Vanguard V25-70 Series User manual

The Vanguard V25-70 Series Two-Way Emergency Voice Communication System is designed to
provide reliable and easy-to-use, communication for firefighters during an emergency.
The system consists of a Master Control Panel capable of controlling and supervising up to a maximum
of 900 emote Handset zones. Each emote Handset is wired to the Master Control Panel on a point to
point configuration. Such configuration prevents cable fault in one handset from affecting the other
handsets in the system.
Individual control buttons makes the system very easy to use as most control functions require only one
press operation. Individual LED status indicators provide operator with a quick overview of the system
status at a glance.
A wide range of system fault monitoring circuits and fault indicators are built into the system. Handsets
and cables are supervised for open and short circuit faults. Power supply unit and battery charger are
protected by fuses and supervised for faults. A one press Lamp Test button checks for faulty indicators.
The built-in battery enables the system to function without interruption even when mains supply fails. After
a mains failure, a boost charge facility allows the drained battery to be recharged to full capacity in a
shorter time. A digital voltmeter and ammeter provides accurate and easy to read system voltage and
current levels.
An optional Cassette Interface Module (complete with cassette recorder) is available to record all voice
transmission through the system. The recording can be started automatically whenever the fire alarm
system is activated.
The system meets the requirement of Singapore Standard CP25: Code Of Practice For Emergency Voice
Communication System in Buildings.
Two-Way Emergency Voice Communication
System : V25-70 Series

V25-70 EMERGENC VOICE COMMUNICATION S STEM FEATURES
Dedicated call buttons: Simple, fast one press operation.
Initiate calls to Remote Handsets: Allows Master Handset to place calls to the emote Handsets.
Privacy mode: For confidential communication between Master and selected emote Handset.
Modular design: Cater for easy future expansion by adding modules.
Audible and visual call indicators: Ensures all incoming calls are annunciated – no missed calls.
Supervised handsets: Immediate alert of cabling faults in any handsets.
Digital voltmeter and current indicators: Convenient checking of system power supply condition.
High voltage and lightning protection circuit: educes downtime caused by induced voltage spikes.
Boost charge facility: Speeds up battery charging after any prolonged mains power failure.
Power supply protection: Short circuit, overload and over voltage protection reduces downtime.
Full LED indicators: LEDs last longer and reduces capacity of standby battery.
Lamp test facility: Fast and convenient one press button to test all status indicators.
Optional Cassette Recorder Module: ecords conversation for post event analysis.
OPERATION
Master Control Panel Calling Remote Handsets
1. aising the Master Handset of the Master Control Panel enables every zone “SELECT” button.
2. Pressing the “SELECT” button of the required zone will cause the selected zone’s “CALL” indicator to flash.
3. A distinctive audible call signal at the selected emote Handset will sound.
4. aising the called emote Handset off its cradle will silence the audible call signal.
5. The flashing “CALL” indicator of the Master Control Panel will turn steady.
6. Communication link is now established.
Privacy Mode
The Privacy Mode facility allows private conversation between the Master Handset and any selected emote Handsets. emote
Handsets which have not been selected will receive a “busy” tone. The system is on Privacy Mode by default.
1. When the Master Handset is raised, the “P IVACY LINE ON” indicator lights up indicating that the system is in Privacy Mode.
2. A “busy” tone will be heard on any of the raised handsets. The “CALL” indicators of the raised handsets will flash.
3. Pressing the “SELECT” button of any raised handset zone will establish communication with it. The flashing “CALL” indicator of
the selected handset zone will turn steady.
4. Additional callers can be added into the communication channel by pressing its “SELECT” button.
5. To disable Privacy Mode and allow all callers to participate in the communication, press the “P IVACY MODE” button. The
“P IVACY LINE ON” indicator turns off. The system is now in conference mode and all new callers will be able to participate in
the conversation.
Master
Model: V25-71
Features
- Battery charging and supervision
- Digital Volt and Amp meter
- AC/ DC fuse protection
- Float and boost charge mode
- Auto boost charge cut off
- Internal AC mains switch & fuse
Specification
Size: 110 (w) x 316 (h) x 110 (d) mm
Weight: 1750 gram
Material: 16 gauge sheet steel
Finish: Powder coated paint, beige
white
Input: 230 VAC
Output: 28.8 V ± 0.5 VDC, 4A*
DC Fuse: 5A*
Battery Fuse: 3A*
Output Fuse: 1A*
Configuration
One module per system, compulsory
* atings for system above 80 zones
available on request
Common Trouble Indicator Module
Model: V25-72
Features
- System fault annunciator
- Common fault indicator
- Audible buzzer
- Call, Busy, eady tone generator
- Supervisory circuit
Specification
Size: 110 (w) x 316 (h) x 52 (d) mm
Weight: 350 gram
Material: 16 gauge sheet steel
Finish: Powder coated paint, beige
white
Input: 15 VDC
Quiescent current: approx. 25mA
Lamp Test Current: approx. 200mA
Configuration
One module per system, compulsory
V25-70 EMERGENC VOICE COMMUNICATION S STEM COMPONENTS

Master
Model: V25-73
Features
- Master Handset
- CPU circuit
Specification
Size: 110 (w) x 316 (h) x 100 (d) mm
Weight: 630 gram
Material: 16 gauge sheet steel
Finish: Powder coated paint, beige
white
Handset: ed Hi-impact ABS plastic
Input: 24 VDC
Quiescent current: 20mA
ing Tone: 2 kHz
Microphone: Carbon
Output impedance: 300 -1K ohm
Frequency esponse: 200 – 3450 Hz
Configuration
One module per system, compulsory
Handset Zone Selector Module
Model: V25-74
Features
- Support 10 emote Handsets
- One press operation
- Individual Call and Fault indicators
- Individual Select buttons
Specification
Size: 110 (w) x 316 (h) x 100 (d) mm
Weight: 510 gram
Material: 16 gauge sheet steel
Finish: Powder coated paint, beige
white
Input: 15 VDC
Quiescent current: approx. 25mA
Lamp test Current: approx. 200mA
Configuration
One module for every ten emote
Handsets, compulsory
Note: equires one Line Supervisory
Card (V25-74.1, not shown) for each
connected emote Handset .
Remote Handset
Model: V25-75
Features
- Housed in heavy gauge steel
- Lockable housing with breakglass
door release
- Top and bottom entry
- etractable cord
Specification
Size: 180 (w) x 386 (h) x 88 (d) mm
Weight: 3950 gram
Material: 16 gauge sheet steel
Finish: ed enamel coating
Handset: ed Hi-impact ABS plastic
Input: 15 VDC
Quiescent current: 20mA
ing Tone: 2 kHz
Microphone: Carbon
Output impedance: 300 -1K ohm
Frequency esponse: 200 – 3450 Hz
Configuration
Quantity depends on site requirement,
compulsory
Portable Handset and Remote Socket
Model: V25-75.1J
Features
- Portable Handset with jack
Specification
Size: 110 (w) x 316 (h) x 100 (d) mm
Weight: 630 gram
Handset: ed Hi-impact ABS plastic
See V25-72 for elect. specification
Configuration
Depends on project requirement.
Model: V25-75.1SK
Features
- Surface and flush mounting type
Specification
Material: 16 gauge stainless steel
Surface: 85 (w) x 85 (h) x 40 (d) mm
Flush: 80 (w) x 85 (h) x 40 (d) mm
Weight: 350 gram
Configuration
Depends on project requirement
V25-70 EMERGENC VOICE COMMUNICATION S STEM COMPONENTS

V25-70 EMERGENC VOICE COMMUNICATION S STEM
- OPTIONAL COMPONENTS
Cassette Interface Module
Model: V25-79
Features
- Auto recording (option to start re-
cording when either Fire Alarm is
activated or when Master Handset
is raised)
- Digital time lapse indicator
- Simultaneous recording of handset
conversation and Public Address
announcements
- Cassette status monitoring
Specification
Size: 110 (w) x 316 (h) x 100 (d) mm
Weight: 630 gram
Material: 16 gauge sheet steel
Finish: Powder coated paint, beige
white
Input: 24 VDC
Quiescent current: 200mA
Configuration
Optional. Module includes cassette
deck, mounted externally (not shown)
Master Control Panel Cassette Recorder
4 pair telephone cable
1 pair DC cable
2 core screen audio cable
2 core 1.5mm
2
cable
Remote Handsets
System Cabling Guide
MASTER CONTROL PANEL
- CONFIGURATION GUIDE
Model of Master Control Panel: V25-70/x
where x is the total numbers of module space required.
The module space is determined as follows:
1. Compulsory module space = 3
2. Add module space for Handset Zone Selector
Module, V25-74 (one V25-74 module
connects up to 10 handsets)
3. Add Optional Cassette Interface Module, if re-
quired.
Compulsory modules: 3
Handset Zone Selector Modules: 2
(1 module for every 10 handsets)
Cassette Interface Module: 1
(opt onal)
Total module space requ red: 6
Model of Master Control Panel: V25-70/6
Distributed By:
Fire Systems Pte Ltd
21 Toh Guan oad East Tel: (65) 6515 1621
#09-12 Toh Guan Centre Fax: (65) 6515 1620
Singapore 608609 www.vanguardfire.sg
This manual suits for next models
8
Popular Conference System manuals by other brands

FrontRow
FrontRow ezRoom Installation

Clear One
Clear One AP400 Installation and operation manual

Black Box
Black Box JPM1105A manual

Clear One
Clear One Converge Pro TH20 Installation and operation manual

Silvercrest
Silvercrest SBTF 10 A1 operating instructions

Clear-Com
Clear-Com EclipseHX quick start guide

AST RESEARCH
AST RESEARCH AST-3780 user manual

TANDBERG
TANDBERG 3000 Addendum to user's manual

Aethra
Aethra vega X7 Use and installation manual

VIS-A-VIS
VIS-A-VIS VITALINQ 94A-07 Operation and installation manual

Polycom
Polycom CX8000 Setting up

COMMUNICATIONS-APPLIED TECHNOLOGY
COMMUNICATIONS-APPLIED TECHNOLOGY ICRI/2P Setup and operating procedures