Utility Solutions XFMR-4BUSHING User manual

Phone (828)323-8914
Fax (828)323-8410
Email [email protected]
Web www.utilitysolutionsinc.com
101 33rd Street Drive SE · Hickory, NC 28602
Load-Trainer
Transformer Simulator
XFMR-4BUSHING Four Bushing Transformer Simulator
C-00847 XFMR-4BUSHING
(5-25-16)
Operation Manual
Product Description 2
Components 3
Set-Up 4
Simulator Description 4
Front Panel Description 5
Toggle Switches 6
Operation 8
Examples 8
Vector Application 19
Transformer Backfeed 19
Parallel Phases 19
Polarity 19
Polarity Example 20
Warranty 20
CONTENTS
Copyright © 2016 Utility Solutions, Inc.

2
C-00847 XFMR-4BUSHING
(5-25-16)
Product Description
The LOAD-TRAINER Transformer Simulator is a fully functional electrical trainer allowing simulation
of most distribution transformer connection schemes. This device contains actual transformers that
completely duplicate in-eld situations.
The power unit’s components are not rated for continuous duty and may heat up during prolonged
use.
The power unit should not be on for extended periods of time and should only be on when
taking voltage readings.
In addition to reduce the risk of electrical shocks, re, etc.:
• Do not remove screws, covers or cabinet. Refer servicing to qualied
personnel.
• Do not expose this device to rain, moisture or combustible materials.
• Select a place that is level, dry and between 41°F and 95°F. Do not place either
unit on a heat generating object.
• Avoid a dusty place or a place subject to vibrations.
• The power cord supplied is congured and rated for standard 120 Volt,
10 Amp receptacles. It is to be used as a disconnect for this device by
unplugging the power cord from the receptacle.
! !
WARNING
Carefully read and fully understand this manual prior to
operating, maintaining or testing this device. Improper
operation, handling or maintenance of this device can result
in death, grievous personal injury and or equipment damage.
! !
WARNING
is unit can exceed 400 volts in certain congurations. Use caution
and treat ALL components and jumpers as if handling live conductors.
! !
WARNING
e unit should NOT be running during hook-up or conguration.

3
C-00847 XFMR-4BUSHING
(5-25-16)
Components
Product Line
XFMR-3BUSHING LOAD-TRAINER THREE BUSHING TRANSFORMER SIMULATOR
XFMR-4BUSHING LOAD-TRAINER FOUR BUSHING TRANSFORMER SIMULATOR
XFMR-PRM PHASE ROTATION METER
XFMR-LEADS ASSORTMENT OF EXTRA BANANA LEADS
XFMR-3BUSHING-PRL ADDITIONAL THREE BUSHING FRONT PANEL
XFMR-4BUSHING-PRL ADDITIONAL FOUR BUSHING FRONT PANEL
Front PanelPower Supply
Multiple-conductor
Cord
Shipping Cases
Power Cord
Patch Cords
Qty Description
1 Front Panel (Large Shipping Case)
1 Power Supply (Small Shipping Case)
1 Multiple-conductor cord with polarized plug (Green)
1 120 Volt, AC Power Cord (Black)
812” red ‘pin’ patch cords
312” black ‘pin’ patch cords
44” black ‘banana’ patch cords
512” red ‘banana’ patch cords
512” black ‘banana’ patch cords

4
C-00847 XFMR-4BUSHING
(5-25-16)
Simulator Description
Simulation of Three-Phase power is created by an electric motor and a 120-to-20 Volt transformer.
The motor is coupled to an alternator that provides a three-phase, four-wire output. The 20 Volt output
of the transformer is rectied and used to excite the rotor of the alternator. A rheostat on the Front
Panel provides ne tuning over the output of the alternator. When the rheostat knob is pointed toward
the word ‘DELTA’ the output voltage of the alternator is approximately seven (7) Volts phase-to-phase
(VPP). When the knob points to ‘WYE’ the output voltage is approximately seven (7) Volts phase-to-
neutral (VPN). See Equation below.
WYE = VPP = √3 • VPN = DELTA
Hence: WYE = VPP = √3 • 7 Volts
WYE = VPP ≈ 12 Volts
It is for this reason that a Delta connected primary wired to a WYE system voltage can produce
secondary voltages much higher than expected. In addition it may be necessary to ne-tune the
rheostat occasionally to obtain the desired voltage output from the transformers.
Set-Up
The Load-Trainer requires two components to operate; the Front Panel (located in
the large shipping case) and the Power Supply (located in the small shipping case).
The Front Panel may be removed from its shipping case and set on a desk or table
using the built-in easel. The Power Supply remains in its shipping case and will be
connected both to the Front Panel and to an electrical wall outlet.
Check that the protective panel on the power supply is in place and the screws are
securely fastened. This Power Supply case should be clear of all other items and
lying at on a level surface with the lid off for adequate ventilation.
PLEASE NOTE - The 120 volts are REAL and NOT simulated. You must use
caution whenever the unit is on. Never leave the unit on while unattended!
The unit should be on when measuring voltages and NEVER while removing
or installing patch cords. Components could OVERHEAT if left on for
extended periods a time!
1. Verify the “ON-OFF” switch on the Front Panel is in the “OFF” position.
1. Connect the green Multiple-conductor Cord to the Front Panel on the lower left hand corner. Turn
the threaded collar on the plug clockwise a single turn to secure it to the polarized receptacle.
2. Attach the black Power Cord to the Power Supply using the female end. Plug in the Power Cord to
a grounded AC outlet.
! !
WARNING
Never leave the unit unattended while plugged in.
Always remove the black power cord when not in use.

5
C-00847 XFMR-4BUSHING
(5-25-16)
Front Panel Description
Three Phase Power System
The four lines at the top of the Front Panel represent a three-phase four-wire power system (A, B, C, N).
The tip jacks located on the lines are connected to buss bars within the panel and are protected by fast
acting thermal circuit breakers and disconnecting switches. The tip jacks are used to make connections
from the three-phase four-wire power system supply to the primaries of single-phase transformers.
Indicator Lights
An indicator light is to the right of each three-phase power line at the top of the Front Panel. This light
will indicate when the line is energized.
Disconnecting Switches
Each three-phase power line has a toggle switch to the right of the indicator light on the Front Panel.
Power can be controlled to each line separately.
Circuit Breakers
Fast acting thermal circuit breakers are included on each of the three-phase power lines at the top of
the Front Panel and function as fuses for accurate simulations. Simply press the circuit breaker to reset.
Transformer Inputs
Three transformer outlines in the middle of the Front Panel use red input terminals (H1 and H2) which
connect to actual transformers located behind the panel. These connections are made using the Pin
Patch Cords (small metal ends). The plugs can be stacked, if desired.
Transformer Outputs
Each transformer has four black unlabeled output terminals. They can be thought of as X1, X2, X3 and
X4 from right to left respectively.
Load Lines
The lines at the bottom of the Front Panel represent load lines (N, L1, L2, L3). Connections between the
transformer output terminals and the load lines are made using the Banana Patch Cords (large metal
ends). These can be stacked if desired.
AC Meter
An AC meter is on the lower right of the Front Panel and is used to measure the transformer’s output.
Tip jacks utilize Banana Patch Cords connected through the load lines or directly to a transformer.
Delta - Wye Rheostat Knob
A rheostat on the Front Panel provides ne tuning over the output of the alternator. It may be necessary
to ne-tune the rheostat to obtain the desired voltage output from the transformers. During Delta
conguration, the knob should be pointed to the left; while in Wye congurations the knob should be
pointing to the right. See Simulator Description for more information.

6
C-00847 XFMR-4BUSHING
(5-25-16)
The eight (8) Toggle Switches located on the left side of the Front Panel can be used by instructors to
simulate real-world scenarios that a student would have to diagnose.
The switches are labeled S1 through S8. The normal position of all switches is UP, toward the top of the unit.
Toggle Switches
Switch Description Transformer TOGGLE POSITION
UP MIDDLE DOWN
S1 Phase Paralleling Switch A-B-C B-B-C*
S2 A-B-C A-B-B*
S3 Secondary Transformer
Switch 1Closed
(secondary)
Open
(secondary)
Open
(secondary)
S4 Polarity & Primary
Transformer Switch 1Additive Open
(primary) Subtractive
S5 Secondary Transformer
Switch 2Closed
(secondary)
Open
(secondary)
Open
(secondary)
S6 Polarity & Primary
Transformer Switch 2Additive Open
(primary) Subtractive
S7 Secondary Transformer
Switch 3Closed
(secondary)
Open
(secondary)
Open
(secondary)
S8 Polarity & Primary
Transformer Switch 3 Additive Open
(primary) Subtractive
*when both S1 & S2 are down phasing is B-B-B
Polarity & Primary
Switches
(S4/S6/S8)
Secondary
Switches
(S3/S5/S7)
H1H2
MIDDLE
H1H2
H1H2
MIDDLE
H1H2
DOWN
UP
H1H2
Note: The Load-Trainer uses instrument transformers to simulate
distribution transformers and are therefore SUBTRACTIVE.
UP
(additive) DOWN
(subtractive)
H1H2
X4X3X2X1X1X2X3X4
X4X3X2X1
X4X3X2X1X4X3X2X1X4X3X2X1

7
C-00847 XFMR-4BUSHING
(5-25-16)
Front Panel
Top of Unit
UP - ABC
DN - BBC
Transformer #1
UP – Closed (secondary)
CTR - Open (secondary)
DN – Open (secondary)
Transformer #2
UP – Closed (secondary)
CTR - Open (secondary)
DN – Open (secondary)
Transformer #3
UP – Closed (secondary)
CTR - Open (secondary)
DN – Open (secondary)
UP - ABC
DN - ABB
(S1 & S2 Both DN - BBB)
Transformer #1
UP - Additive Polarity
CTR - Open (primary)
DN - Subtractive Polarity
Transformer #2
UP - Additive Polarity
CTR - Open (primary)
DN - Subtractive Polarity
Transformer #3
UP - Additive Polarity
CTR - Open (primary)
DN - Subtractive Polarity
Normal position of all switches is UP, toward the top of the unit.
Left Side of Front Panel
FIGURE 1: Toggle Switches
S2 S4 S6 S8
S1 S3 S5 S7

8
C-00847 XFMR-4BUSHING
(5-25-16)
Operation
The Load-Trainer Transformer Simulator has the capability to connect single-phase and the following
types of three-phase transformers:
Simple Single-Phase Transformer Connections
1. The system should be OFF and remain OFF except for observing voltage measurements on the AC
meter for short periods of time.
2. Be sure all 8 Toggle Switches are in the UP position for normal operation. Be sure all 3 Disconnecting
Switches are ‘ON’ and reset any tripped Circuit Breakers.
3. Using the red ‘pin’ tip patch cords connect a single-phase transformer to a DELTA system primary
as shown in Example 1.
4. Set rheostat pointer to ‘DELTA’.
5. Make output connections with the red and black banana patch cords bringing leads down to load
lines to a 120 Volt WYE secondary as shown in Example 1.
6. Turn the unit ON. The Power Supply will start and deliver the proper voltage to the transformer.
NOTE: The power unit should not be operated for extended periods of time. Run only when
taking voltage readings.
7. If connections have been properly made voltage should appear on the AC Meter. These readings
should be near normal for the transformer bank being made. Use the rheostat to make minor
adjustments.
8. Problems can be introduced after the installation has been shown to operate correctly. This is
done by the toggle switches on the left side of the Front Panel (see Figure 1) and at the instructors
discretion to simulate real world scenarios.
NOTE:
In certain congurations the actual measured device output voltage is greater than or less than the
expected voltage for a given simulation. The AC Meter has been scaled at the factory to compensate for
the differing output voltages. An independent meter device may display voltages that are not expected.
Delta-Delta
Delta-Wye
Open Delta-Open Delta
Wye-Delta
Wye-Wye
Wye (one leg out)-Open Delta
Examples
The following table summarizes the Connection Diagrams provided on the following pages:
Example Simulation
1 Single Phase Transformer w/ Delta Primary & 120 Volt Wye Secondary
2 Single Phase Transformer w/ Delta Primary & 120 Volt Delta Secondary
3 Single Phase Transformer w/ Delta Primary & 120/ 240 Volt Delta Secondary
4 Three Phase Transformer w/ Delta Primary & 120 / 208 Volt Wye Secondary
5 Three Phase Transformer w/ Delta Primary & 120 Volt Delta Secondary
6 Three Phase Transformer w/ Delta Primary & 120 / 240 Volt High Leg B Delta Secondary
7 Three Phase Transformer w/ Open Delta Primary & 120 Volt Open Delta Secondary
8 Three Phase Transformer w/ Wye Primary & 120 Volt Delta Secondary
9 Three Phase Transformer w/ Wye Primary & 120 / 208 Volt Wye Secondary
10 Three Phase Transformer w/ Wye (One Leg Out) & 120 Volt Open Delta Secondary

9
C-00847 XFMR-4BUSHING
(5-25-16)
Single Phase Transformer with Delta Primary
and 120 Volt Wye Secondary
Example 1
Toggle Switches: All in the UP Position
Rheostat Knob: Delta
Expected Meter Reading
Phase to Ground: 120 volts
Phase to Phase: 0 volts (not shown)
S2 S4 S6 S8
S1 S3 S5 S7

10
C-00847 XFMR-4BUSHING
(5-25-16)
Single Phase Transformer with Delta Primary
and 120 Volt Delta Secondary
Example 2
Toggle Switches: All in the UP Position
Rheostat Knob: Delta
Expected Meter Reading
Phase to Ground: 0 volts (not shown)
Phase to Phase: 120 volts
S2 S4 S6 S8
S1 S3 S5 S7

11
C-00847 XFMR-4BUSHING
(5-25-16)
Single Phase Transformer with Delta Primary
and 120/240 Volt Delta Secondary
Example 3
Toggle Switches: All in the UP Position
Rheostat Knob: Delta
Expected Meter Reading
Phase to Ground: 120 volts (not shown)
Phase to Phase: 240 volts
S2 S4 S6 S8
S1 S3 S5 S7

12
C-00847 XFMR-4BUSHING
(5-25-16)
Three Phase Transformer with Delta Primary
and 120/208 Volt Wye Secondary
Example 4
Toggle Switches: All in the UP Position
Rheostat Knob: Delta
Expected Meter Reading
Phase to Ground: 120 volts (not shown)
Phase to Phase: 208 volts
S2 S4 S6 S8
S1 S3 S5 S7

13
C-00847 XFMR-4BUSHING
(5-25-16)
Three Phase Transformer with Delta Primary
and 120 Volt Delta Secondary
Example 5
Toggle Switches: All in the UP Position
Rheostat Knob: Delta
Expected Meter Reading
Phase to Ground: 0 volts (not shown)
Phase to Phase: 120 volts
S2 S4 S6 S8
S1 S3 S5 S7

14
C-00847 XFMR-4BUSHING
(5-25-16)
Three Phase Transformer with Delta Primary
and 120/240 Volt High Leg B Delta Secondary
Example 6
Toggle Switches: All in the UP Position
Rheostat Knob: Delta
Expected Meter Reading
Phase to Ground: L1120 volts (shown) / L2208 volts / L3120 volts
Phase to Phase: 240 volts
S2 S4 S6 S8
S1 S3 S5 S7

15
C-00847 XFMR-4BUSHING
(5-25-16)
Three Phase Transformer with Open Delta Primary
and 120 Volt Open Delta Secondary
Example 7
Toggle Switches: All in the UP Position
Rheostat Knob: Delta
Expected Meter Reading
Phase to Ground: 0 volts (not shown)
Phase to Phase: 120 volts
S2 S4 S6 S8
S1 S3 S5 S7

16
C-00847 XFMR-4BUSHING
(5-25-16)
Three Phase Transformer with Wye Primary
and 120 Volt Delta Secondary
Example 8
Toggle Switches: All in the UP Position
Rheostat Knob: Wye
Expected Meter Reading
Phase to Ground: 0 volts (not shown)
Phase to Phase: 120 volts
S2 S4 S6 S8
S1 S3 S5 S7

17
C-00847 XFMR-4BUSHING
(5-25-16)
Three Phase Transformer with Wye Primary
and 120/208 Volt Wye Secondary
Example 9
Toggle Switches: All in the UP Position
Rheostat Knob: Wye
Expected Meter Reading
Phase to Ground: 120 volts (not shown)
Phase to Phase: 208 volts
S2 S4 S6 S8
S1 S3 S5 S7

18
C-00847 XFMR-4BUSHING
(5-25-16)
Three Phase Transformer with Wye (One Leg Out) Primary
and 240 Volt Open Delta Secondary
Example 10
Toggle Switches: All in the UP Position
Rheostat Knob: Wye
Expected Meter Reading
Phase to Ground: 0 volts (not shown)
Phase to Phase: 240 volts
S2 S4 S6 S8
S1 S3 S5 S7

19
C-00847 XFMR-4BUSHING
(5-25-16)
Vector Application to Transformer Connections
One feature of the Load-Trainer Transformer Simulator is the vector application to transformer
connections. This unit can be used to teach transformer connections using the vector concept. If
desired, the instructor should apply his own arrows as follows: the vector arrows between the H1 and H2
terminals should be xed in position pointing left (from H2 to H1). Vectors representing the secondary
windings can be attached to the front of the panel pointing right and can be reversed to indicate a
change in polarity. Switches #4, 6 and 8 are used to change polarity of the secondary windings. Refer
to “Toggle Switches” on page 6 for more information about changing polarity.
Transformer Backfeed
Numerous situations can be duplicated to produce a transformer backfeed. An example is the lack of
grounding on a Wye-Delta bank. To simulate transformer backfeed connect a Wye-Delta bank (see
Example 8) with the H2 terminals of each transformer connected to each other but oating. Run the unit
to show proper operation. Open one of the Disconnecting Switches located on the Front Panel to the
‘OFF’ position. The indicator light will go off. Repeat this procedure with the H2 terminals grounded. In
this case the open phase will glow indicating a backfeed.
Parallel Phases
Parallel phases can also be simulated on the Load-Trainer Transformer Simulator. It is quite possible
for a bank connected Wye (one leg out)-Open Delta (see Example 10) to become energized from
the same phase. In most instances a jumper on a vertical corner burning into and falling down on the
phase below has caused this. If the bank is connected between these phases this results in the input
windings being in parallel and the output windings still connected in series. Using normal procedures
this produces a situation that is difcult to troubleshoot. This situation can be duplicated with the use
of toggle switches #1 or #2 or both (see Simulator Description). Do not measure voltages on the
system supply phases. It would be rare for a trouble-shooter to have the equipment to measure the
phase voltage.
Polarity
When single-phase transformers are connected together to make a three-phase transformer bank, the
EMF (electromotive force) will effect the systems Polarity. The direction of both the high and low voltage
coil windings of a transformer and the numbering of it’s corresponding leads will determine if polarity is
additive or subtractive. A physical phenomenon caused by the magnetomotive forces in a transformer’s
core and coil becomes evident when the low voltage windings are reversed.
Let’s use a single-phase transformer as an example. If the direction of the high voltage windings (H1-H2)
are the same as the low voltage windings (X1-X4), the load currents in the primary and secondary are
opposed. This is called Subtractive Polarity. Conversely, if the secondary windings of the transformer
are reversed (X4-X1) and going in the opposite direction of the high voltage windings, then the load
currents would be the same. This is called Additive Polarity. See Figure 2.
Vector Application

20
C-00847 XFMR-4BUSHING
(5-25-16)
Polarity Example
A practical example of additive and subtractive polarity can be demonstrated in a Delta-Delta transformer
(see Example 5). Set up the transformer connections as illustrated and measure voltage across L1 and
L2. Move the position of the Additive/Subtractive switch #4 from Up to Down and observe the voltmeter
and the lamps on the system voltage lines A, B, and C. What happened? Turn off power. The voltmeter
drops to zero and the lamps on phase A and B glow very dimly.
Now reverse the leads on X1 and X2 for transformer #1 only, turn on the power and observe the
voltmeter. What happens? Turn off power. The voltage is restored and the lamps glow normally. This
is caused by a backfed EMF (electromotive force) induced across both A and B phases and L1 and L2
from the other two transformers (#2 and #3).
Now lets try another example. Conrm all switches are up, connections are made properly according
to Example 5 and measure voltage across L1 and L2. This time change the position of two Additive/
Subtractive switches #6 and 8 from Up to Down simultaneously. What happens? Why? Turn off power.
The results are the same as if we changed only switch #4. The reason is the same.
Now without doing anything else move switch #4 from Up to Down. Turn on the power and observe
the voltmeter. What happens? It would appear as if everything is back to “Normal.” Why, because the
electromotive force of all three single-phase transformers are going in the same direction. The direction
of the EMF is the same for all transformers, but opposite from the original conguration. This would
need to be corrected in the real world or else three-phase motors would rotate in the opposite direction
and customers would not be happy.
A more detailed discussion of Polarity is beyond the scope of this manual.
Warranty
Utility Solutions, Inc. warrants the Load-Trainer for any defects in manufacturing for the period of one
year. If the tool is returned within that time period, Utility Solutions, Inc. will replace or repair the tool
free of charge.
Additive Polarity Subtractive Polarity
Figure 2
H1H2
X3X2X1
X4
H1H2
X2X3X4
X1
Table of contents
Other Utility Solutions Transmitter manuals
Popular Transmitter manuals by other brands

Electronic Broadcast Equipment
Electronic Broadcast Equipment SIRIO 2000T User and maintenance manual

ABB
ABB TB82PH operating instructions

Vega
Vega VEGABAR 82 operating instructions

AUTEC
AUTEC Dynamic Series Original instructions

CAMDEN
CAMDEN Lazerpoint CM-TXLF Series installation instructions

Sunx
Sunx M-DW1 instruction manual