Vanguard V5 User manual

V5
Operator’s Manual
Fire Alarm Panel
(AVF&LCD)

O&M-V5-FAP-AVF-LCD R0
Operator’s Manual (Fire Alarm Panel c/ AVF & LCD)
Pg 1 of 21
CONTENTS
1. GENERAL
1.1 Introduction 2
1.2 System Description 2
1.2.1 Zone Detection Module 3
1.2.2 System Control Module 3
1.2.3 LCD Event Logging Module 5
2. OPERATING INSTRUCTIONS
2.1. Normal Operating Conditions 5
2.2. Fire Alarm Condition 6
2.2.1. Silencing the Alarm Bells / Sounders 6
2.2.2. Resetting the System 7
2.3. Fault Condition 7
2.3.1. Silencing the Fault Buzzer 7
2.3.2. Resetting the System 7
2.4. Initiating Evacuate Alarm 8
2.4.1. Silencing Evacuate Alarm 8
2.5. Zone/Auxiliary Disable 8
2.6. Indicators Test 8
2.7 Alarm Verification Feature (AVF) 8
2.8 LCD Event Logging Module (LLM) 9
2.8.1 MENU Function 9
3. ROUTINE MAINTENANCE
3.1. Introduction 12
3.2. Maintenance Responsibilities 12
3.3. Operator Duties – Log Records 12
3.4. Regular Testing and Inspection 12
3.4.1 Daily Check 12
3.4.2 Weekly Test 13
3.4.3 Monthly Test 13
3.4.4 Annual Test 14
4. FAULT FINDING TIPS 16
5. TECHNICAL SPECIFICATION & INSTALLATION DIAGRAM 19

O&M-V5-FAP-AVF-LCD R0
Operator’s Manual (Fire Alarm Panel c/ AVF & LCD)
Pg 2 of 21
1. GENERAL
1.1 Introduction
This manual provided only the basis operator’s information on the control and operation
of the Fire Alarm System. To ensure continuous reliability of the system, the o ner or
o ner’s representative should establish an agreement to carry out regular maintenance
of the installation ith the manufacturer or manufacturer’s representative or a
competent and qualified contractor trained to service and maintain this system.
The arrangements for maintenance should be such as ell ensure that a qualified
person is available on call at all time to provide service in the event of any fault that
develops at the installation. For the requirements of the Regular Testing and
Inspection, please refer to the section covered in this manual.
1.2 S stem Description
This Fire Alarm System utilises the V5 Fire Alarm Panel. The system may
comprise one or more alarm panel net orked together itch performs the task of
processing the input signals and thereafter transmit the output signals or initiates other
auxiliary functions. The alarm panel (s) are usually sited in the building fire command
centre or any prominent location clearly visible from the main entrance.
Input devices are used to cause a change in panel status. These devices may be the
combination of Manual Call Points (as in manual and automatic alarm system),
Heat/Smoke Detectors (as in automatic alarm systems).
Output devices are used to provide an audio & visual arning. Output devices
commonly used are alarm bells although sirens and strobe lights are sometimes used.
These three components: Input Devices, Control Panel and Output Devices form the
backbone of a Fire Alarm System.
Non-addressable Fire Alarm Systems operates on a “Zone” basis. These zones are
groups of input devices grouped in accordance to the locality they are protecting. In the
event of a Fire/Fault condition, the location here the signal had originated ill be
defined by the respective indication on the panel. It is therefore important to be familiar
ith the zoning of the protected area. A zoning diagram (or zone chart) is usually
provided for this purpose.
The Alarm Panel is provided ith a feature that continuously monitoring the continuity of
the input/detection, output/sounder circuits to ensure integrity of the system. It is also
equipped ith a battery back-up supply (lasting at least 24 hours) in the event of an
incoming supply failure.

O&M-V5-FAP-AVF-LCD R0
Operator’s Manual (Fire Alarm Panel c/ AVF & LCD)
Pg 3 of 21
1.2.1 Zone Detection Module
Indicators and Control
a) Fire (Red) : Zone in fire condition
b) Fault (Amber) : Zone detection circuit open/short fault condition
c) Disable (Amber) : Zone in disabled condition
d) Disable S itch (Blue) : To disable zone fire & fault detection circuit
(Note: Zone disable function only prior to an alarm activation.)
1.2.2 S stem Control Module
Indicators
a) Po er On (Green) : System energised by Mains and/or Standby Battery
b) Fire (Red) : General Fire Indicator, system in fire condition
c) Fault (Amber) : General Fault Indicator, system in fault condition
Zone Detection Module - ZDM
1
2
3
4
5
7
8
System Control Module - SCM
Model No. 5
V
1 2 3 4 51 2 3 4 5
Alarm CounterAlarm Counter

O&M-V5-FAP-AVF-LCD R0
Operator’s Manual (Fire Alarm Panel c/ AVF & LCD)
Pg 4 of 21
d) Disabled (Amber) : General Disabled Indicator, system in disabled
condition
e) System Fault (Amber) : Indicate Programmable Micro Controller failure
f) Fire Sent (Red) : Fire Signal to Alarm Remote Monitoring Station
activated (Optional)
g) Fire Line Trouble (Amber) : Fire Signal Line open/short (Optional)
(Note: It shall not be suppressed during the Fire Alarm condition)
h) Fault line Trouble (Amber) : Fault Signal Line open/short (Optional)
i) Sounder Fault (Amber) : Alarm sounder line open/short
(Note : It shall not be suppressed during Fire Alarm condition)
j) Earth Fault (Amber) : Field input/output ires shorted to ground
k) Auxiliary Fault (Amber) : Auxiliary supply / auxiliary supervised line open/short
l) Mains Failure (Amber) : 230V AC Mains supply failure
m) Charger fault (Amber) : Charger Fuse blo n / charger voltage (lo / high)
n) Battery Fault (Amber) : Battery supply disconnected / battery fuse blo n /
battery voltage (lo / high)
o) Alarm Counter (3x7Seg.) : Indicate that number of alarm (false) been activated
(for FALSE Alarm Management)
p) AVF Off (Amber) : Indicate that AVF function been set off
q) Retard State (Amber) : Indicate that system in Retard State
r) Confirmation State (Amber) : Indicate that system in Confirmation State
Control Switches
a) Buzzer Silence (Black) (1) : To silence fault buzzer (Audio & Visual)
b) Sounder Silence (Amber) (2) : To silence alarm sounder (Audio & Visual)
c) System Reset (Bro n) (3) : To normalise the system
(Note: Silence alarm sounder before RESET)
d) Indicators Test (White) (4) : To test the orking condition of all LED
indicators and buzzer
e) Auxiliary Disable (Blue) (5) : To disable auxiliary output control function
(Audio & Visual)
f) Sound Alarm (Red) (6) : To raise alarm sounder manually for
emergency evacuation (Audio & Visual)

O&M-V5-FAP-AVF-LCD R0
Operator’s Manual (Fire Alarm Panel c/ AVF & LCD)
Pg 5 of 21
1.2.3 LCD Event Logging Module
Indicators
a) Po er On (Green) : System energised by Mains and/or Standby Battery
b) Processor Fault (Amber): Indicates that Micro Processor Unit failure in processing
c) LCD Display : To display the Panel Status and the Alarm / Fire event c/
date and time (20 Characters x 4 Lines)
Control Switches
a) Escape (Yello ) : To exit from current function / screen
b) Menu (1) (Green) : To access other level of function or pass ord key as “1”
c) Up (2) (White) : To move cursor up / page up or pass ord key as “2”
d) Do n (3) (Blue) : To move cursor do n / page do n or pass ord key as “3”
e) Enter (Red) : To select / accept the function / setting
2. OPERATING INSTRUCTIONS
2.1 Normal Operating Conditions
Under normal operating conditions
a) The “POWER ON” LED (Green) lighted
b) No other indicator shall be lighted
c) The panel and all alarms should be completely silent
d) LCD display sho n as
(07/04/06: 7th April 2006, M000: “Main” panel address “000”, 20:06: 8:06PM)
LCD Event Logging Module - LLMLCD Event Logging Module - LLM
FIRE ALARM SYSTEM
07/04/0 M000 20:0
FIRE ALARM SYSTEM
07/04/0 M000 20:0

O&M-V5-FAP-AVF-LCD R0
Operator’s Manual (Fire Alarm Panel c/ AVF & LCD)
Pg 6 of 21
2.2 Fire Alarm Condition
The panel / system shall enter into an alarm condition hen an input device (such as
smoke/heat detector, call point; or pressure/flo s itch) is activated.
Under Fire Alarm conditions:
a) T in “FIRE” LEDs (Red) of the alarm zone lighted
b) General, “FIRE “ LED (Red) lighted
c) A “Fire sent” LED (Red) lighted (If Alarm Monitoring Station is connected)
d) Panel Alarm Buzzer sound
e) External alarm bells/sounders activated
f) Signal sent to alarm monitoring station (If Alarm Monitoring Station is connected)
g) Auxiliary functions activated (eg: Lift homing, AHU shutdo ns)
h) LCD display sho n as (Individual Fire event – latched and recorded)
(001EC: Current Event Counter “001”, Fire)
(01: 1st event of 001EC, M00Z002: “Main” panel address “000” Zone “002” Fire, at 14:49: 2:49PM)
i) For multiple fire events, it shall be displayed by manual action (Up / Do n key)
2.2.1 Silencing the Alarm Bells / Sounders
It is a requirement under the Singapore standard Code of Practice CP 10: 2005 that the
first alarm can only be silenced after 3 minutes of continuous operation and any
subsequent alarms may be silenced immediately. Any attempts to silence the first alarm
during the initial 3 minutes of operation ill have no effect on the system.
The Sounder Silence LED ill flash hen the 3 minutes is lapsed; to indicate alarm
silencing is permit-able. To silence the alarm upon expiry of the initial 3 minutes and any
subsequent alarm, carry out the follo ing procedure:
a) Press “SOUNDER SILENCE” S itch (Amber) (2)
b) Sounder Silence LED becomes steady
c) External alarm bells/sounders silence
d) To silence Alarm Buzzer, press “BUZZER SILENCE” S itch (Black) (1)
e) Panel remains in fire state until reset
001EC FIRE
01 M00Z002 14:49

O&M-V5-FAP-AVF-LCD R0
Operator’s Manual (Fire Alarm Panel c/ AVF & LCD)
Pg 7 of 21
2.2.2 Resetting the S stem
Before the system is reset, the cause of the alarm must be investigated and duly
rectified. In the case of a false alarm, make sure that there is no incident of fire before
resetting the system.
Note : It is not possible to reset the system before the alarm is silenced.
a) Re-instate the affected devices to normal
b) Press “System Reset” S itch (Green) (3)
c) Upon resetting, the system should resume to normal operating condition, if there are
no other events to cause another alarm and the original cause of the alarm being
rectified.
2.3 Fault Conditions
A self diagnostic circuit are provided to check itself and indicates a ide range of
possible faults.
Under Fault Conditions:
a) The respective zone fault Amber LED lighted and/or
b) The respective system fault Amber LED lighted
c) General, amber “FAULT” LED lighted
d) Panel fault buzzer sound
e) LCD display sho n as (Common Fault – non-latching)
(07/04/06: 7th April 2006, M000: “Main” panel address “000”, 10:06: 10:06AM)
2.3.1 Silencing the Fault Buzzer
If the fault cannot be rectified, it may be silenced by:
a) Press “BUZZER SILENCE” S itch (Black) (1)
b) Buzzer Silence Amber LED lighted
c) Panel remains in fault state until fault rectified
2.3.2 Resetting the S stem
The cause of the fault should be investigated and rectified. If it is due to a mains supply
failure, the system ill normalise hen the mains supply resumes. Some faults are
internal to the system and are not covered in this manual. Once the fault(s) are rectified,
the panel shall be normalised.
FAULT
07/04/0 M000 10:0

O&M-V5-FAP-AVF-LCD R0
Operator’s Manual (Fire Alarm Panel c/ AVF & LCD)
Pg 8 of 21
2.4 Initiating Evacuate Alarm
The system is provided ith a “Sound Alarm” s itch in the event of emergency.
To sound alarms for emergency evacuate:
a) Press “Sound Alarm” s itch (Red) ( )
b) Sound Alarm amber LED lighted
c) External alarm bells/sounders activated
2.4.1 Silencing Evacuate Alarm
To silence the evacuate alarm:
a) Re-press the “Sound Alarm” S itch (Red) ( )
b) External alarm bells/sounders silenced
2.5 Zone/Auxiliar Disable
This function is executed hen disable of the respective zone(s) and/or auxiliary
functions is intended. Zone disable s itches ill render the respective zone(s) in-
operative and ill not be affected by the change in condition of the related input
device(s).
Note : It is not possible to perform a zone disable hen an fire alarm condition has
already occurred in the respective zones.
To carry out zone/auxiliary disablement:
a) Press “Disable” for zone respectively or “Auxiliary Disable” S itch (Blue) (5)
b) Disabled amber LED lighted
c) General, “Disabled” amber LED lighted
d) Zone(s)/auxiliary function remains in Disable Condition until normalised
2.6 Indicators Test
An “Indicators Test” s itch is provided to test the orking condition of the visible
(LEDs) and audible (Buzzer) indicators.
a) Press the momentary “Indicators Test” S itch (White) (4)
b) All the LED indicators lighted and Buzzer sounds
c) Release the s itch to normalise
2.7 Alarm Verification Feature (AVF)
Alarm Verification Feature (AVF) is provided to reduce the alarm caused by the transient
environmental conditions. AVF feature is only subjected to the auto detection zones (e.g.
Smoke, Heat). Alarm Counter (max 999) is incorporated to record the number of alarm
activation been filtered by AVF.
Under Auto Detection Zone (been set to AVF mode) goes into alarm
a) T in “FIRE” LEDs (Red) of the alarm zone lighted and panel ill reset itself
automatically
b) Alarm Counter increase One count
c) “RETARD STATE” LED (Amber) lighted (20sec)

O&M-V5-FAP-AVF-LCD R0
Operator’s Manual (Fire Alarm Panel c/ AVF & LCD)
Pg 9 of 21
d) No outputs are activated (FIRE output, external Alarm Bells/ Aux output)
e) When Retard State (20 sec) lapses, Retard State LED go off
f) “CONFIRMATION STATE” LED (Amber) lighted (120sec)
During Confirmation State (120sec)
a) If no alarm activated, panel back to normal condition itself hen Confirmation State (120 sec)
expire
b) If any zone goes into alarm, panel goes into FIRE condition
2.8 LCD Event Logging Module (LLM)
LCD Event Logging Module (LLM) is provided as add on feature to display and record
the activated alarm zone information complete ith date and time.
LLM is integrated ith non-volatile memory (EEPROM) to store and record the activated
alarm zone event up to 999, it ill not be lost even the system total po er failure. The
recorded zone alarm event are essential for the FALSE ALARM MANAGEMENT.
LLM is also incorporated ith backup battery for real time clock, it ill be continuous
running during the system total po er failure.
LLM is operated by Micro Controller Processor Unit, it is fully supervised and monitored
for the soft are processing. In the events of Processor fault, and audio & visual signal
ill be given. The failure of the Porcessor will not impair the Primary Function of
the Fire Alarm System.
2.8.1 MENU Function
It is provided easy and user friendly operation.
MENU
VIEW FIRE ARCHIVE
PRINT FIRE ARCHIVE
SETUP
PNL ADR
TIME
DATE
DELETE
PRINTER

O&M-V5-FAP-AVF-LCD R0
Operator’s Manual (Fire Alarm Panel c/ AVF & LCD)
Pg 10 of 21
2.8.1.a VIEW FIRE ARCHIVE
To vie the recorded alarm zone event;
a) Press “Menu”
b) Select “VIEW FIRE ARCHIVE” by “Up” / “Do n” key and press “Enter”
(017TC: Total Event Counter “017”, Fire)
(017: 17th event of 017TC, M00-Z005: “Main” panel address “000” Zone “005” Fire) at
(02/04/06: 2nd April 2006, 15:32:12: 3:32:12PM)
c) The rest recorded event are able to vie by manual action (Do n/Up key)
2.8.1.b PRINT FIRE ARCHIVE
To print the recorded alarm zone event;
a) Connect the Printer
b) Press “Menu”
c) Select “PRINT FIRE ARCHIVE” by “Up” / “Do n” key and press “Enter”
Print start from (017/TC017: 17th event of Total Event Counter “017”)
d) Select the starting event by “Up” / “Do n” key and
e) Press “Enter”, Printer ill start print the back ard event until the last event
“000” and stop
f) During the printing: to stop the print, press “Escape”
2.8.1.c SETUP
To setup the panel;
a) Press “Menu”
b) Select “SETUP” by “Up” / “Do n” key and Press “Enter”
c) Select the required setup function by “Up” / “Do n” key and Press “Enter”
017TC FIRE
017 M00-Z005
02/04/0 15:32:12
PRINT FROM
017/TC017
PNL ADR
TIME
DATE
DELETE
PRINTER

O&M-V5-FAP-AVF-LCD R0
Operator’s Manual (Fire Alarm Panel c/ AVF & LCD)
Pg 11 of 21
(1) PNL ADR: To set the Panel Address, select by “Up” / “Do n” key and
press “Enter” to save
(e.g. M000: Main Panel Address 000, S001: Sub Panel Address 001)
(2) TIME: To set the Time, select the time by “Up” / “Do n” key and
press “Enter” to save (Hour:Minute:Second – 24Hr System)
(3) DATE: To set the Date, select the Date by “Up” / “Do n” key and
press “Enter” to save (Day:Month:Year)
(4) DELETE: To delete the recorded event, key in the pass ord and press
press “Enter” (Delete all recorded event)
(Pass ord and Access Level control is provided to prevent unauthorized
system control and alteration of alarm event recorded.)
(5) PRINTER: To Enable / Disable the printer for on-line printing,
select Enable / Disable by “Up” / “Do n” key and
press “Enter” to save
PANEL ADDRESS M000
PRESS ENTER TO SAVE
HH:MM:SS
19:4 :22
DD/MM/YY
10/04/0
?????
PASSWORD
PRINTER
[ENABLE] DISABLE

O&M-V5-FAP-AVF-LCD R0
Operator’s Manual (Fire Alarm Panel c/ AVF & LCD)
Pg 12 of 21
3. ROUTINE MAINTENANCE
3.1 Introduction
To ensure continuous reliability of the fire alarm system, regular testing and servicing
shall be carried out. Only trained and competent personal are allo ed to performance
the routine testing and maintenance.
3.2 Maintenance Responsibilities
The o ner shall appoint a competent person to supervise and coordinate all matters in
relation to the fire alarm systems. This include arranging for the system to be checked,
tested and serviced in accordance ith the requirements as described in the Singapore
Standard CP 10 : 2005 – Code of Practice for the installation and Servicing of Electrical
Fire Alarm Systems.
3.3 Operator Duties – Log Records
The operators / o ner appointed competent person shall also be responsible for
keeping all the log records for all alarms activation (genuine, practice, test or false),
faults, service tests and routine preventive maintenance, repair and alteration orks
carried out on the fire alarm system.
3.4 Regular Testing and Inspection
The follo ing regular testing and inspection procedures are recommended:
3.4.1 Daily Check
3.4.2 Weekly Test
3.4.3 Monthly Test
3.4.4 Annual Test
3.4.1 Daily Check
A check should be made everyday to ascertain if the system is operating normally.
Fault(s) detected should be recorded and steps taken immediately to ensure that the
fault(s) is rectified.
a) Check that only the green “POWER ON” LED is lighted. All other indicators should
be off and the panel completely silent. If a fault has occurred and the panel buzzer
sounding, the appropriate indicator ill light up.
b) Record the fault (s) detected.
c) Determine the area affected by the fault and decide hether special actions (such as
fire patrols) are required in that area.

O&M-V5-FAP-AVF-LCD R0
Operator’s Manual (Fire Alarm Panel c/ AVF & LCD)
Pg 13 of 21
d) If possible, determine the cause of the fault or note the activities immediately prior to
the area affected.
e) Silence the fault buzzer.
f) Inform the maintenance contractor responsible for servicing and arrange for repair.
3.4.2 Weekl Test
The follo ing tests and checks should be made by the operator or by the maintenance’s
contractor responsible for servicing and performance of the system.
a) Carry out a simulated and transmission of fire alarm and faults signals to the
monitoring station and confirm it is functioning correctly.
Note : It ill be necessary to contact the alarm monitoring company prior to
transmitting of the simulated fire alarm and faults signals being tested and also to
check ith the monitoring company after completion of test to ensure that the fire
alarm and faults signal as received and advise them the system reset.
b) Check the battery condition and the voltage reading by the use of a multi-meter.
c) On completion of the above tests, ensure that all s itches are in the correct
operating position.
d) Rectify all faults (if any) immediately.
e) Enter the test result(s) and follo -up actions in the log record.
3.4.3 Monthl Test
In addition to the eekly test, the follo ing checking and testing procedures are to be
carried out each month.
a) Simulate fire and fault condition in all zones one by one. The procedure of the
simulation should follo section 2 (operating instruction) of this manual. Confirm ith
the monitoring station that the fire alarm and fault signals have been received.
b) Remove the bell line fuse. The buzzer should sound together ith “SOUNDER
FAULT” and both amber “O” indications lighted. The panel should be silenced hen
“BUZZER SILENCE” is activated. Replace the bell line fuse. System should
normalise.
c) Disable a zone in accordance to the procedures as described in section 2.5. Active a
device in that respective zone. It should have no alarm signal activated on the
panel. Normalise the disable zone.

O&M-V5-FAP-AVF-LCD R0
Operator’s Manual (Fire Alarm Panel c/ AVF & LCD)
Pg 14 of 21
d) Check charger voltage and battery terminals condition. Ensure that no faults signal
are indicated on the panel.
e) Disconnect the battery supply. The “POWER ON” and “BATTERY FAULT”
indicators should be lighted and the buzzer sounding. Connect back the battery and
system should normalise itself.
f) S itch off incoming mains supply. The “POWER ON”, “MAINS FAULT” and
“CHARGER FAULT” indicators should be lighted and the buzzer sounding. The
standby battery should take over the supply to the system. Resume the mains
supply and system should normalise itself.
g) Check earth leakage function by applying a short bet een the positive leg of the
detector line and earth (chassis). The buzzer should sound together ith “EARTH
FAULT” and red “+” indication lighted. Repeat, using the negative leg of the detector
line. The buzzer should sound together ith “EARTH FAULT” and amber “-“
indication lighted.
h) Check that the panel is in a clean and operative condition.
i) Visually inspect the condition of the components, terminations and cables.
j) Ensure that all faulty parts are satisfactorily replaced and recorded. Enter in the log
record any fault(s) that require repair.
k) Check that all s itches are return to their operating positions after test.
l) Enter the test results and follo -up actions, if any, in the log record.
3.4.4 Annual Test
The annual checks should include all the inspections and testing procedures specified
in sections 3.4.1, 3.4.2, 3.4.3. and the follo ing:
a) The maintenance/servicing personnel should arrange to check the operation of at
least 20 percent of the detectors in an installation each year. The selection of
detectors to be tested should be spread over as many zones as possible and should
be made in such a ay that all detectors in an installation should have been checked
at least once in 5 years.
The checking of the detectors should take the form of in situ testing to ensure it is
operational.
b) Circuits connecting ancillary equipment hich require automatic voltage regulated
supplies should be checked to ensure correct operation and voltage output.

O&M-V5-FAP-AVF-LCD R0
Operator’s Manual (Fire Alarm Panel c/ AVF & LCD)
Pg 15 of 21
c) Where the heat-sensitive element of thermal detectors or the enclosure of other
detectors are found to be coated ith paint or any material likely to affect the
operation of the detectors, such material should be cleaned off or if necessary have
the detector replaced.
Note: In certain environments it may be necessary to clean and test the smoke
detectors at more frequent intervals.
d) Enter the test results and follo -up actions, if any, in the log record.

O&M-V5-FAP-AVF-LCD R0
Operator’s Manual (Fire Alarm Panel c/ AVF & LCD)
Pg 16 of 21
4. FAULT FINDING TIPS
CHECK LIST
FAULT Specific
Indication Possible Causes
ACTION SHOULD
BE TAKEN
- Manual Call-point - Vandalise
- Glass Broken
- Heat / Smoke
Detector
- Environment
- Faulty
- Flo S itch - Leakage
- Misused
- Sub Alarm Panel - Activated
Zone Fire
(False Alarm)
- EOL Resistor - Shall be 6.8K Ohm
- Inspect the alarm
activated zone
IF FALSE ALARM
1. Check the possible
causes and rectified the
problem
2. Press “Sounder
Silence” (Yello -2)
(After 3 min alarm)
3. Press “Reset”
(Green-3)
If unable to Reset
1. Press “Buzzer
Silence” (Black-1)
2. Press “Sounder
Silence” (Yello -2)
(After 3 min alarm)
3. Call for service
“LS” (Red) - Line Short
(@ back of ZDM)
- Zone line - Line short circuit
- Zone line - Line open circuit
- Zone Detector - Missing / Removed
- Zone Termination - Loose
- Sub Alarm Panel - Fault at Sub Panel
Zone Fault
If not,
May be Line Open
- EOL Resistor - Shall be 6.8K Ohm
All Zone Fault - Detector Fuse - Blo n
- Alarm Fuse - Blo n
- Termination - Loose
- EOL Resistor - Shall be 6.8K Ohm
Alm-1 / Alm-2
“O” (Amber) - Open
(@ FBM)
- Alarm line - Open circuit
- Alarm line - Connection reversed
- Short circuit
Sounder Fault
Alm-1 / Alm-2
“S” (Red) - Short
(@ FBM) - Bell / Sounder - Polarized Bells /
Sounders shall be used
- Connection reversed
- Faulty
1. Press “Buzzer
Silence” (Black-1)
2. Check the possible
causes and rectified
3. When fault is
rectified, back to normal
If unable to normalise
1. Call for service
Tip: To segregate, the
fault caused by either
Line or Panel problem:
1. Dismantle the line
2. Terminate ith EOL
Resistor
Fault clear,
- LINE problem
Fault remains,
- PANEL problem

O&M-V5-FAP-AVF-LCD R0
Operator’s Manual (Fire Alarm Panel c/ AVF & LCD)
Pg 17 of 21
CHECK LIST
FAULT Specific
Indication Possible Causes
ACTION SHOULD
BE TAKEN
Earth “+VE” (Red)
(@ FBM)
- One or more Field
“+VE” line and/or
- Alarm “–VE” line
(in normal condition)
Earth Fault
Earth “-VE” (Amber)
(@ FBM)
- One or more Field
“-VE” line and/or
- Alarm “+VE” line
(in normal condition)
- Shorted to Chassis /
Trucking / Conduit
1. Press “Buzzer
Silence” (Black-1)
2. Dismantle all the
Line accordingly ith
proper marking
3. Terminate back the
lines one by one to
trace the faulty lines
4. Rectify the fault.
5. When fault is clear,
back to normal
If unable to normalise
1. Call for service
- Aux Fuse - Blo n “Aux Fuse” (Amber)
(@ FBM) - Auxiliary Output - Over loaded
- Line shorted
Auxiliary Fault
Alm-2 “O” / “S”
(@ FBM)
- Alarm-2 output is used for Auxiliary
(Option as provided)
- Refer to “Sounder Fault” for fault finding
- AC 230V Mains - Failure
- AC Fuse - Blo n
- AC S itch - OFF position
Mains Failure
Charger Fault
- “Mains Failure”
(Amber)
- “Charger Lo /
Fuse” (Amber)
(@ PSM)
- Termination - Loose
- Charger Fuse - Blo n
- System total load - Over loaded
“Charger Lo /
Fuse” (Amber)
(@ PSM) - System Voltage - Lo < 21V
Charger Fault
“CH/BAT High” (Red)
(@ PSM)
- System Voltage - High > 30V
- Battery Fuse - Blo n
- Termination - Loose
- Cable shorted
- Connection Reversed
“Battery Lo / Dis.”
(Amber)
(@ PSM)
- Battery - Lo > 21V
- Faulty
Battery Fault
“CH/BAT High” (Red)
(@ PSM)
- System Voltage - High > 30V
1. Press “Buzzer
Silence” (Black-1)
2. Check the possible
causes and rectified
3. When fault is
rectified, back to normal
If unable to normalise
1. Call for servicing
Remark:
1. Fuse shall be
replaced ith Rated
Fuse as accordingly.
2. System normal
operating voltage shall
be DC 27.5V.
(Adjustable by VR1 @
PSM)

O&M-V5-FAP-AVF-LCD R0
Operator’s Manual (Fire Alarm Panel c/ AVF & LCD)
Pg 18 of 21
CHECK LIST
FAULT Specific
Indication Possible Causes
ACTION SHOULD
BE TAKEN
- Fire signal Line - Disconnected “1” (Amber) - Open
(@ DIM) - Termination - Loose
- Fire signal Line - Shorted
Fire Line Trouble
(Alarm Monitoring
Station) “1” (Red) - Short
(@ DIM) - Alarm Monitoring
Transmitter Panel
- Faulty
- Fault signal Line - Disconnected “2” (Amber) - Open
(@ DIM) - Termination - Loose
- Fault signal Line - Shorted
Fault Line Trouble
(Alarm Monitoring
Station) “2” (Red) – Short
(@ DIM) - Alarm Monitoring
Transmitter Panel
- Faulty
1. Press “Buzzer
Silence” (Black-1)
2. Check the possible
causes and rectified
3. When fault is
rectified, back to normal
If unable to normalise
1. Call for service
Remark:
Fire and Fault signals
are connected to Alarm
Monitoring Transmitter
Panel only at Main
Alarm Panel hen
required.
(This function is
provided as an option
hen required)
Legend:
ZDM
FBM
SCM
PSM
DIM
: Zone Detection Module
: Fire Base Module
: System Control Module
: Po er Supply Module
: DECAM Interfacing Module
LS
O
S
EOL
: Line Short
: Open circuit
: Short circuit
: End Of Line Resistor

O&M-V5-FAP-AVF-LCD R0
Operator’s Manual (Fire Alarm Panel c/ AVF & LCD)
Pg 19 of 21
V5
Technical Specification
and
Installation Diagram
Other manuals for V5
1
Table of contents
Popular Smoke Alarm manuals by other brands

LST
LST ÜMM-55000-833 Specification sheet

Flexit
Flexit SP445 installation instructions

Notifier
Notifier CP-651E Installation and maintenance instructions

Ei Electronics
Ei Electronics MCP401RC User instructions

SCS Sentinel
SCS Sentinel DAAF-10Y-CE Installation and use instruction

FireClass
FireClass DUO-CEL Installation & commissioning manual