UWT RN 3000 Series User manual

page
Level limit switch
Series RN 3000 / 6000
Technical information / Instruction manual
Page
Safety notes/ Technical support 2
---------------------------------------------------------------------------------------------------------
Introduction 3
---------------------------------------------------------------------------------------------------------
Function 4
---------------------------------------------------------------------------------------------------------
Technical data 6
---------------------------------------------------------------------------------------------------------
Approvals 14
---------------------------------------------------------------------------------------------------------
Options 15
---------------------------------------------------------------------------------------------------------
Mounting 16
---------------------------------------------------------------------------------------------------------
Electrical installation 20
---------------------------------------------------------------------------------------------------------
Signal and alarm output 25
---------------------------------------------------------------------------------------------------------
Setting/ Sensitivity 28
---------------------------------------------------------------------------------------------------------
Maintenance 29
--------------------------------------------------------------------------------------------------------
Notes for use in Hazardous Locations 30
---------------------------------------------------------------------------------------------------------
Disposal 32
Subject to technical change We assume no liability for typing errors.
All dimensions in mm (inches). Different variations than specied are possible.
Please contact our technical consultants.
Table of contents
RN 3000 / 6000 gi011016
1
Rotonivo®1
2
3
4
5
6
7
8
9
10
11
12

page
Level limit switch
Series RN 3000 / 6000
Technical information / Instruction manual
Safety notes / Technical support
Notes
• Installation, maintenance and commissioning may be accomplished only by qualied technical personnel.
• The product must be used only in the manner outlined in this instruction manual.
Special attention must be paid to warnings and notes as follows:
WARNING
Relates to a caution symbol on the product: A failure to observe the necessary
precautions can result in death, serious injury and/ or considerable material damage.
WARNING
Relates to a caution symbol on the product: Risk of electric shock
WARNING
A failure to observe the necessary precautions can result in death, serious injury
and/ or considerable material damage.
This symbol is used, when there is no corresponding caution symbol on the product.
CAUTION A failure to observe the necessary precautions can result in considerable material
damage.
Safety symbols
In manual and on
product
Description
CAUTION: refer to accompanying documents (manual) for details.
Earth (ground) Terminal
Protective Conductor Terminal
Technical support
Please contact your local supplier (for address see www.uwt.de). Otherwise you can contact:
UWT GmbH Tel.: 0049 (0)831 57123-0
Westendstr. 5 Fax: 0049 (0)831 76879
www.uwt.de
Rotonivo®
1
2
3
4
5
6
7
8
9
10
11
12
RN 3000 / 6000
gi011016
2
1
2
3
4
5
6
7
8
9
10
11
12

page
Level limit switch
Series RN 3000 / 6000
Technical information / Instruction manual
Introduction
The ROTONIVO is an electromechanical Level limit switch and
is used for level monitoring of bulk goods.
The units can be delivered with a wide range of Ex-approvals
for use in Hazardous Areas.
They can be equipped for process over- and lowpressure and
also for very high or low process temperatures.
Selected applications:
• building materials industry
lime, styrofoam, moulding sand, etc.
• food industry
milk powder, our, salt, etc.
• plastics industry
plastics granules etc.
• timber industry
• chemical industry
• mechanical engineering
The ROTONIVO is normally screwed into the lateral container
wall so that it is in level with the lling height to be registered and
monitored.
The device can also be mounted from the top of the container. In
this case an extension piece is used to mount the probe level with
the height to be registered.
The length of the probe can be up to 4 m (158") with an extension
tube or up to 10 m (394“) with an extension rope.
The use of a sliding sleeve for the version RN 3002/ RN 6002 is
recommended so that the switch point can be changed easily
during operation of the device.
RN 3002-rope
RN 6002-rope
optional
sliding
sleeve
RN 3004
RN 6004
RN 3003
RN 6003
Applications
RN 3002
RN 6002
RN 3001
RN 6001
RN 3001
RN 6001
with pendulum shaft
RN 3000 / 6000 gi011016
3
Rotonivo®1
2
3
4
5
6
7
8
9
10
11
12
1
2
3
4
5
6
7
8
9
10
11
12

page
Level limit switch
Series RN 3000 / 6000
Technical information / Instruction manual
Function
A measuring vane is driven by a synchronous motor. The
bearing of the motor inside the housing allows it to swing. The
motor is xed to a switching lug.
If the vane is uncovered, a spring pulls the motor and switching
lug to the left position (gure 1).
When material covers the vane and thus stops the rotation, the
motor and switching lug swings to the right position (gure 2).
The signal output indicates "covered" and the motor is stopped.
When the vane becomes uncovered due to falling material,
the spring pulls the motor and switching lug back to the left
position (gure 1). The motor is started and the signal output
indicates "uncovered".
Fail safe alarm
With the option fail safe alarm it is possible to recognize a fault of
the unit in time and to initiate an alarm relay. The following faults
are observed:
• Motor
• Gear
• Electronic for motor power supply
• Supply voltage failure
• Defect of the connecting wires
Functional safety SIL2 (IEC 61508)
With option Functional safety the unit observes the motor, gear
and electronic. The result of this diagnostics is present on the
signal output, which states the full/ empty condition.
Switchable signal output (Fail safe high/ low)
With version "Universal voltage", "PNP" and optional "AC" a
switchable signal output FSH/ FSL is integrated.
Signal output delay:
The version "Universal voltage" and "PNP" has an integrated
adjustable delay for the signal output.
Figure 1
Switch for
signal output
Switching
lug
Switch for
motor stop
Figure 2
Selection guide
RN 3001
RN 6001
RN 3001
RN 6001
pendulum shaft
RN 3002
RN 6002
RN 3002-rope
RN 6002-rope
RN 3003
RN 6003
RN 3004
RN 6004
Full detector xx* x x x x
Demand detector xx* x x
Empty detector xx* x x
Vertical mounting x x x x* x
Oblique from the top x x** x
Horizontal mounting x x x
Oblique from the bottom x x
* consider max. permitted mech. traction force
** only with option "bearing at tube end"
Rotonivo®
1
2
3
4
5
6
7
8
9
10
11
12
RN 3000 / 6000
gi011016
4

page
Level limit switch
Series RN 3000 / 6000
Technical information / Instruction manual
Application Sealing material (1) Metal Bearing
NBR FPM (Viton) PTFE
(Teon)
Aluminium Stainless steel (2)
1.4301/ SS 304
Stainless steel
Animal feed press x x x
Synthetic granules, powders x x
Salt x x x
Dust lter (temp. up to 392°F) x x
Dust lter (temp. up to 302°F) x x
Bitumen x x
Cement x x
Wood chip dryer x x
Pressure conveying vessel, 8bar x x
Sugar x x
Flour x x
Carbon black x x
Shaft sealing and metal material
(1) Delivered in version with process temperature and process pressure as following (see also option pos.17):
NBR: max. 80°C and max. 0.8 bar
FPM (Viton): max. 150°C and max. 0.8 bar
PTFE (Teon): max. 250°C and max. 0.8 bar
max. 80°C/ 150°C/ 250°C and max. 5 bar/ 10 bar
(2) In particular cases 1.4404 (SS316L) is recommended
Function
Electronic
RN 3000
Power supply
Output signal
SPDT (1) DPDT PNP FSH/
FSL(2)
Adjustable
delay
Fail safe
alarm
AC version 24 V or 48 V or 115 V or 230 V AC • - - - - -
DC version 24 V DC • - - - - -
DC version 24 V DC PNP - - • • • -
Universal
voltage 24 V DC/ 22 .. 230 V AC • - - • • option
RN 6000
Power supply
Output signal
SPST SPDT (1) DPDT PNP FSH/
FSL(2)
Adjustable
delay
Fail safe
alarm
AC version 24 V or 48 V or 115 V or 230 V AC - • - - - - -
DC version 24 V DC - • - - - - -
Universal
voltage 24 V DC/ 22 .. 230 V AC - - • (3) - • • option
Universal
voltage SIL2 24 V DC/ 22 .. 230 V AC • • (4) - - • • -
(1) Microswitch, with Universal voltage Relais
(2) Switchable signal output (Fail safe high/ low)
(3) For Ex approval "Increased safety" (pos.2 C,R,S) not in combination with option Fail safe alarm
(4) Additional output, not SIL conform
RN 3000 / 6000 gi011016
5
Rotonivo®1
2
3
4
5
6
7
8
9
10
11
12

page
Level limit switch
Series RN 3000 / 6000
Technical information / Instruction manual
Technical Data
Series RN 3000
Standard
Series RN 6000
Standard
Series RN 6000
de explosionproof with increased
safety terminal box
Series RN 6000
d ameproof/ explosionproof
Housing versions
Extensions
RN ..001
Thread/ ange Temperature
extended shaft
Process
temperature A
150°C (302°F) 200mm (7.87”)
250°C (482°F) 200mm (7.87”)
350°C (662°F) 30 0mm (11.8” )
600°C (1112°F ) 400mm (15.7”)
1.100°C (2012°F) 700mm (27.6”)
Triclamp
Dimensions
Rotonivo®
1
2
3
4
5
6
7
8
9
10
11
12
RN 3000 / 6000
gi011016
6

page
Level limit switch
Series RN 3000 / 6000
Technical information / Instruction manual
Technical Data
RN ..002
Without sealing
and bearing at
tube end (see also
option pos.32)
Thread/ Flange Temperature
extended shaft
RN ..002 rope
Type standard (pos.1 C)
(max. 4 kN load)
Type reinforced (pos.1 H)
(max. 28 kN load)
Thread/ Flange Thread/ Flange
Triclamp
Temperature
extended shaft
150/ 250°C
(302/ 482°F)
Temperature
extended shaft
350/ 600°C
(662/ 1,112°F)
Process
temperature A
150°C (302°F) 200 mm (7.87”)
250°C (482°F) 200 mm (7.87”)
350°C (662°F) 300 mm (11.8”)
600°C (1,112°F) 400 mm (15.7”)
1.100°C (2,012°F) 700 mm (27.6”)
RN 3000 / 6000 gi011016
7
Rotonivo®1
2
3
4
5
6
7
8
9
10
11
12

page
Level limit switch
Series RN 3000 / 6000
Technical information / Instruction manual
Technical Data
Process
temperature B
80°C (176°F)
0.8 bar (11.6 psi)
10 mm
(0.39”)
80°C (176°F)
5/ 10 bar (73/ 145 psi)
75 mm
(2.95”)
150/ 250°C
(302/ 482°F)
0.8/ 5/10 bar
(11.6/ 73/ 145 psi)
210 mm
(8.27”)
Material C
steel ø55 mm (ø2.17”)
aluminium ø60 mm (ø2.36”)
Vane D
50 mm x .. mm
(1.97” x ..”) 139 mm (5.47”)
98 mm x .. mm
(3.86” x ..”) 187 mm (7.36”)
Temperature
extended shaft
Temperature extended
shaft
Thread/ Flange Triclamp
Process
connection
Process
temperature A
150°C (302°F) 200 mm (7.87”)
250°C (482°F) 200 mm (7.87”)
350°C (662°F) 300 mm (11.8”)
600°C (1,112°F) 400 mm (15.7”)
Rotonivo®
1
2
3
4
5
6
7
8
9
10
11
12
RN 3000 / 6000
gi011016
8
RN 3005
RN ..004
RN ..003

page
Level limit switch
Series RN 3000 / 6000
Technical information / Instruction manual
Technical Data
Measuring vanes
code type a b
B
C
E
F
G
I
rectangular
rectangular
rectangular
rectangular
rectangular
rectangular
50 mm (1.97'')
50 mm (1.97'')
50 mm (1.97'')
98 mm (3.86'')
98 mm (3.86'')
98 mm (3.86'')
98 mm (3.86'')
150 mm (5.90')
250 mm (9.84'')
98 mm (3.86'')
150 mm (5.90'')
250 mm (9.84')
code B,C,E,F,G,I
rectangular vane code P
notched 40 x 80
code A
boot shaped vane 40 x 98
to lead in 1½“ socket
(length of socket
max. 40 mm (1.57”))
to lead in 1¼ “ socket
(length of socket
max. 40 mm (1.57”))
code D
boot shaped vane 35x106
to lead in 1“ or
M32 x 1.5 socket
(max. 40 mm (1.57”))
code M
rubber vane 98 x 250
Insertion of the hinged vane
through a long socket
spring
code S
hinged vane 98 x 100
single sided
code K
hinged vane 98 x 200 double
sided
code R
boot shaped vane 28 x 98
b=37 mm (1.46")
for 1½“/ 1¼“
b=28 mm (1.1")
for 1"/ M32 x 1.5
b=37 mm (1.46")
für 1½“/ 1¼“
b=28 mm (1.1")
for 1"/ M32 x 1.5
code J
boot shaped vane
26 x 77 to lead in M30
socket (max. 40
mm (1.57”))
RN 3000 / 6000 gi011016
9
Rotonivo®1
2
3
4
5
6
7
8
9
10
11
12

page
Level limit switch
Series RN 3000 / 6000
Technical information / Instruction manual
Technical Data
Electrical data
Connection terminals see page 23/ 24
Cable entry M20 x 1.5 screwed cable gland
NPT ½“ conduit connection
NPT ¾” conduit connection (only RN 6000)
Clamping range (diameter) of the factory provided cable glands:
M20 x 1.5: 6 .. 12 mm (0.24 .. 0.47")
Protection class I
III (Version 24 V DC PNP)
Overvoltage category II
Pollution degree 2 (inside housing)
Power supply see page 23/ 24
Installed load see page 23/ 24
Signal and alarm output see page 23/ 24
Isolation Power to signal and alarm output: 2,225 Vrms
Signal output to signal output (DPDT): 2,225 Vrms
Indicating light By built-in LED (apart form AC version)
Mechanical data
Housing Aluminium housing, powdercoated, RAL 5010 gentian blue
RN3000: optional plastic PA6 GF, RAL 5010 gentian blue
Seal between housing and lid: NBR
Seal between housing and process connection: NBR
Nameplate: poyester lm
Degree of protection RN 3000: IP66*
RN 6000: IP66*
Types with process connection and extension in stainless steel:
IP66*, NEMA Type 4X (not for: RN 600x with process temperature ≥150°C (302°F),
RN 6002 with sliding sleeve, RN 6003)
* IEC/EN/NBR 60529
Material process connection
(options available)
Thread: 1.4305 (303) or 1.4404 (316L) or aluminium
Triclamp: 1.4305 (303) or 1.4404 (316L)
Flange rectangle: 1.4301 (304) or aluminium
Flange DN/ ANSI: 1.4541 (321) or 1.4404 (316L), DN32 also made of aluminium
Material extension
(options available)
RN x001: 1.4301 (304)/ 1.4305 (303) or 1.4404 (316L)
RN x002 pipe: 1.4301 (304)/ 1.4305 (303) or 1.4404 (316L) or aluminium
RN x002 rope: 1.4305 (303)/ 1.4401 (316)
RN x003: 1.4301 (304) or aluminium
RN x004: 1.4301 (304)/ 1.4305 (303) or 1.4404 (316L) or aluminium
RN 3005: 1.4305 (303) or 1.4404 (316L)
Material vane shaft 1.4301 (304)/ 1.4305 (303) or 1.4404 (316L)
Material measuring vane incl.
socket (options available)
boot-shaped and rectangular vane: 1.4301 (304) or 1.4404 (316L)
hinged vane 1.4301 (304)/ 1.4305 (303)/ 1.4310 (301) or 1.4404 (316L)
rubber vane 1.4301 (304)/ rubber SBR
Tolerance length "L“ ±10 mm (±0.39“)
Bearing Ball bearing, dust-tight
Sealing Radial rotary shaft sealing
Material: NBR (Acrylnitril-Butadien-rubber)
FPM (Viton)
PTFE (Teon)
Graphite based (version 350°C (662°F) and 600°C (1,112°F)
See also selection guide on page 5.
Rotonivo®
1
2
3
4
5
6
7
8
9
10
11
12
RN 3000 / 6000
gi011016
10

page
Level limit switch
Series RN 3000 / 6000
Technical information / Instruction manual
Technical Data
RN 3000 Version Extension
80°C
(176°F )
150/ 250/ 350/ 600°C
(302/ 482/ 662/ 1,112°F)
1,100°C
(2,012°F)
Aluminium * Stainl. steel * Aluminium Stainl. steel *
RN 3001
RN 3002
RN 3002-
rope
RN 3003
RN 3004
RN 3005
1.2 kg
(2.6 lbs)
1.3 kg
(2.9 lbs)
2.1 kg
(4.6 lbs)
3.7 kg**
(8.1 lbs)
1.3 kg
(2.9 lbs)
1.3 kg
(2.9 lbs)
1.5 kg
(3.3 lbs)
1.6 kg
(3.5 lbs)
2.4 kg
(5.3 lbs
6.1 kg* *
(13.4 lbs)
1.6 kg
(3.5 lbs)
1.6 kg
(3.5 lbs)
+1.2 kg
(+2.6 lbs)
+1.2 kg
(+2.6 lbs)
+1.2 kg
(+2.6 lbs)
+1.2 kg
(+2.6 lbs)
+1.2 kg
(+2.6 lbs)
+2.8 kg
(+6.2 lbs)
+2.8 kg
(+6.2 lbs)
-
+1.3 kg /m
(+2.9 lbs per 39.3“)
-
+0.4 kg/ 100mm
(+0.9 lbs per 3.93”)
+0.15 kg/ 100 mm
(+0.3 lbs per 3.93”)
-
+2.7 kg/m
(+5.9 lbs per 39.3“)
+0.25 kg/m
(+0.6 lbs per 39.3“)
+0.6 kg/ 100 mm
(+1.3 lbs per 3.93”)
+0.3 kg/ 100 mm
(+0.7 lbs per 3.93”)
Overall weight
(ca.)
* Process connection
** Version with ange 150x150x12mm (5.9x5.9x0.47”), L=250mm (9.84”)
All weights are without anges (except RN 3003) and smallest measuring vane.
RN 6000 Version Extension
80°C
(176°F )
150/ 250/ 350/ 600°C
(302/ 482/ 662/ 1,112°F)
1,100°C
(2,012°F)
Aluminium * Stainl. steel * Aluminium Stainl. steel *
RN 6001
RN 6002
RN 6002-
rope
RN 6003
RN 6004
1.5 kg
(3.3 lbs)
1.6 kg
(3.5 lbs)
2.4kg
(5.3 lbs)
4.0 kg**
(8.8 lbs)
1.6 kg
(3.5 lbs)
1.8 kg
(4.0 lbs)
1.9 kg
(4.2 lbs)
2.7 kg
(5.9 lbs)
6.4 kg**
(14.1 l bs)
1.9 kg
(4.2 lbs)
+12 kg
(+2.6 lbs)
+1.2 kg
(+2.6 lbs)
+1.2 kg
(+2.6 lbs)
+1.2 kg
(+2.6 lbs)
+1.2 kg
(+2.6 lbs)
+2.8 kg
(+6.2 lbs)
+2.8 kg
(+6.2 lbs)
-
+1.3 kg /m
(+2.9 lbs per 39.3“)
-
+0.4 kg/ 100 mm
(+0.9 lbs per 3.93”)
+0.15 kg/ 100 mm
(+0.3 lbs per 3.93”)
-
+2.7 kg/m
(+5.9 lbs per 39.3“)
+0.25 kg/m
(+0.6 lbs per 39.3“)
+0.6 kg/ 100 mm
(+1.3 lbs per 3.93”)
+0.3 kg/ 100 mm
(+0.7 lbs per 3.93”)
All mentioned weights are with Standard-housing.
By use of de-housing: +1.4 kg (+3.1 lbs)
d-housing: +1.0 kg (+2.2 lbs)
* Process connection
** Version with ange 150 x 150 x 12 mm (5.9 x 5.9 x 0.47”), L=250 mm (9.84”)
All weights are without anges (except RN 6003) and smallest measuring vane.
Friction clutch Protects the gear unit against impacts of the measuring vane
Speed of measuring vane 1 rotation or 5 rotations per minute
Sound level max. 50 dBA
RN 3000 / 6000 gi011016
11
Rotonivo®1
2
3
4
5
6
7
8
9
10
11
12

page
Level limit switch
Series RN 3000 / 6000
Technical information / Instruction manual
Technical Data
Operating conditions
RN 3000:
Ambient temp. (housing)/
process temperature
-40°C (-40°F) ambient and process temperature for version with heating of housing (pos.26)
-40°C (-40°F) ambient temperature not for version with plastic housing in Ex Version
+350/ 600°C (+662/ 1,112°F) process temperature not for version RN 3003, not for Ex-approvals
+1,100°C (2,012°F) process temperature for version RN 3001, RN 3002, not for Ex-approvals
For versions with Ex-approvals: see remarks on page 31.
RN 6000:
Ambient temp. (housing)/
process temperature
-40°C (-40°F) ambient and process temperature for version with heating of housing (pos.26)
+350/ 600°C (+662/ 1,112°F) process temperature not for version RN6003, not for Ex-approvals
+1,100°C (2,012°F) process temperature for version RN 6001, RN 6002, not for Ex-approvals
For versions with Ex-approvals: see remarks on page 31.
Ventilation Ventilation is not required
Min. powder density/
sensitivity
see section “Sensitivity” on page 28
Output signal delay Version AC, DC Universal voltage
Sensor free -> covered* ca. 1.3 sec ca. 1.5 sec + 0 .. 20 sec adjustable
Sensor covered -> free ca. 0.2 sec ca. 0.2 sec + 0 .. 60 sec adjustable
*after blocking of the masuring vane
Features of bulk material Hardly any limitations.
Rotonivo®
1
2
3
4
5
6
7
8
9
10
11
12
RN 3000 / 6000
gi011016
12

page
Level limit switch
Series RN 3000 / 6000
Technical information / Instruction manual
Steel: max. 500 Nm*
Alu: max. 180 Nm*
max. 50 Nm*
max. 50 Nm*
Steel: max. 600 Nm*
Alu: max. 250 Nm*
Technische Daten
Max. permitted
mechanical torque
RN 3001/ 6001: RN 3002/ 6002
RN 3004/ 6004:
RN 3003/ 6003:
* at 40°C
For version with reinforced rib on request
Protective measures in case of high load: mounting of an protective canopy above the probe
(horizontal installation) or xing of the extension tube.
Max. tractive force RN 3001/ 6001 pendulum shaft: 400 N (only applicabel as full detector)
RN 3002/ 6002-rope: 4 kN (type standard) 28 kN (type reinforced)
Max. process pressure -0.9 .. +0.8 bar (-13.1 .. 11.6 psi) or -0.9 .. +5 bar (-13.1 .. 73 psi) or -0.9 .. +10 bar (-13.1 .. 145 psi)
-0.1 .. +0.1 bar (-1.5 .. 1.5 psi) for 600°C (1,112°F) and 1,100°C (2,012°F) version
For pressure over 0.8 bar (11.6 psi) the Teon sealing is used.
For versions with Ex-approvals: see remarks on page 30.
Vibration 1.5 (m/s2)2/ Hz according to EN 60068-2-64
Relative Humidity 0 - 100%, suitable for outdoor use
Altitude max. 2,000 m (6,562 ft)
Expected product
lifetime
Following parameters have a negative inuence on the expected product lifetime:
High ambient- and process temperature, corrosive environment, high vibration, high ow rate of
abrassive bulk material passing the sensor element, high amount of measurement cycles..
Transport and storage
Transport Observe the instructions as stated on the transport packing, otherwise the products may get
damaged.
Transport temperature: -40 .. +80°C (-40 .. +176°F)
Transport humidity: 20 .. 85%
Transport incoming inspections must be caried out to check for possible transport damage.
Storage Products must be stored at a dry and clean place.
They must be protected from inuence of corrosive enviroment, vibration and exposure to direct
sunlight.
Storage temperature: -40 .. +80°C (-40 .. +176°F)
Storage humidity: 20 .. 85%
RN 3000 / 6000 gi011016
13
Rotonivo®1
2
3
4
5
6
7
8
9
10
11
12

page
Level limit switch
Series RN 3000 / 6000
Technical information / Instruction manual
Approvals
* Depending on selected version
RN 3000
RN 6000
General Purpose *
(Ordinary Locations)
• •
•
•
• •
CE EN 61010-1 (IEC/CB)
FM
CSA
TR-CU
Hazardous Locations * • •
•
•
• •
•
•
•
•
•
•
•
•
• •
•
•
• •
ATEX
IEC-Ex
FM
CSA
TR-CU
INMETRO
Dust explosion
Gas explosion
Dust explosion
Gas explosion
Dust explosion
Gas explosion
Gas explosion
Dust explosion
Gas explosion
Gas explosion
Dust explosion
Gas explosion
Gas explosion
Dust explosion
Gas explosion
Gas explosion
ameproof
ameproof/ increased safety
ameproof
ameproof/ increased safety
ameproof
ameproof/ increased safety
ameproof
ameproof/ increased safety
ameproof
ameproof/ increased safety
ameproof
ameproof/ increased safety
ATEX II 1/2 D Ex t IIIC T! Da/Db IP6X
ATEX II 2G Ex d IIC T! Gb
ATEX II 2G Ex de IIC T! Gb
IEC-Ex t IIIC T! Da/Db IP6X
IEC-Ex d IIC T! Gb
IEC-Ex de IIC T! Gb
Cl. II, III Div. 1 Gr. E,F,G
XP Cl. I Div. 1 Gr. B-D
Cl. I Zone 1 AEx d IIC
Cl. I Zone 1 AEx de IIC
Cl. II, III Div. 1 Gr. E,F,G
Ex DIP A20/21
XP Cl. I Div. 1 Gr. B-D
Cl. I Zone 1 Ex d IIC
Cl. I Zone 1 Ex de IIC
Ex ta/tb IIIC T! Da/Db X
Ex d IIC T! Gb X
Ex de IIC T! Gb X
Ex ta/tb IIIC T! Da/Db IP6X
Ex d IIC T! Gb
Ex de IIC T! Gb
Detailed allocation of types and electronic modules to approvals: see selection list.
Functional safety • SIL 2 (IEC 61508)
The Safety Manual RN6000 must be considered when using the units in safety systems.
EMC • • EN 61326 - A1
Hygiene* • • EHEDG
Food grade material • • According to directive 1935/2004/EC
RoHS Conform • • According to directive 2011/65/EU
Pressure Equipment
Directive
(2014/68/EU)
The units are not subject to this directive, because they are classied as „pressure-keeping
equipment“ and do not have a pressurized housing (see Art.1, clause 2.1.4).
The units are designed and manufactured in accordance to the Pressure Equipment Directive.
The unit is NOT intended for use as a "equipment part with safety function" (Art.1, clause 2.1.3).
If the units should be used as "equipment part with safety function", please contact the
manufacturer.
Rotonivo®
1
2
3
4
5
6
7
8
9
10
11
12
RN 3000 / 6000
gi011016
14

page
Level limit switch
Series RN 3000 / 6000
Technical information / Instruction manual
Options
Weather protection
cover
If the measuring device is used outdoors, the use of the
weather protection cover is recommended. It protects the
device from all atmospheric inuences such as:
• rain water
• condensation water
• excessively high temperatures due to insolation
• excessively low temperatures in winter
Material: PE, weather and temperature stable
Not available for housing version d and de.
For use in Hazardous Locations: only permitted for zone 2 and
22 or Division 2.
Sliding sleeve RN 3002/ 6002 Process connection and material as chosen
Version with selection code pos.30:
Only for applications without process pressure.
Not available for Ex-approvals.
Version with selection code pos.31: For applications with
process pressure. Sealing material to the extension tube:
viton.
Mounting set Screws and washers for xing the unit on a ange.
Flat gasket On the face sealing of the process connection thread.
Incl. sealing face for version with G 1½" thread.
Max. 250°C
LED
(Glass window in lid)
To see the indicating light on the electronic module from
outside.
Not available for housing version d and de.
Bulb Bright indicating light seen from outside.
Not available for use in Hazardous Locations.
Plug Used instead of cable gland.
Not available for use in Hazardous Locations and FM/ CSA general purpose.
Connection of the plug wires to the internal terminals of the unit must be done on site or according to
customer demands.
Valve connector (incl. mating plug)
4-pole (incl. PE), max. 230 V, enclosure plastic, IP65
Plug M12 (without mating plug)
4-pole, max. 25 V or 5 -pole , max. 60 V
Enclosure brass, IP67
Plug Han 4A (incl. mating plug)
5-pole (incl. PE), max. 230 V, enclosure zinc, IP65
LED
Glass window
RN 3000 / 6000 gi011016
15
Rotonivo®1
2
3
4
5
6
7
8
9
10
11
12

page
Level limit switch
Series RN 3000 / 6000
Technical information / Instruction manual
Process pressure Improper installation may result in loss of process pressure.
Chemical resistance
against the medium
Materials of construction are choosen based on their chemical compatibility (or inertness) for
general purposes. For exposure to specic environments, check with chemical compatibility
charts before installing.
Mechanical load The torque at the fastening spot must not exceed the specied ratings. See page 12 for details.
Mounting location Keep away from incoming material and from silo walls.
The installation has to be carried out, that the sensor elements cannot hit the wall of the silo. The
ow of the medium and xtures in the container must be considered. This is especially important
for extension length of more than 3000 mm (118“)
Sliding sleeve Tighten both straining screws M8 with 20 Nm
to obtain resistance against pressure
Flange mounting A plastic seal must be used to tighten the ange.
EHEDG-approval/
Food grade material
The materials are available for the use under normal and predictable applications (according to
directive 1935/2004 Art.3). Other conditions can inuence the safety.
General Safety Instructions
Additional Safety Instructions for Hazardous Locations
Installation regulations For devices to be used in Hazardous Locations the respective valid installation regulations must
be observed.
Sparks The installation has to be done in a way, that mechanical friction or impact does not cause
sparks between the aluminium enclosure and steel.
EHEDG approval EHEDG conform design (material and construction in
contact with the process).
Approved with ush welding socket
Material: aluminium or 1.4301 (304) or 1.4404 (316L)
(details see: mounting instructions EHEDG version, page
17).
Food grade material Food grade material in contact with the process food (sealing and grease FDA conform). The option
does not automatically implement a food conform design (food conform gaps, surface and radiuses).
Mounting
Options / Mounting
Rotonivo®
1
2
3
4
5
6
7
8
9
10
11
12
RN 3000 / 6000
gi011016
16

page
Level limit switch
Series RN 3000 / 6000
Technical information / Instruction manual
Mounting
Mounting instructions
The housing can be rotated against the
threaded connection after mounting.
RN 6000: For the d- and de- housing:
Fixing screw must be unfastened
to enable rotation. Fix the screw
again, when the housing has the
right position.
Threaded connection
Fixing screw
Housing
metal-metal
sealing
seal thread with
teon tape
welding with
container wall
Flush welding
socket
Dimension of ush welding socket (for optional on site manufacturing):
Length of extension L
Surfaces in contact with
process Ra ≤0.8 µm
Section A Section B
Dimensions in mm
* suggested values
(in brackets values to be
adhered bindingly)
Rotatable housing
Direction of the cable glands When the unit is mounted from the side, ensure, that the cable glands face downwards and are
closed
to avoid water penetration into the housing.
Sealing Seal the process connection thread with teon tape against process pressure.
Alternative use of a at gasket is possible (option pos. 15)
Precaution for later
dismounting/ Service
• Use teon tape to avoid seizing of aluminium process connection thread with the socket
• Grease the screws of the lid if corrosive atmosphere is present (e.g. close to sea)
EHEDG-Approval Seal the thread with teon tape against process pressure.
Metal-metal sealing:
• The support muß be plane and without any gap. No teon tape (or similar) is allowed to be in
between.
• Fixing torque 100 Nm
The quality of the welding with the container wall must be according to the respective
regulations (e.g. gaps, transitions, surface nish).
RN 3000 / 6000 gi011016
17
Rotonivo®1
2
3
4
5
6
7
8
9
10
11
12
A
RN ..001 28 mm
(1.1” )
RN ..002/
RN ..004
38 mm
(1.5”)

page
Level limit switch
Series RN 3000 / 6000
Technical information / Instruction manual
Mounting
RN 3001
RN 6001
A Full detector vertical and oblique from the top
max. „L“=600 mm (23.62”)
B With pendulum shaft or rope extension: Full detector
vertical from the top. Observe max. pulling force.
C Full detector horizontal
max. „L“=300 mm (11.8”)
D Demand or empty detector horizontal
max. „L“=150 mm (5.9”)
Protective angle recommended depending on load.
E Empty detector oblique from the bottom
max. „L“=150 mm (5.9”)
Protective angle recommended depending on load.
Horizontal mounting: Boot shaped vane recommended (min.
mech. load, because the vane aligns to the movement of the
material).
RN 3002
RN 6002 A Full detector vertical from the top
max. „L“=3,000 mm (118“)
Remark:
Deviation up to max. 10° from vertical installation with option
„Bearing at tube end“ possible.
B Full detector vertical from the top
max. „L“=4,000 mm (158“)
Support from side recommended.
RN 3002-Rope
RN 6002-Rope A Full detector vertical
B Demand detector vertical
C Empty detector vertical
max. „L“=10,000 mm (394“)
Observe max. tractive force.
Rotonivo®
1
2
3
4
5
6
7
8
9
10
11
12
RN 3000 / 6000
gi011016
18

page
Level limit switch
Series RN 3000 / 6000
Technical information / Instruction manual
Mounting
RN 3003
RN 6003 A Full detector horizontal
B Demand detector horizontal
C Empty detector horizontal
Protective angle recommended depending on load.
RN 3004
RN 6004 A Full detector vertical and oblique from the top
B Full detector horizontal
C Demand or empty detector horizontal
Protective angle recommended depending on load.
D Empty detector oblique from the bottom
Protective angle recommended depending on load.
Horizontal mounting: Boot shaped vane recommended
(min. mech. load, for the vane aligns to the movement of the
material).
RN 3000 / 6000 gi011016
19
Rotonivo®1
2
3
4
5
6
7
8
9
10
11
12

page
Level limit switch
Series RN 3000 / 6000
Technical information / Instruction manual
Electrical installation
Handling In the case of improper handling or handling malpractice, the electric safety of the device cannot be
guaranteed.
Installation regulations The local regulations or VDE 0100 (Regulations of German Electrotechnical Engineers) must be
observed.
WIth use of 24 V supply voltage, an approved power supply with reinforced insulation to mains is
required.
Fuse Use a fuse as stated in the connection diagrams (see pages 23 and 24).
RCCB protection In the case of a fault, the supply voltage must be automatically switched off by a RCCB protection
switch to protect against indirect contact with dangerous voltages.
Power supply switch A voltage disconnection switch must be provided near the device.
Wiring diagram The electrical connections are made in accordance with the wiring diagram.
Supply voltage Compare the supply voltage applied with the specications given on the electronic module and name
plate before switching the device on.
Cable gland The screwed cable gland and closing element must have following specications:
Ingress protection IP66, temperature range from -40°C to +70°C, UL or VDE or INMETRO certied
(depending on the country where the unit is installed), pull relief. Make sure that the screwed cable
gland safely seals the cable and that it is tight (danger of water intrusion). Cable glands that are not
used have to be sealed with a blanking element.
The diameter of the eld wiring cable has to match to the clamping range of the used cable gland.
Conduit system In case of using a conduit system (with NPT thread) instead of a cable gland the regulations of the
country, where the unit is installed, must be observed. The conduit must have a tapered thread either
NPT ½“ or NPT ¾” in accordance with the unit and ANSI B 1.20.1. Not used inlets must be closed
tight with a metal blanking element.
Field wiring cables • The diameter has to match to the clamping range of the used cable gland.
• The cross section has to match with the clamping range of the connection terminals and consider
the max. current.
• All eld wirings must have insulation suitable for at least 250 V AC.
• The temperature rating must be at least 90°C (194°F).
• If higher immunity interferences as specied in the stated EMC standards are present (see chapter
approval), a shielded cable is required, otherwise an unshielded instrumentation cable is
satisfactory.
Guiding the cables in the
terminal box
Cut the eld wiring cables to appropriate length to t properly into the terminal box.
Microswitch protection Provide protection for microswitch contacts to protect the device against inductive load surges.
Protection against static
charging
The housing of the unit must be grounded to avoid static charging of the unit. This is particularly
important for applications with pneumatic conveying and non-metallic containers.
General Safety Instructions
External equipotential
bonding terminal
RN 3000 RN 6000
Additional Safety Instructions for Hazardous Locations
Connect to equipotential
bonding of the plant
Rotonivo®
1
2
3
4
5
6
7
8
9
10
11
12
RN 3000 / 6000
gi011016
20
This manual suits for next models
11
Table of contents
Other UWT Switch manuals

UWT
UWT Capanivo CN 4000 Series User manual

UWT
UWT Vibranivo VN 1000 Series User manual

UWT
UWT Vibranivo VN 4000 Series User manual

UWT