VALERE Power BC Series User manual

Page 1 of 47 Version 2.0
DO600000191 November, 2006
BC Series Controller
Operation Manual
24 x7 Installation and Technical Support
1-866-240-6614

Page 2 of 47 Version 2.0
DO600000191 November, 2006
Table of Contents
1Overview.......................................................................................................3
2Controller Connections...............................................................................3
2.1 Temperature Probes ...................................................................................................... 4
2.2 Alarm Cable Connection................................................................................................ 4
2.3 Auxiliary Input Alarms .................................................................................................... 5
2.4 Expansion Controller Connection................................................................................... 6
2.5 Remote/Computer Interface........................................................................................... 7
3Controller Insertion & Setup.......................................................................8
4Navigation ..................................................................................................12
5Controller Login.........................................................................................13
6Presets........................................................................................................13
7Controller Configuration Menu.................................................................13
7.1 Language ..................................................................................................................... 14
7.2 Review Module............................................................................................................. 14
7.3 Setpoints ...................................................................................................................... 15
7.4 Alarms..........................................................................................................................17
7.5 Tests............................................................................................................................. 19
7.6 Thermal........................................................................................................................ 23
7.7 LVD Menu .................................................................................................................... 27
7.8 Ringer........................................................................................................................... 29
8Troubleshooting ........................................................................................31
Appendix A........................................................................................................37

Page 3 of 47 Version 2.0
DO600000191 November, 2006
1Overview
This manual is intended to be a supplement to the Compact and Integrated shelf
Installation and Maintenance manuals. This manual also only covers operation
of the BC50x/10xx-series controllers from the front display. See section 2.5 for
more information on remote operation.
Table 1 shows all controllers covered by this manual and some specifications of
each type. You can find the model of the controller on the product label of the
controller. To determine the type of controller find the model, for example
BC500-A01-10. The first section, in this case BC500, is the type of controller.
Model # Local Interface Remote Interface T Probes/Aux In Form-C Relays Expansion connector
BC500 3 buttons & display None 3 6 Yes
BC502 3 buttons & display RS232 3 6 Yes
BC1000 3 buttons & display LAN 3 6 Yes
BC1001 3 buttons & display Modem 3 6 Yes
BC1011 3 buttons & display LAN - powered by
shelf bias 36 Yes
Table 1 - Controller list
2Controller Connections
The BC series controller has several external connections. These connections
are discussed in the following sections.
Figure 1 - Controller connections (BC1000 shown)
Remote
Connection
BC10xx only
Expansion
controller
co
nn
ec
ti
o
n
Alarm cable
connection
Display
connection
(3) Temperature
Probe/AUX
alarm inputs

Page 4 of 47 Version 2.0
DO600000191 November, 2006
Figure 2 - Controller connections (BC502 shown)
2.1 Temperature Probes
Up to three, battery temperature probes (sold separately) may be installed for
battery temperature compensation. Attach the probe (either a ring terminal
or paddle style) to a battery and insert the cable connector end into the
mating end of the probe; connect the other end into the temperature probe
inputs denoted as T1, T2, and T3 from left to right. See DO600000039 –
Temperature Probe Sensor manual for more installation information.
Temperature compensation must be enabled for the system to take
advantage of the temperature probes. See section 7.6 for instructions on
setting up thermal compensation. Assuming thermal compensation is
enabled, the controller will automatically setup itself to monitor temperature
via the external probes.
2.2 Alarm Cable Connection
Six form C alarm relays are available through a connector labeled ALM in
Figure 1. To access these alarms, use the cable (sold separately), that has a
shelf mating connector on one end and bare tinned wire on the other.
Available alarm cables are CA210203104 (10ft), CA210203105 (50ft), and
CA210203106 (100ft). Plug the connector end into the ALM connector on
the controller. As for the non-connectorized end, the alarm cable provides
both normally open (NO) and normally closed (NC) alarms. Therefore
choose the proper alarm polarity and connect it and the common (C) to the
alarming equipment.
Table 2 is a list of alarm contacts and the corresponding color code of the
alarm cable. The alarm names in Table 2 are based on the Valere default
controller with profile number 01 (PN 01). Your profile number may be
Alarm cable
connection
Display
connection
(3) Temperature
Probe/AUX
alarm inputs
RS232
COM port

Page 5 of 47 Version 2.0
DO600000191 November, 2006
different and can be determined by accessing the main menu. The main
menu can be accessed by pressing the MENU button down for 5 seconds.
The controller will then display “WELCOME PN XX”; this is your profile
number. Contact Valere tech support at 1-866-240-6614 for a copy of your
company’s controller settings if different from profile # 01. A relay test can be
used to verify that the alarm cable is connected properly. See section 7.5 for
setting up the relay test.
Alarm Cable
Alarm
Channel
Functional
Designation Wire Color Alarm
Behavior
NC Orange/White
stripe
Contact Opens
On Alarm
C Orange Common
A
(Major
Alarm) NO Orange/Black
stripe
Contact Closes
On Alarm
NC Red/White
stripe
Contact Opens
On Alarm
C Red Common
B
(Minor
Alarm) NO Red/Black
stripe
Contact Closes
On Alarm
NC Green/White
stripe
Contact Opens
On Alarm
C Green Common
C
(AC
Fail) NO Green/Black
stripe
Contact Closes
On Alarm
NC Yellow/White
stripe
Contact Opens
On Alarm
C Yellow Common
D
(BD
Alarm) NO Yellow/Black
stripe
Contact Closes
On Alarm
NC Lt Blue/White
stripe
Contact Opens
On Alarm
C Lt Blue Common
E
(LVD
Open
Alarm) NO Lt Blue/Black
stripe
Contact Closes
On Alarm
NC Tan/White
stripe
Contact Opens
On Alarm
C Tan Common
F
(DIST
Alarm) NO Tan/Black
stripe
Contact Closes
On Alarm
Input (+) White
Input
Alarm Input (-) Black
Closed =
Alarm
Table 2- Alarm Cable color code
2.3 Auxiliary Input Alarms
To use the temperature probe input port as an external alarm channel, simply
connect a normally open dry contact relay onto an input cable
(CA210023676) and plug the other end into an available input port (T1, T2,

Page 6 of 47 Version 2.0
DO600000191 November, 2006
or T3). When the relay closes an Aux alarm will be triggered, on the
controller.
In addition, a fourth alarm is available via the black (I-NEG) and white (I-
POS) wires on the output alarm cable. This input will accept either a contact
closure or a voltage between 5Vdc and 60Vdc to trigger an alarm. Connect
voltage to the proper wire based on polarity, and when voltage is applied an
Aux alarm will be triggered. It is not necessary to ground the second wire.
Connecting to the wrong polarity wire will not damage the controller.
When an alarm is detected, the controller will set an AUX ALARM followed
by a string of zeros and ones. See Table 10 for help deciphering the alarm
code.
No setup is required to produce an AUX ALARM. Although, if your system is
equipped with a LAN interface, alarms can be user mapped, to a different
relay, through the web interface using the software utility provided by Valere.
Refer to Application Bulletin 201, “Connecting to the LAN Port”, that is
included with a LAN capable controller, for mapping alarms.
2.4 Expansion Controller Connection
Use of the EXP port is dependent upon the shelf configuration. Not all
configurations make use of the EXP port. The EXP connection is only used
on systems with an external LVD and/or multiple power shelves, such as the
Integrated Power System. This allows the main system controller (BC-
series) to manage an external LVD and/or a second power shelf with an
EC1000.
Connect the communication cable from the external LVD or EC1000
expansion controller into the mating connector labeled EXP. The controller
will automatically recognize the external LVD or second power shelf and
configure itself automatically. No further setup is required. A second power
shelf will require a rectifier(s) to be installed to be active in the controller
software. See example connection in Figure 3.

Page 7 of 47 Version 2.0
DO600000191 November, 2006
Figure 3 - Expansion connection
2.5 Remote/Computer Interface
The BC-series controller is available in many different varieties, including
several with remote or computer interfaces. See Table 1 for a list of
controllers and connections available for each type.
For the BC502, with the RS232 connection, refer to DO600000132 – BC502
(RS232) manual for further information on how to connect to and use the
RS232 port. Communication with the BC502 is via a supplied
communication cable (CA210042487).
For the BC1000 and BC1011, with the Ethernet LAN connection, refer to
Application Bulletin 201, “Connecting to the LAN Port” for further information
on how to connect to and use the Ethernet LAN port. Communication with
the LAN port is via an Ethernet cross-over cable or straight through cable a
router. This cable is not supplied by Valere Power.
For the BC1001, with the modem connection, refer to Application Bulletin
202, “Modem User Manual” for further information on how to connect to and
use the modem port. Communication with the modem requires a working
phone line, and a VT100 capable interface.

Page 8 of 47 Version 2.0
DO600000191 November, 2006
3Controller Insertion & Setup
Install the controller by sliding the controller into the shelf, tightening the
mounting screw, and attaching the display to the shelf. Once DC power is
applied to the shelf, either by the rectifiers or batteries, the controller will power
up. The controller will automatically recognize all the components in the system
and automatically set itself up. After several seconds the controller will settle to
either SYSTEM OK or SYSTEM ALARM. See section 8 for assistance with any
alarms.
The controller will arrive already setup with the default settings based on the
profile number. No setup is required. These default setpoints can be found in
Table 3. The values in Table 3 are based on the Valere default controller with
profile number 01 (PN 01). Your profile number may be different and can be
determined by accessing the main menu. The main menu can be accessed by
pressing the MENU button down for 5 seconds. The controller will then display
“WELCOME PN XX”; this is your profile number. Contact Valere tech support at
1-866-240-6614 for a copy of your company’s controller settings if different from
profile # 01.
Figure 4 – Controller Installation
Mounting
Screw
Spring
Latch

Page 9 of 47 Version 2.0
DO600000191 November, 2006
12 Volt
Nominal 24 Volt
Nominal 48 Volt
Nominal
Valere Valere Valere
Parameter Description Default Default Default
LANGUAGE The language in which the controller will
display English English English
FLOAT V The voltage to which the rectifiers will
regulate the plant during float mode 12 Vdc 27 Vdc 54 Vdc
BATT. CL
status* Enables the battery current limit feature Disabled Disabled Disabled
BATT. CL I* The controller will limit the current to the
batteries at this setpoint 255 A 255 A 255 A
RECT. CL status Enables the system current limit feature Disabled Disabled Disabled
RECT CL I The controller will limit the current of the
rectifiers to the value 200 A 200 A 200 A
FALLBACK
status
Enables or Disables the Fallback feature.
Fallback provides a safe voltage to which the
rectifiers will output when they lose
communication with the controller for more
than one minute. Disabled Disabled Disabled
FALLBACK V
The safe voltage to which the rectifier will
fallback to in the event communication is lost
with the controller for more than one minute 11 Vdc 25 Vdc 50 Vdc
HVSD The controller will shut down the rectifiers if
the plant voltage exceeds this setpoint 14 Vdc 29 Vdc 58 Vdc
HIGH V
The controller will issue a High Voltage
Alarm if the plant voltage exceeds this
setpoint 13 Vdc 28.25
Vdc 57 Vdc
BD ALARM
The controller will issue a Battery-On-
Discharge alarm if the plant voltage falls
below this setpoint 11 Vdc 24 Vdc 48 Vdc
LVD Warning
The controller will issue a Low Voltage
Warning if the plant voltage falls below this
setpoint 10 Vdc 22 Vdc 44 Vdc
CAPACITY
status
An alarm is set if the number of installed
rectifiers will not support N+1 redundancy
required by the load. Disabled Disabled Disabled
I SHARE status
A minor alarm is set if the output current of
any rectifier exceeds current sharing
tolerances Enabled Enabled Enabled
COM FAIL
status
An alarm is set if any rectifier either stops
communicating or is removed from the shelf.
User action is required to clear the alarm Disabled Disabled Disabled
BOOST status
Enables or Disables the boost charge tests.
The boost feature will increase the output
voltage of the rectifiers for a short period of
time, usually to charge the batteries. Disabled Disabled Disabled
BOOST V The voltage at which the boost charge test will
increase to once the feature is activated 13 Vdc 28 Vdc 56.5 Vdc
BOOST H The length of time the boost charge test will
run 12 hours 12 hours 12 hours

Page 10 of 47 Version 2.0
DO600000191 November, 2006
12 Volt
Nominal 24 Volt
Nominal 48 Volt
Nominal
Valere Valere Valere
Parameter Description Default Default Default
BD TEST status Enables or Disables the battery test Disabled Disabled Disabled
BDT TIME
MNT Sets the length of time (minutes) that the
battery test will run. 30 min 30 min 30 min
BDT ALRM V
Sets the voltage at which an alarm will be
generated if the battery voltage falls below it
during the battery test 10.5 Vdc 26 Vdc 52 Vdc
BD ABRT V
The voltage at which the battery discharge test
will abort at when the system voltage drop
below this point. 10.5V 22V 43V
BD TEST
CONST
Sets the alarm constant for the Bat Test. 0 will
disable Thermal Compensation effects during
BD Test. 1 will take Thermal Compensation
effects into account during test 0 0 0
RLY TEST
Enables or Disables the relay test. Relay test
allows the user to activate alarm relay contacts
A-F. Disabled Disabled Disabled
T COMP status
Enables thermal compensation. Thermal
compensation adjusts the float voltage of the
rectifiers to increase or decrease the
temperature of the batteries. Disabled Disabled Disabled
T START T The high temperature at which the controller
activates thermal compensation 35 °C 35 °C 35 °C
T SLOPE T
The slope value at which the controller will
reduce the float voltage per degree if thermal
compensation is active 18 mV/°C 36 mV/°C 72 mV/°C
STOP VLT V
The minimum voltage to which the controller
will reduce plant voltage for thermal
compensation 11.25 Vdc 25.25 Vdc 50.5 Vdc
T SENSE
Selects temperature sensing device to use for
battery temperature compensation; Internal
sensor or External temp probes. The
controller will autosense when external probe
is attached and automatically adjusts value to
external. External External External
TL START T The low temperature at which the controller
activates thermal compensation -20 °C -20 °C -20 °C
TL SLOPE T
The slope value at which the controller will
increase the float voltage per degree if low
thermal compensation is active 0 mV/°C 0 mV/°C 0 mV/°C
STOP VLT V
The maximum voltage to which the controller
will increase the plant voltage for thermal
compensation 12.75 Vdc 28 Vdc 56 Vdc
T RUNAWY T The temperature at which the controller will
activate thermal runaway 60 °C 60 °C 60 °C

Page 11 of 47 Version 2.0
DO600000191 November, 2006
12 Volt
Nominal 24 Volt
Nominal 48 Volt
Nominal
Valere Valere Valere
Parameter Description Default Default Default
T RUNAWY V The voltage to which the rectifiers will reduce
for temperatures above T RUNAWY T 11 Vdc 25 Vdc 50 Vdc
TEMP IS Selects the units the temperature readings are
given in. Either Celsius or Fahrenheit Celsius Celsius Celsius
LVD 1 OPEN
V**
The system LVD contactor will open if the
plant voltage falls below this setpoint. x = 1-4
for systems with multiple LVDs 9.5 Vdc 21 Vdc 42 Vdc
LVD 1 RCNT
V**
The system LVD contactor will reconnect if
the plant voltage exceeds this setpoint. x = 1-4
for systems with multiple LVDs 11.5 Vdc 25 Vdc 50 Vdc
LVD 1 RCNT
SEC**
The amount of time, in seconds, that the plant
voltage must exceed the LVD reconnect
setpoint prior to reconnecting the LVD
contactor. x = 1-4 for systems with multiple
LVDs 20 Sec 20 Sec 20 Sec
RNG AC V*** AC voltage setpoint for the ringer output n/a n/a 86 Vac
RNG DC V***
The DC value at which the Ringer RMS value
is offset. The value should be the same value
as the float voltage. n/a n/a -Vfloat
RNG FREQ
HZ*** Output frequency of the ringer n/a n/a 20 Hz
High
temperature
alarm threshold
(LAN only)
High temperature value at which the
controller will trigger a HIGH TEMP alarm.
Accessed via the LAN card only. 98 °C 98 °C 98 °C
High
temperature
alarm release
(LAN only)
The temperature value at which the controller
will release a HIGH TEMP alarm. Accessed
via the LAN card only. 93 °C 93 °C 93 °C
Password Administrator/User 5001 5001 5001
* - Requires Shunt
** - Requires LVD
*** - Requires Ringer
Table 3- Controller Settings

Page 12 of 47 Version 2.0
DO600000191 November, 2006
4Navigation
Figure 5 shows the controller front display and three button keypad for
assistance with navigation the controller Appendix A contains the complete menu
tree for the controller. The UP and DN buttons are used to scroll through the
functions and the MENU button is used to select and/or drop down into a sub-
menu. Navigating through the controller can be broken down into three menu
levels Basic, Main/Review, and Administrator.
The Basic menu is the default menu when the controller is in an idle state it will
typically display SYSTEM OK. Using the UP/DN buttons you can navigate the
basic menu, through the following menus: Float Voltage/Current, Battery charge
current, temperature probe 1, temperature probe 2, temperature probe 3, and
internal temperature. In addition, the basic menu will display system alarms and
current system status.
The Main/Review menu can be accessed by holding the menu button down for 5
seconds. Scroll to the review section and all plant parameters can be viewed
from this level. When CHOOSE: >REVIEW is displayed press the MENU button
once to access the review menu. The Review menu only allows the user to
review setpoints and run tests that are enabled.
The Administrator menu allows the user to change system setpoints to desired
values. The following sections will expand more on the Administrator menu.
Figure 5 - Controller display

Page 13 of 47 Version 2.0
DO600000191 November, 2006
5Controller Login
The following is a step by step process for logging into the controller as an
administrator. All setpoints and features require login to change values or enable
features. Tests such as battery discharge test, boost test, and lamp test do not
require logging in to execute, provided the feature has been enabled. Default
password is 5001.
1. With display showing “System OK”, press and hold MENU button for 5
seconds. Release MENU button when Welcome screen appears.
2. Press the UP button to scroll to CHOOSE: >LOGIN and press MENU.
Display shows PASSWORD ->0000<-, and first 0 flashes.
3. Press MENU to change first digit to desired value. Each press of the
MENU button advances by one. Pressing UP selects that value for the
first digit, which stops flashing, and advances to the second digit,
which will begin to flash.
4. Repeat procedure above for all four digits.
5. Press UP to select <, which will then flash, and press MENU to enter
the password.
6. Controller displays OK: ADMIN for 5 seconds.
6Presets
Once you have logged into the controller, you can set all controller values to one
of three preset values by selecting either PRESET A, PRESET B, or PRESET C.
This can be done by pressing the UP button to scroll to CHOOSE: PRESET and
press the MENU button. This will enter the preset submenu. Press the UP
button to scroll to the appropriate preset value, and press the MENU button, and
hold it for about 5 seconds. The controller will exit out to the previous menu,
indicating that the preset values have been set. All presets are the same and are
the default values.
EXIT INSTRUCTIONS: Press the UP button to scroll to CHOOSE: EXIT and
press the MENU button. This will return you to the SYSTEM OK menu.
7Controller Configuration Menu
Once you have logged into the controller, you can make adjustments to any of
the following setpoints by pressing the UP button to scroll to CHOOSE: CONFIG
and pressing the MENU button. This will enter the configuration submenu list.
The configuration menu can be navigated by pressing the UP button to scroll
through all the menu choices.
EXIT INSTRUCTIONS: You can exit and logout of the configuration menu by
pressing the UP button to scroll to the end of the menu string and pressing the
MENU button at the BACK TO MAIN screen. This will send you back to the main
menu. All changes require logging out to take effect. Press UP button to scroll

Page 14 of 47 Version 2.0
DO600000191 November, 2006
to CHOOSE: EXIT and press the MENU button to exit back to the SYSTEM OK
menu.
7.1 Language
The language menu allows you to select the controller’s displayed language.
This menu can be accessed by pressing the MENU button at the CHOOSE:
LANGUAGE menu. Once the menu has been entered the screen will display
the current language setting. For example by default the screen would
display LANGUAGE: ENGLISH. This setting can be changed by pressing
the MENU button. The screen will then change to CHOOSE: ENGLISH. The
value can then be adjusted by pressing the UP and DN buttons. Once the
desired language is showing on the display, press the MENU button to select
that value.
NOTE: Please note that once a new language has been selected the screen
will be displayed in that language. If you do not understand that language,
navigation through the menu will be very difficult.
To exit this menu press the UP button until EXIT LANGUAGE is displayed on
the screen, and press MENU to exit. This will take you back to the
configuration menu. Continue to the next menu for adjustment or follow the
exit instructions at the beginning of this section.
7.2 Review Module
The review module menu allows you to see the DC current output of each
individual rectifier in the system.
This menu can be accessed by pressing the MENU button at the REVIEW:
MODULE menu. Once the menu has been entered the screen will display
the current value of the first rectifier in the first shelf (designated S1>) in the
system. The display will also show five slots representing the five possible
rectifier slots in a Valere System. The solid square represents the rectifier
currently being viewed, and the non-solid square represents the remaining
rectifiers installed in the system. Pressing the UP button at this point will
scroll through the remaining rectifiers in order. If the system is equipped with
a second power shelf (designated as S2>) the controller will also display that
shelf’s rectifiers in order after shelf 1.
To exit this menu press the UP button until EXIT MODULE is displayed on
the screen, and press MENU to exit. This will take you back to the
configuration menu. Continue to the next menu for adjustment or follow the
exit instructions at the beginning of this section.

Page 15 of 47 Version 2.0
DO600000191 November, 2006
7.3 Setpoints
The setpoints menu allows you to adjust controller setpoints such as float
voltage, rectifier current limit, and battery current limit. Please note that
some features require a low voltage disconnect (LVD) or shunt to be visible.
This menu can be accessed by pressing the MENU button at the CONFIG
SETPOINTS menu. The first setpoint displayed will be the float voltage of
the system. Press the UP button to continue scrolling thru the setpoints
menu. The menu will circle back to FLOAT once the end has been reached.
To exit this menu press the UP button until EXIT SETPOINTS is displayed on
the screen, then press the MENU to exit. This will take you back to the
configuration menu. Continue to the next menu for adjustment or follow the
exit instructions at the beginning of this section to exit. Below is a table of
setpoint ranges for all variables in the Setpoint menu.
Setpoints 12V (Volts) 24V (Volts) 48V (Volts)
Float Voltage 10.50 - 14.00 21.00 - 28.50 42.00 - 58.00
Battery Current Limit State enabled or disabled enabled or disabled enabled or disabled
Battery Current Limit 5 - 600 5 - 600 5 - 600
Rectifier Current Limit State enabled or disabled enabled or disabled enabled or disabled
Rectifier Current Limit 5 - 200 5 - 200 5 - 200
Fallback State enabled or disabled enabled or disabled enabled or disabled
Fallback Voltage 10.50 - 14.00 21.00 - 28.50 42.00 - 57.00
Table 4 - Setpoint value ranges
7.3.1 Float Voltage (Float)
Float voltage is the DC voltage which the rectifiers will output.
To adjust the float voltage, scroll to FLOAT V = xx.xx, press the MENU
button, and the screen will display CHOOSE: V = xx.xx. The value can
then be adjusted by pressing the UP and DN buttons in the corresponding
directions. This value can be adjusted in 0.5 V increments, and must be
1.00Vdc less than HVSD. Once the desired value is reached, press the
MENU button to accept the new value.
Press the UP button to move to the next setpoint or scroll to EXIT
SETPOINTS and press MENU.
7.3.2 Rectifier Current Limit (Rect CL)
Allows the user to set a limit, below the maximum capacity of the rectifier,
on the amount of current each rectifier will output
To enable rectifier current limit, scroll to RECT CL DISABLED press the
MENU button, and the screen will display RECT CL ENABLED.

Page 16 of 47 Version 2.0
DO600000191 November, 2006
Press the UP button to scroll to RECT CL I = xx. Press the MENU button
and the screen will display CHOOSE: I = xx. The value can then be
adjusted by pressing the UP and DN buttons in the corresponding
directions. This value can be adjusted in 2 amp increments. Once the
desired value is reached, press the MENU button to accept the new value.
For example, a system with three 50A rectifiers with an RECT CL I set to
20 A will limit each rectifier to 20 A for a total output of 60 A.
Press the UP button to move to the next setpoint or scroll to EXIT
SETPOINTS and press MENU.
7.3.3 Battery Current Limit (Batt CL)
Allows the user to set a limit on the amount of current being sent to the
batteries. This feature requires a battery LVD or shunt to be visible in the
menu structure. Also the batteries must be connected in series with this
LVD or shunt. Please see your shelf installation manual for proper
connection points for batteries.
NOTE: Connecting an equipment load in series with the LVD or shunt with
this feature enabled could possible cause the equipment to not work
properly. Follow your shelf’s installation manual for proper connections.
To enable battery current limit, scroll to BATT CL DISABLED press the
MENU button, and the screen will display BATT CL ENABLED.
Press the UP button to scroll to BATT CL I = xx. Press the MENU button
and the screen will display CHOOSE: I = xx. The value can then be
adjusted by pressing the UP and DN buttons in the corresponding
directions. This value can be adjusted in 5 amp increments. Once the
desired value is reached, press the MENU button to accept the new value.
Press the UP button to move to the next setpoint or scroll to EXIT
SETPOINTS and press MENU.
7.3.4 Fallback
Allows the user to set a safe voltage for the rectifiers to “fallback” to in
case the rectifier loses communication with the controller. This feature will
activate one minute after a loss of communication with the controller. In
addition this feature is only available via the front display.
To enable fallback, scroll to FALLBACK DISABLED, press the MENU
button, and the screen will display FALLBACK ENABLED.
Press the UP button to scroll to FALLBACK V = xx.xx. Press the MENU
button and the screen will display CHOOSE: V = xx.xx. The value can

Page 17 of 47 Version 2.0
DO600000191 November, 2006
then be adjusted by pressing the UP and DN buttons in the corresponding
directions. This value can be adjusted in .05 V increments. Once the
desired value is reached, press the MENU button to accept the new value.
This value must be less than the 1 < HVSD setpoint and greater than the
LVD OPEN setpoint.
Press the UP button to move to the next setpoint or scroll to EXIT
SETPOINTS and press MENU.
7.4 Alarms
The alarms menu allows you to adjust controller alarm setpoints such as high
voltage shutdown, high voltage alarm, battery on discharge alarm, capacity
alarm, current share alarm, and communication fail alarm.
This menu can be accessed by pressing the MENU button at the CONFIG
ALARMS menu. The first alarm displayed will be the high voltage shutdown
(HVSD) of the system. Press the UP button to continue scrolling thru the
alarm menu. The menu will circle back to HVSD once the end has been
reached.
To exit this menu press the UP button until EXIT ALARMS is displayed on
the screen, and press MENU to exit. This will take you back to the
configuration menu. Continue to the next menu for adjustment or follow the
exit instructions at the beginning of this section to exit.
Alarms 12V (Volts) 24V (Volts) 48V (Volts)
High Voltage Shutdown 11.50 - 15.00 22.00 - 29.50 48.00 - 59.00
High Voltage Alarm 11.50 - 15.00 24.00 - 28.50 48.00 - 59.00
Battery Discharge Alarm 10.00 - 13.50 20.00 - 27.00 40.00 - 55.00
Low Voltage Warning Alarm 9.00 - 13.00 20.00 - 26.00 40.00 - 52.00
Capacity Alarm enabled or disabled enabled or disabled enabled or disabled
Current Share Alarm enabled or disabled enabled or disabled enabled or disabled
Communication Failure Alarm enabled or disabled enabled or disabled enabled or disabled
Table 5 - Alarm value ranges
7.4.1 High Voltage Shutdown (HVSD)
HVSD is the DC voltage at which the rectifiers will shutdown if exceeded.
To adjust the high voltage shutdown, scroll to HVSD V = xx.xx, press the
MENU button, and the screen will display CHOOSE: V = xx.xx. The value
can then be adjusted by pressing the UP and DN buttons in the
corresponding directions. This value can be adjusted in 0.25 V
increments. This value must be at least 1V greater than the float voltage
value. Once the desired value is reached, press the MENU button to
accept the new value.

Page 18 of 47 Version 2.0
DO600000191 November, 2006
Press the UP button to move to the next setpoint or scroll to EXIT
ALARMS and press MENU.
7.4.2 High Voltage Alarm (HVA)
HVA is the DC voltage at which the controller will trigger an alarm if
exceeded. This is your warning before the system will shutdown, due to
HVSD.
To adjust the high voltage alarm, scroll to HVA V = xx.xx, press the MENU
button, and the screen will display CHOOSE: V = xx.xx. The value can
then be adjusted by pressing the UP and DN buttons in the corresponding
directions. This value can be adjusted in 0.25 V increments. This value
can be adjusted below the float voltage, and can be adjusted above
HVSD. Once the desired value is reached, press the MENU button to
accept the new value.
Press the UP button to move to the next setpoint or scroll to EXIT
ALARMS and press MENU.
7.4.3 Battery on discharge Alarm (BD Alarm)
BD Alarm is the DC voltage at which the controller will trigger an alarm if
the battery voltage falls below it. This is your first warning that the system
is being powered on batteries.
To adjust the battery discharge alarm, scroll to BD ALARM V = xx.xx,
press the MENU button, and the screen will display CHOOSE: V = xx.xx.
The value can then be adjusted by pressing the UP and DN buttons in the
corresponding directions. This value can be adjusted in 0.5 V increments.
This value can be adjusted above the float voltage. Once the desired
value is reached, press the MENU button to accept the new value.
Press the UP button to move to the next setpoint or scroll to EXIT
ALARMS and press MENU.
7.4.4 Low Voltage Warning Alarm (LVD Warn)
LVD warning is the DC voltage at which the controller will trigger an alarm
if the battery voltage falls below it. This is your second warning that the
system is being powered on batteries and the battery voltage is
dangerously low.
To adjust the low voltage alarm, scroll to LVD WARN V = xx.xx, press the
MENU button, and the screen will display CHOOSE: V = xx.xx. The value
can then be adjusted by pressing the UP and DN buttons in the
corresponding directions. This value can be adjusted in 0.5 V increments.

Page 19 of 47 Version 2.0
DO600000191 November, 2006
Once the desired value is reached, press the MENU button to accept the
new value.
Press the UP button to move to the next setpoint or scroll to EXIT
ALARMS and press MENU.
7.4.5 Capacity Alarm (Capacity)
Capacity alarm is the alarm that is triggered when N+1 redundancy is lost.
This is your warning that the system will be on battery back up if another
rectifier is lost.
To enable the capacity alarm, scroll to CAPACITY DISABLED, press the
MENU button, and the screen will display CAPACITY ENABLED.
Press the UP button to move to the next setpoint or scroll to EXIT
ALARMS and press MENU.
7.4.6 Current Share Alarm (I-share)
Current share alarm is the alarm that is triggered when one or more
rectifier is not sharing the current evenly.
To enable the current share alarm, scroll to I-SHARE DISABLED, press
the MENU button, and the screen will display I-SHARE ENABLED.
Press the UP button to move to the next setpoint or scroll to EXIT
ALARMS and press MENU.
7.4.7 Communication Failure Alarm (Comm Fail)
Communication fail alarm is the alarm that is triggered when the controller
loses communication with a rectifier. This is caused by a rectifier being
removed from the system. This alarm can be cleared from the main menu
by pressing MENU when the screen reads HIT MENU TO CLEAR.
To enable the communication fail alarm, scroll to COMM FAIL DISABLED,
press the MENU button, and the screen will display COMM FAIL
ENABLED.
Press the UP button to move to the next setpoint or scroll to EXIT
ALARMS and press MENU.
7.5 Tests
The tests menu allows you to adjust controller test setpoints such as boost,
battery discharge test, and Relay test. All tests can be executed from the

Page 20 of 47 Version 2.0
DO600000191 November, 2006
review menu if it has already been enabled. An Admin login is required to
enable or adjust any values.
This menu can be accessed by pressing the MENU button at the CONFIG
TESTS menu. The first test displayed will be lamp test. Press the UP button
to continue scrolling thru the tests menu. The menu will circle back to
EXECUTE LAMPTEST once the end has been reached.
To exit this menu press the UP button until EXIT TESTS is displayed on the
screen, and press MENU to exit. This will take you back to the configuration
menu. Continue to the next menu for adjustment or follow the exit
instructions at the beginning of this section to exit.
Test 12V (Volts) 24V (Volts) 48V (Volts)
Battery Boost State enabled or disabled enabled or disabled enabled or disabled
Battery Boost Voltage 11.00 - 14.00 21.00 - 28.50 42.00 - 58.00
Battery Boost Duration 1 - 48 (hours) 1 - 48 (hours) 1 - 48 (hours)
BDT state enabled or disabled enabled or disabled enabled or disabled
Test duration 15 - 300 (min) 15 - 300 (min) 15 - 300 (min)
Alarm voltage 9.00 - 14.00 (volts) 10.00 - 28.50 (volts) 45.00 - 52.00 (volts)
Abort voltage 9.00 - 14.00 (volts) 10.00 - 28.50 (volts) 40.00 - 52.00 (volts)
Alarm coefficient 0 or 1 0 or 1 0 or 1
BDT operating state active or inactive active or inactive active or inactive
Relay Test State enabled or disabled enabled or disabled enabled or disabled
Table 6 - Test value ranges
7.5.1 Lamp Test
Lamp test, when executed, will light every LED on the controller and
rectifiers. This can be used to determine if all LEDs are working properly.
To execute the lamp test, scroll to EXECUTE LAMPTEST and press the
MENU button. All LED’s will illuminate briefly and then return to their
normal state. This test can be executed from the review menu without
logging in as an administrator.
Press the UP button to move to the next setpoint or scroll to EXIT TESTS
and press MENU.
7.5.2 Boost test (Boost)
Boost test is a feature that will increase the float voltage of the rectifier to
boost charge your batteries or equalize your battery’s cell voltages. This
feature is a manually executed feature that will automatically turn off after
a set period of time. BOOST V is the voltage to which the rectifiers will be
increased if this test is executed. BOOST H is the length of time this test
will run if this test is executed. Once executed boost can be aborted from
the Basic menu. The screen will also display BOOST ACTIVE when the
test is active.
Other manuals for BC Series
1
This manual suits for next models
5
Table of contents
Other VALERE Power Controllers manuals