Wiring Diagram:
1.DO NOT MATE CONNECTOR UNTIL INSTALLATION IS
COMPLETE AND AC POWER IS SUPPLIED.
2.TEST ACCESSORY LEADS-OBSERVE PROPER
POLARITY WIRING.
UL Listed
For field or factory installation
Specifications:
Dimensions
15''x2.17''x1.3''(382mmx55mmx32mm)
17.7''(450mm) Flexible Conduit
Temperature Rating (Ambient)
0°C to +50°C (32°F to 122°F)
Recharge Time
≥24Hours
Battery Charging Current
250mA
Battery
Li-ion battery -14.8V 3300mAh
Test Switch/Charging Indicator Light
Low Voltage,illuminated Test Switch
Full Warranty
5 Years
Illumination Time
≥90 Minutes
Output Power
25W max.
Output Current and Voltage
520-1000mA ,25V-48V DC
AC Input Power Rating
5.5W max.
AC Input Current
100mA max.
Universal Input Voltage
100-277Vac,50/60Hz
Dimensions:
Case-15''X2.24''X1.3''(mounting center-14.4'')
15''
2.24''
1.3''
1.65''
14.4''
382mm
55mm
365.7mm
42mm
32.2mm
WALL SWITCH
BLACK
WHITE
LED DRIVER
Driver +
Driver -
WHITE
BLACK
Battery Wiring
EMERGENCY
LED DRIVER LED+(PURPLE)
LED-(BROWN)
AC-L
AC-N
with Connector
E511841
RoHS
BC
Features:
Meet most of safety standards for lighting
Battery protections over charge protection over
discharge protection short circuit protection
: 、
、
Internal Li-ion battery
The batteries Meet 500 cycles of standard CH and
standard DCH
Intelligent emergency automatic detection function
RoHS compliant
Indicator shows a variety working modes
Constant output power(Auto-sensing output within each range)
Standard CSA C22.2 NO.141 UL924、
Emergency LED Driver
25 Watts Constant Output Power
EMI-2G-25W
BROWN
BLUE
Test Plate
White
White
LED ARRAY
IMPORTANT SAFEGUARDS
The EMI-2G-25W emergency driver can be used with most LED loads that have a rated
voltage of 25-48Vdc.These emergency driver have been evaluated to and found compliant to UL 924.The
emergency pack assembly is accepted as a component of a luminaire where the suitability of the
combination shall be determined by UL or Authorities.The as-installed performance of
the system must meet or exceed all Federal,State,and Local code requirements.
Do not connect battery pack connector until all other wiring is complete and AC power is on.
Do not mount near gas or electric heaters.
Do not let power supply cords touch hot surfaces.
This LED Emergency Backup unit requires an un-switched AC power source of 100-277Vac,50/60Hz The
AC driver must be on the same branch circuit as the LED Emergency Backup unit.
Do not use outdoors.
To prevent electrical shock only mate unit connector after installation is complete and before the
AC power to the fixture is back on.
The electrical rating of this product is 100-277Vac.Installer must confirm that there is 100-277Vac to the
fixture before installation.
Before installing,make certain the AC power to the fixture is off.
Risk of fire or electric shock.This LED Emergency Backup installation requires knowledge of luminaire.
electrical systems.If not qualified,do not attempt installation.Contact a qualified electrician.
Risk of fire or electric shock.Luminaire wiring and electrical parts may be damaged when drilling for
installation of LED Emergency Backup.Check for enclosed wiring and components.
Applications
Operation
When using electrical equipment, basic safety precautions should always be followed including
the following:
Equipment should be mounted in locations and at heights where it is not be subjected to tampering by
unauthorized personnel.
The use of accessory equipment is not recommended by the manufacturer and may cause an unsafe condition.
Do not use this equipment for other than its intended use.
Use with grounded, UL Listed, dry or damp location rated fixtures.
SAVE THESE INSTRUCTIONS
AC Operation:
AC power is present, The LED load from the LED driver is normal power supply, AC LED driver output current can not exceed
150W or 4A,the emergency driver is charging in a standby mode. The green LED light flashes indicates that it is charging. The
green LED light on indicates that it is full charged. After the AC power supply working 48h,The emergency LED drive will
automatically from AC power working switch into emergency working mode for 30s every month and then automatically backs to
the working mode of the AC power supply, the AC power supply works per year for automatically from the AC power mode backs
to the working emergency mode Until the emergency discharge is completed.
Emergency operation:
When the AC power goes out ,The emergency driver detects the AC power outage and automatically switch to the working
emergency mode. The red LED light on indicates that it is discharging, the red LED flashes to indicate low battery power. The red
LED light off indicates that the discharge is complete. When the AC power is restored, The emergency driver backs to AC power
working and starts recharging.
Malfunction operation:
When the emergency LED driver fault, the yellow LED on.
Emergency LED Driver
25 Watts Constant Output Power
EMI-2G-25W
READ AND FOLLOW ALL SAFETY INSTRUCTIONS

Popular Lighting Equipment manuals by other brands

LUTEC 7635402012 owner's manual

LUTEC

LUTEC 7635402012 owner's manual

Bionizer BioDoser Instruction book

Bionizer

Bionizer BioDoser Instruction book

LED's light 190010 manual

LED's light

LED's light 190010 manual

SOLAR VISION TX300 installation manual

SOLAR VISION

SOLAR VISION TX300 installation manual

roblight FL 1500 XT user manual

roblight

roblight FL 1500 XT user manual

HAYA HYP008F user manual

HAYA

HAYA HYP008F user manual

Lightolier Armstrong F7000-17 product manual

Lightolier

Lightolier Armstrong F7000-17 product manual

Steren LAM-225 instruction manual

Steren

Steren LAM-225 instruction manual

MULTIQUIP GloBug GB113BC Operation and parts manual

MULTIQUIP

MULTIQUIP GloBug GB113BC Operation and parts manual

Altman SS-STRIP series Specifications

Altman

Altman SS-STRIP series Specifications

Bowens ESTIME 3000 Operating instrctions

Bowens

Bowens ESTIME 3000 Operating instrctions

Techni-Lux DL-PAR46RGB/B manual

Techni-Lux

Techni-Lux DL-PAR46RGB/B manual

Viabizzuno catena Installing instructions

Viabizzuno

Viabizzuno catena Installing instructions

PXM PX392 PxArt+ 18 manual

PXM

PXM PX392 PxArt+ 18 manual

Blizzard Lighting Motif Sketch user manual

Blizzard Lighting

Blizzard Lighting Motif Sketch user manual

Chauvet SlimBANK TRI-18 user manual

Chauvet

Chauvet SlimBANK TRI-18 user manual

thomann PAR64 10MM UV user manual

thomann

thomann PAR64 10MM UV user manual

Chauvet CH-750 user guide

Chauvet

Chauvet CH-750 user guide

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.