C-00409 USLR-XLT
Manual (2-14-20)
Copyright © 2020 Utility Solutions, Inc.
Operation Manual
LOAD-RANGER® XLT Load Break Tool
USLR-XLT-1 Up To 27 kV Load Break Tool
USLR-XLT-2 27 kV - 38 kV Load Break Tool
Available Options:
H - Hard Case
S - Soft Case
E - Extended Hood
P - Pad Mount
NC - No Counter
The LOAD-RANGER® XLT Portable Load Break Tool is designed to be used on
“hook equipped” disconnects, cutouts, switches and power fuses up to 34.5 kV and
150 BIL or less.
The LOAD-RANGER® XLT Portable Load Break Tool can safely:
• break associated cable charging currents, line charging currents, and
transformer magnetizing currents providing the transformers carry greater than
5% load
• switch magnetizing current of ungrounded primary transformers providing the
transformers carry greater than 5% load
• operate switches and fuses in metal enclosures and switchgear such as
pad-mounted gear up to 25kV. It is recommended that the tool is tted with
an optional insulated extension hood (-E version), or a Pad-Mount option is
available with an extended hood and a low prole mounting arm (-P version)
• switch single capacitor banks found on distribution systems
Applications
Catalog
Number
Capacitor
Bank Rating
kVAC
Three-Phase
Nominal System
Voltage
Three-Phase (kV)
Capacitor Bank Connection System
USLR-XLT-1 1800 Up to 14.4 Grounded Wye Connected Grounded System
USLR-XLT-1 2400 Up to 16 Grounded Wye Connected Grounded System
USLR-XLT-1 3000 Up to 23.9 Grounded Wye Connected Grounded System
USLR-XLT-1 3600 Up to 26 Grounded Wye Connected Grounded System
USLR-XLT-1 1800 Up to 14.4 Ungrounded Wye Connected Grounded System
USLR-XLT-1 2400 Up to 16 Ungrounded Wye Connected Grounded System
USLR-XLT-1 1800 Up to 14.4 Ungrounded Wye Connected Ungrounded System
USLR-XLT-1 2400 Up to 16 Ungrounded Wye Connected Ungrounded System
USLR-XLT-2 3000 Up to 23.9 Grounded Wye Connected Grounded System
USLR-XLT-2 3600 Up to 27.6 Grounded Wye Connected Grounded System
USLR-XLT-2 4800 Up to 34.5 Grounded Wye Connected Grounded System
USLR-XLT-2 3000 Up to 23.9 Ungrounded Wye Connected Grounded System
USLR-XLT-2 3600 Up to 27.6 Ungrounded Wye Connected Grounded System
USLR-XLT-2 3000 Up to 23.9 Ungrounded Wye Connected Ungrounded System
USLR-XLT-2 3600 Up to 27.6 Ungrounded Wye Connected Ungrounded System
Single bank capacitors only. Do not use LOAD-RANGER® XLT Portable Load
Break Tools for switching back-to-back / parallel capacitor banks.
Capacitor Ratings
The nature of any single pole switching on distribution circuits
has the potential for excessive voltages due to a variety of
factors, such as KVA, loading and transformer connections.
For applications on ungrounded primaries or single phase
units connected in a delta conguration above 21.96kV, any
single pole switching should only be performed if each phase is
carrying at least 5% load; or if the primary neutral is grounded
during switching operations. The primary neutral shall also be
grounded prior to any single pole switching of lightly loaded
banks rated 150kVA or less (3PH) or 50KVA or less (1PH) at
voltages above 21.96kV.
Single-Pole Switching
Safety Procedures
Do not use this tool on applications where the maximum
system voltage exceeds the maximum design voltage rating
of the tool. Likewise, do not use a tool that is “over-rated” for
the application. The XLT-2 model should NOT be used inside
padgear or cabinets.
Acquaint yourself with all operational features prior to use. It is
also recommended that the user practice using the tool on un-
energized equipment to gain familiarity with proper operation.
! !
DANGER
Contact with high voltage will cause death or grievous personal
injury to the operator. Only use this device in conjunction with
safe operating practices around energized lines and equipment.
! !
WARNING
Carefully read and fully understand this manual prior to
operating, maintaining or testing this device. Improper
operation, handling or maintenance of this device can result
in death, grievous personal injury and or equipment damage.
! !
WARNING
Only trained and qualied personnel should operate, inspect and
maintain this device.