 500
0400-0300CT-N1 300 - 361 - 300 - 336 - 279 - 500
0400-0350VT-N1 - 350 - 414 - 344 - 385 - 320 600
0400-0350CT-N1 350 - 414 - 344 - 385 - 320 - 600
0400-0400VT-N1 - 400 - 477 - 397 - 444 - 369 700
0400-0400CT-N1 400 - 477 - 397 - 444 - 369 - 700
0400-0500VT-N1 - 500 - 600 - 499 - 558 - 464 800
0400-0500CT-N1 500 - 600 - 499 - 558 - 464 - 800
SIZE 4 0400-0600VT-N1 - 600 - 720 - 599 - 670 - 557 -
0400-0600CT-N1 600 - 720 - 599 - 670 - 557 - 5
0400-0700VT-N1 - 700 - 840 - 698 - 781 - 649 5
0400-0700CT-N1 700 - 840 - 698 - 781 - 649 - 5
0400-0800VT-N1 - 800 - 960 - 798 - 893 - 742 5
0400-0800CT-N1 800 - 960 - 798 - 893 - 742 - 5
0400-0900VT-N1 - 900 - 1080 - 898 - 1004 - 835 5
0400-0900CT-N1 900 - 1080 - 898 - 1004 - 835 - 5
0400-1000VT-N1 - 1000 - 1200 - 998 - 1116 - 928 5
0400-1000CT-N1 1000 - 1200 - 998 - 1116 - 928 - 5
0400-1250VT-N1 - 1250 - 1500 - 1247 - 1395 - 1160 5
0400-1250CT-N1 1250 - 1500 - 1247 - 1395 - 1160 - 5
0400-1500VT-N1 - 1500 - 1800 - 1496 - 1674 - 1392 5
0400-1500CT-N1 1500 - 1800 - 1496 - 1674 - 1392 - 5
0400-1750VT-N1 - 1750 - 2100 - 1746 - 1953 - 1624 5
0400-1750CT-N1 1750 - 2100 - 1746 - 1953 - 1624 - 5
0400-2000VT-N1 - 2000 - 2400 - 1995 - 2232 - 1856 5
0400-2000CT-N1 2000 - 2400 - 1995 - 2232 - 1856 - 5
0400-2500VT-N1 - 2500 - 3000 - 2494 - 2790 - 2320 5
0400-2500CT-N1 2500 - 3000 - 2494 - 2790 - 2320 - 5
THIS VOLTAGE SERIES HAS A MAXIMUM HP RATING OF 3,OOOHP.
1 Horsepower based on 440-480 Vac Motors.
2Constant Torque (CT) overload rating is 150% for two minutes; Variable Torque (VT) overload rating is 120 % for two minutes.
3Output and Input KVA at nominal voltage 480Vac
4UL Class T, J, and Semiconductor Fuses (preferred): Gould Shawmut A50Q, Bussmann FWH.
5Built-in as standard

INTRODUCTION 1-7
Table 1-3
Class 500 Drive Models (Typical Voltage 525/575/600 VAC)
500-600VAC (-10% to +10%)
Frame
Designation
NEMA 1
(IP20)
Catalog
Number
Motor HP1
Continuous2
Output
Current
(Amps)
Output
KVA3
Input Current
(Amps)
Input
KVA3
Maximum
Recommended
AC Line Fuses4
(Amps)
CT VT CT VT CT VT CT VT CT VT
SIZE 1
0500-0015-N1
10
15
11
17
11
17
12
17
12
17
30
0500-0020-N1 15 20 17 22 17 22 17 21 17 21 35
0500-0025-N1 20 25 22 28 22 28 22 28 22 28 40
0500-0030-N1 25 30 27 34 27 34 27 34 27 34 50
0500-0040-N1 30 40 32 41 32 41 32 40 32 40 60
0500-0050-N1 40 50 41 52 41 52 40 48 40 48 70
0500-0060-N1 50 60 52 65 52 65 54 61 54 61 90
0500-0060CT-N1 60 - 62 - 62 - 58 - 58 - 90
SIZE 2 0500-0075-N1 60 75 62 78 62 78 58 72 58 72 100
0500-0100-N1 75 100 77 99 77 99 75 96 75 96 150
0500-0125-N1 100 125 99 125 99 124 96 124 96 123 175
0500-0150-N1 125 150 125 157 124 156 124 154 123 153 200
0500-0200-N1 150 200 144 192 143 191 142 191 141 190 300
0500-0200CT-N1 200 - 192 - 191 - 191 - 190 - 300
SIZE 3 0500-0250VT-N1 - 250 - 242 - 241 - 240 - 239 350
0500-0250CT-N1 250 - 242 - 241 - 240 - 239 - 350
0500-0300VT-N1 - 300 - 289 - 288 - 286 - 285 400
0500-0300CT-N1 300 - 289 - 288 - 286 - 285 - 400
0500-0350VT-N1 - 350 - 336 - 335 - 333 - 331 500
0500-0350CT-N1 350 - 336 - 335 - 333 - 331 - 500
0500-0400VT-N1 - 400 - 382 - 380 - 378 - 377 600
0500-0400CT-N1 400 - 382 - 380 - 378 - 377 - 600
0500-0500VT-N1 - 500 - 500 - 498 - 495 - 493 700
0500-0500CT-N1 500 - 500 - 498 - 495 - 493 - 700
0500-0600VT-N1 - 600 - 600 - 598 - 594 - 592 800
0500-0600CT-N1 600 - 600 - 598 - 594 - 592 - 800
SIZE 4 0500-0700VT-N1 - 700 - 750 - 697 - 693 - 690 5
0500-0700CT-N1 700 - 750 - 697 - 693 - 690 - 5
0500-0800VT-N1 - 800 - 800 - 797 - 792 - 789 5
0500-0800CT-N1 800 - 800 - 797 - 792 - 789 - 5
0500-0900VT-N1 - 900 - 900 - 896 - 891 - 887 5
0500-0900CT-N1 900 - 900 - 896 - 891 - 887 - 5
0500-1000VT-N1 - 1000 - 1000 - 996 - 990 - 986 5
0500-1000CT-N1 1000 - 1000 - 996 - 990 - 986 - 5
0500-1250VT-N1 - 1250 - 1250 - 1245 - 1238 - 1232 5
0500-1250CT-N1 1250 - 1250 - 1245 - 1238 - 1232 - 5
0500-1500VT-N1 - 1500 - 1500 - 1494 - 1485 - 1479 5
0500-1500CT-N1 1500 - 1500 - 1494 - 1485 - 1479 - 5
0500-1750VT-N1 - 1750 - 1750 - 1743 - 1733 - 1725 5
0500-1750CT-N1 1750 - 1750 - 1743 - 1733 - 1725 - 5
0500-2000VT-N1 - 2000 - 2000 - 1992 - 1980 - 1972 5
0500-2000CT-N1 2000 - 2000 - 1992 - 1980 - 1972 - 5
0500-2500VT-N1 - 2500 - 2500 - 2490 - 2475 - 2465 5
0500-2500CT-N1 2500 - 2500 - 2490 - 2475 - 2465 - 5
THIS VOLTAGE SERIES HAS A MAXIMUM HP RATING OF 3,500HP.
1 Horsepower based on 550-600 Vac Motors.
2Constant Torque (CT) overload rating is 150% for two minutes; Variable Torque (VT) overload rating is 120 % for two minutes.
3Output and Input KVA at nominal voltage 575Vac.
4UL Class T, CC, J, and Semiconductor Fuses (preferred): Gould Shawmut A70Q, Bussmann FWP.
5Built-in as standard

1-8 INTRODUCTION
END INTRODUCTION SECTION

INSTALLATION AND WIRING 2-1
2.0 INSTALLATION AND WIRING
Section 2.0 provides the information needed to
properly mount and wire the PHOENIX Drive. Since
most start-up difficulties are the result of incorrect
wiring, it is essential that the wiring is done as
instructed. Read and understand this section in its
entirety before actual installation begins.
2.1 SAFETY WARNINGS
WARNING
Only qualified electrical personnel familiar with the
construction and operation of this equipment and the
hazards involved should install, adjust, operate or
service this equipment.
WARNING
The control and its associated motors and operator
control devices must be installed and grounded in
accordance with all national and local codes (NEC,
VDE 0160, BSI, etc.). To reduce the potential for
electric shock, disconnect all power sources before
initiating any maintenance or repairs. Keep fingers
and foreign objects away from ventilation and other
openings. Keep air passages clear. Potentially lethal
voltages exist within the drive enclosure and
connections. Use extreme caution during installation
and start-up.
WARNING
The following information is only a guide for proper
installation. US Drives cannot assume responsibility
for the compliance or noncompliance to any code,
national, local or otherwise for the proper installation of
this drive or associated equipment. A hazard of
personal injury and/or equipment damage exists if
codes are ignored during the installation.
2.2 INITIAL CHECKS
Before installing the PHOENIX Drive, check the unit
for physical damage sustained during shipment. If
damaged, file a claim with the shipper and return for
repair following the procedures outlined on the back
cover. If no damage is observed, remove all shipping
restraints and padding. Check drive nameplate data
for conformance with the AC power source and motor.
2.3 DETERMINING CONTROL LOCATION
The PHOENIX Drive is suitable for most well-
ventilated factory areas where industrial equipment is
installed. Locations subject to steam vapors or
excessive moisture, oil vapors, flammable or
combustible vapors, chemical fumes, corrosive gases
or liquids, or excessive dirt, dust or lint should be
avoided unless an appropriate enclosure has been
supplied or a source of clean air is supplied to the
enclosure. The location should be dry and the
ambient temperature should not exceed 122°F (50°C).
If the mounting location is subject to vibration, the unit
should be shock mounted.
2.4 MOUNTING
Figure 2-1 shows the minimum required surrounding
air space for panel mounted PHOENIX Drives (size 1
through size 3 units). Note that the panel mounted
units must be mounted in an upright position. Figure
2-2a shows dimensional information for size 1 through
size 2 units. Figure 2-2b shows dimensional
information for size 3 through size 4 units. If through
panel mounting is chosen (available on size 1 through
size 3 units), a suitable sealant should be applied to
the mounting faces of the drive and the panel to
prevent leakage.
Figure 2-1
Minimum Required Surrounding Air Space
for size 1 through size 3 PHOENIX Drives

Frame
Designation H
Inches
[mm]
W
Inches
[mm]
D
Inches
[mm]
W1
Inches
[mm]
HP
Inches
[mm]
WP
Inches
[mm]
HT
Inches
[mm]
HM
Inches
[mm]
WT
Inches
[mm] Knockouts Weights
Lbs
[Kgs]
SIZE 1 27.00
[685.8] 12.67
[321.8] 11.91
[302.5] 9.75
[247.7] 25.21
[640.3] 7.75
[196.9] 23.00
[584.2] 12.5
[317.5] 11.03
[280.2] Four 1.359” [34.5] DIA. Knockouts
For 1” [25.4] Trade Size Conduits 75
[34]
SIZE 2 32.50
[825.5] 20.11
[510.8] 13.52
[343.4] 17.74
[450.6] 30.1
[764.5] 11.74
[298.2] 28.5
[723.9] 14.25
[362.0] 18.74
[476.0] Three 3” [76.2] & Three 1.359” [34.5] DIA. Knockouts
For 2.5” [63.5] & 1” [25.4] Trade Size Conduits 180
[82]
Figure 2-2a
PHOENIX Mounting Information: Size 1 Through Size 2 Units
2-2 INSTALLATION AND WIRING
* Note: Top and bottom endplates are removable to gain access to mounting holes and to punch holes for conduits.

NEMA TYPE 1 (IP20) DIMENSIONS: SIZE3 TO SIZE 4
INSTALLATION AND WIRING 2-3
Figure 2-2b
PHOENIX Mounting Information: Size 3 Through Size 4 Units
Frame
Designation
H
Inches
[mm]
W
Inches
[mm]
D
Inches
[mm]
W1
Inches
[mm]
HP
Inches
[mm]
WP
Inches
[mm]
HT
Inches
[mm]
HM
Inches
[mm]
WT
Inches
[mm]
Weights
Lbs
[Kgs]
SIZE 3
44.16
[1121.7]
31.13
[790.7]
17.81
[452.37]
28.81
[731.7]
42.21
[1072.1
25.31
[642.8]
40
[1016]
21
[533.4]
29.72
[754.9]
500
[227]
Size 3 can also be free-standing with optional floor stand kit from US Drives.
All size 4 drives are free-standingenclosures.
* Note: Top and bottom endplates are removable to gain access to mounting holes and to punch holes for conduits.

2-4 INSTALLATION AND WIRING
2.5 AC SUPPLY SOURCE
PHOENIX Drives are suitable for use on a power
system capable of delivering up to a maximum of
200,000 rms symmetrical amperes, 250/500/600
+10% volts maximum when used with AC input line
fuses specified in tables 1-1, 1-2 and 1-3 respectively.
WARNING
To guard against personal injury and/or equipment
damage caused by improper fusing, use only the
recommended line fuses specified in tables 1-1, 1-2
and 1-3.
2.5.1 Unbalanced Distribution Systems
The PHOENIX Drive is designed to operate on three-
phase supply systems whose line voltages are
symmetrical. Surge suppression devices are included
to protect the drive from lightning induced overvoltages
between line and ground. Where the potential exists
for abnormally high phase-to-ground voltages (in
excess of 125% of nominal), or where the supply
ground is tied to another system or equipment that
could cause the ground potential to vary with
operation, suitable isolation is required for the drive.
Where this condition exists, an isolation transformer is
strongly recommended.
2.5.2 Ungrounded Distribution Systems
All PHOENIX Drives are equipped with an MOV (Metal
Oxide Varistor) that provides voltage surge protection
which is designed to meet IEEE 587. The MOV circuit
is designed for surge suppression only (power line
transient protection), not continuous operation.
With ungrounded distribution systems, the phase-to-
ground MOV connection could become a continuous
current path to ground where the phase-to-ground
voltages are continuously above 125% of the nominal
line to line voltage.
2.5.3 Input Power Conditioning
Since all PHOENIX Drives have a built in 3% bus
reactor, an external line reactor or isolation
transformer is generally not required. Under extreme
conditions, however, an external line reactor or
isolation transformer may be required.
The basic guidelines for determining if a line reactor or
isolation transformer is required are as follows:
1. If the AC input power system does not have a
neutral or one phase referenced to ground (see
section 2.5.2), an isolation transformer with the
neutral of the secondary grounded is highly
recommended. If the line-to-ground voltages
on any phase can exceed 125% of the nominal
line-to-line voltage, an isolation transformer with
the neutral of the secondary grounded, is
always required.
2. If the AC line supplying the drive has power
factor correction capacitors that are switched in
and out, an isolation transformer or 3% line
reactors are recommended between the drive
and the capacitors.
3. If the AC line frequently experiences transient
power interruptions or significant voltage spikes,
an isolation transformer or 3% reactors are
recommended.
2.5.4 Input Fusing
WARNING
PHOENIX Drives sizes 1 through 4 do not provide
input power short circuit fusing. Maximum Recom-
mended AC Line Fuses are shown in tables 1-1, 1-2
and 1-3. Note that branch circuit breakers or
disconnect switches can not respond fast enough to
provide the level of protection that the drive
components require.
2.6 Input Devices
WARNING
Hardwired Stop Circuit
The drive start/stop control circuitry includes solid-
state components. If hazards due to accidental
contact with moving machinery or unintentional flow of
liquid, gas or solids exist, an additional hardwired stop
circuit is required to remove AC line power to the drive.
When AC power is removed, the motor will coast to a
stop. Consequently, an auxiliary braking method may
be required.
WARNING
Motor Starters
The PHOENIX Drive is intended to be controlled by
control input signals that will start and stop the motor.
A device that routinely disconnects then reapplies line
power to the drive for the purpose of starting and
stopping the motor is not recommended.

INSTALLATION AND WIRING 2-5
WARNING
Bypass Contactors
An incorrectly applied or installed bypass system can
result in Drive damage or reduction in product life.
The most common mistakes are:
• Wiring the AC line to the Drive output or control
terminals.
• Incorrect bypass or output circuits.
• Output circuits that do not directly connect to the
motor.
2.7 ELECTRICAL INTERFERENCE
(EMI/RFI)
2.7.1 Drive Immunity
The immunity of the PHOENIX Drives to externally
generated interference is outstanding. No special
precautions other than following the procedures
outlined in this manual are required.
It is recommended that the coils of AC and DC
energized contactors interfaced with the drives be
suppressed with RC networks and diodes respectively
or with similar devices. This is because non-
suppressed coils (inductors) can generate high
electrical transients.
In areas prone to frequent lightning strikes, the
standard MOV’s (Metal Oxide Varistors) supplied with
the drive may need to be supplemented with
additional surge suppression MOV’s on the AC line
feeding the drive
2.7.2 Drive Emissions
Care must be used in the routing of power and ground
connections to the drive to avoid interference with
sensitive equipment that may be nearby. The cable
from the drive to the motor carries switched voltages
and should be routed well clear of sensitive
equipment. The ground conductor of the motor cable
should be connected to the drive ground stud directly.
Connecting this ground conductor to a cabinet ground
point or ground bus bar may cause high frequency
current to circulate in the ground system of the drive
enclosure. The motor end of this ground conductor
must be solidly connected to the motor case ground.
See Figure 2-3.
Shielded or armored cable may be used to minimize
radiated emissions from the motor cable. The shield
or armor should be connected to the drive ground stud
and to the motor ground as shown in Figure 2-3.
2.8 GROUNDING
Refer to the “Recommended Power Wiring” diagram in
figure 2-3 for grounding instructions. The drive must
be connected to AC system ground using the power
ground stud(s) provided near the input and output
power terminal blocks. All drives provide a separate
power ground stud or terminal point for both the input
AC power terminal blocks (L1, L2 and L3) and the
output to motor terminal blocks (U, V, and W). Ground
impedance must conform to requirements of national
and local industrial codes (NEC, VDE 0160, BSI, etc.)
and should be inspected and tested at regular
intervals.
The outgoing motor cable ground wire connects
directly to the power ground stud as well as incoming
AC line system ground wire. These ground wires
must have a current rating in compliance with the
above mentioned national and local codes. This
results in the motor frame ground to be solidly
connected through the drive chassis to the AC system
ground.
Note that the drive signal common (COM) should not
be connected to the power ground stud directly. If
desired, one of these commons may be connected to
earth ground at a single point outside the drive
enclosure - see section 2.8.3 for more details.
For multiple drive systems, if the signal common on
each drive is to be grounded, they can be “daisy-
chained” connected, using a single COM point on each
drive. Note that this drive COM “bus” should only tie to
earth ground at only one point.
2.8.1 Grounding Sensitive Circuits
It is critical to control the paths through which high
frequency ground currents flow. Sensitive circuits
should not share a path with such currents. Control
and signal conductors should not be run near or
parallel to power conductors.
2.8.2 Motor Cable Grounding
The ground conductor of the motor cable (drive end)
must be connected to the power ground stud
provided near the U, V and W output to motor
terminals. Grounding directly to drive provides a direct
path for high frequency current returning from the
motor frame and ground conductor. At the motor end,
the ground conductor should also be connected to the
motor case ground. See Figure 2-3.
If armored or shielded cables are used, the
armor/shield should be grounded at both ends per
figure 2-3.

2-6 INSTALLATION AND WIRING
2.8.3 Control Logic and Signal Grounding
The control logic and signal wiring for the PHOENIX
Drive is shown in Figure 2-4. If the control wires are
short, and contained within a cabinet that has no
sensitive circuits, the use of shielded control wiring is
not necessary. For all configurations, it is strongly
suggested that shielded wire be used for the signal
wiring.
It is generally recommended that the drive control
board signal common (COM) be connected to true
earth ground at one point in a single or multi-drive
system. For this case, a single #16AWG wire should
be connected from one COM terminal on the control
board to a single point outside of the drive enclosure.
With this ground connection in place, shields from
incoming signal cables may be grounded at the control
board terminal block COM terminals. The remote end
of the shielded signal cables should be taped off with
no connection to earth ground.
CAUTION
Floating Signal Common
If the signal common (COM) on the drive control board
is to be left floating (not connected to earth ground),
the shields should be grounded only at the remote
end. At the drive end, the shields should be taped off.
For the case of a floating signal common on the drive
control board, signal shields for external cables routed
to the drive control board terminal blocks must not be
connected to any of the COM terminals. This is so
high frequency ground currents will not be injected into
the control board signal common with no low
impedance path to ground.

Figure 2-3
Recommended Power Wiring
INSTALLATION AND WIRING 2-7
J:\...power

2-8 INSTALLATION AND WIRING
2.9 Power Cabling
Input and Output power connections are made through the power terminal block and power ground stud. The
actual drive label markings are shown in Table 2-1. Maximum torque values for terminal connections are also
indicated on labels next to the connection points.
Table 2-1
Power Signal Description
Terminal Description
GND Power Earth Ground Stud
L1 L2 L3
AC LINE INPUT AC Line Input Terminals
DC- DC+ DC Bus Terminals
U V W
OUTPUT TO MOTOR Motor Connection
2.9.1 Lug Kits
Tables 2-2a. through 2-2c. details the Lug kits that are available for the PHOENIX Drives to aid in making power
terminations. When ordering note that the kits are grouped according to voltage classes.
Table 2-2a.
Lug Kits for Class 200 Drive Models
VOLTAGE RANGE 200-250VAC (-10% to +10%)
Frame
Designation
Drive
Part Number
Motor HP
Continuous
Output Current
(Amps)
Lug Kit
Part number
CT VT CT VT
SIZE 1
0200-0010-N1
7.5
10
22
28
NOT REQUIRED
0200-0015-N1 10 15 28 42 NOT REQUIRED
0200-0020-N1 15 20 42 54 NOT REQUIRED
0200-0025-N1 20 25 54 68 NOT REQUIRED
0200-0030-N1 25 30 68 85 NOT REQUIRED
0200-0030CT-N1 30 - 80 - NOT REQUIRED
SIZE 2 0200-0040-N1 30 40 80 104 LUG-2
0200-0050-N1 40 50 104 130 LUG-2
0200-0060-N1 50 60 130 163 LUG-2
0200-0075-N1 60 75 145 192 LUG-2
0200-0100-N1 75 100 192 248 LUG-2
0200-0100CT-N1 100 - 248 - LUG-2
SIZE 3 0200-0125VT-N1 - 125 - 312 LUG-3
0200-0125CT-N1 125 - 312 - LUG-3
0200-0150VT-N1 - 150 - 360 LUG-3
0200-0150CT-N1 150 - 360 - LUG-3
0200-0200VT-N1 - 200 - 480 LUG-3
0200-0200CT-N1 200 - 480 - LUG-3
0200-0250VT-N1 - 250 - 602 LUG-3
0200-0250CT-N1 250 - 602 - LUG-3
1 Consult factory
Table of contents
Popular DC Drive manuals by other brands

HNC Electric
HNC Electric HV610 Series user manual

Control Techniques
Control Techniques Unidrive Servo Series Product data

Aerotech
Aerotech Soloist HPe 10 Hardware manual

Moog
Moog MSD Servo Drive Series Device Help

Becker
Becker R8/17PRF+ operating instructions

Lincoln Electric
Lincoln Electric MAXsa 29 Operator's manual