©Vantage, 8/17/2016 / IS-0585-B WireLink and RadioLink DIN LVRS — MODEL: LVRS8-DIN & STOLER821 page 1 of 2
INSTALLATION
VANTAGECONTROLS.COM VANTAGE INSTALL GUIDES
2168 West Grove Parkway, Suite 300, Pleasant Grove, UT. 84062 USA
Telephone: 801 229-2800 ●Fax: 801 224-0355 WireLink and RadioLink DIN LVRS — MODEL: LVRS8-DIN & STOLER821
Overview
Vantage’s DIN Low Voltage Relay Station WireLink™ model,
LVRS8-DIN and RadioLink™ model, STOLER821 feature 8 isolated,
latching relay channels for switching low voltage or dry contact
closures to third party systems or devices. The DIN LVRS does not
produce or provide any power. Each relay is single-pole, double-
throw, which offers a normally closed, normally open set of
contacts for each relay. Each relay has an actuator button on the
front of the LVRS which toggles the relay and is useful for testing
wiring and operation without programming the system. Some
examples for using a DIN LVRS would be: draperies, pumps, garage
doors, HVAC dampers, lifts, screens, pool covers, sprinklers,
showers, baths, security systems, etc.
Station Specifications
Description Specification
Dimensions, HWD 85.7mm x 157.2mm x 61.9mm
3.38” x 6.19” x 2.44”
Weight 201g
Mounting 35 mm DIN Rail (EN 50 022: 1977)
Relay Inputs 8
Relay Actuators 8
Max. Current @ Relay 1A
Max. Voltage @ Relay 48VAC / 30VDC
Min. Voltage @ Relay 0VAC / 0VDC
Lightning Surge
Protection Low Voltage ITU-T K.20
Station Wiring
configuration Daisy-chain/Star/Branch
Station Bus Specification
2C, 16AWG / 1.31mm2, twisted, non-
shielded, <30pF per foot. Separate a
minimum of 12" / 30.5cm from other
parallel communication and/or high
voltage runs.
Station Equivalent
InFusion 0.5W on IC-24 / 0.5W on IC-36
Station Equivalent QLink 1 Station
Station Equivalent
RadioLink 1 Station on RadioLink Systems
Station Bus connections* 24V / 36V Station Bus
LED Indicators Status and Load State
Ambient Operating
Temperature 0-35°C / 32-95°F
Ambient Operating
Humidity 5-95% non-condensing
CE, UL and CUL Listed YES
*CAUTION: 36V stations have a symbol on the Serial Number
sticker. Any station, not displaying this symbol, should not be
connected to a 36Volt Station Bus.
Software/Firmware
The WireLink model is compatible with InFusion Design Center
software or QLink 3.5 and Controller Firmware 6.5 or higher. The
RadioLink model is compatible with InFusion Design Center or
QLink 4.0 and Controller Firmware 7.0 or higher. For new projects
it is recommended that firmware and software be kept to the most
current release.
Installation/Mounting
Installation of Vantage products should be performed or
supervised by a Certified Vantage Installer. The Low Voltage Relay
Station installation is very simple. There are two methods of
connecting the Station Bus to the Low Voltage Relay Station for
the WireLink model:
a. Using the 2 wire pigtail connection located on the top of the
DIN LVRS
b. Using the pins on the side of the Station to pass Station Bus
(see Drawing) Part #VDC-0197
c. The RadioLink model needs a power supply connected.
Vantage part VFA-0008, 12 Volt Plug-in Supply for use with
RadioLink Products 12VDC 1500mA is nominal.
d. The DIN LVRS is mounted on a standard 35 mm DIN Rail
(EN 50 022: 1977).
e. All low voltage connections to the LVRS relays are wired to
removable screw terminal connectors. These relays may be
given custom names in software to facilitate their use in the
installation.
Connecting Device Requirements
Each individual low voltage contact is rated as follows:
Maximum Current = 1A
Maximum Voltage = 48Vac / 30Vdc
Station Set Up in Software
InFusion: First select the room, then click on Vantage Objects in
the Object Explorer and expand Stations, WireLink or Stations,
RadioLink. From the list of stations double click on the DIN LVRS to
place it in the room. In the Object Editor, name the station and
make sure it is on the correct station bus port.
QLink: First change to Wiring view, right click on the Main
Controller and from the pop-up menu, select Add DIN Stations or
Add RadioLink Stations | Low Voltage Relay from the station list.
This will reveal the DIN Relay Station Definition Dialog Box. Type
the name of the Station. Click OK to exit the Definition window.
Right click on the station and select Add Low Voltage Relay to add
the relay loads. In the Relay Definition window, name the relay and
assign it to the correct floor and room.
Programming the Relay Station
Because they are relays the eight buttons on the DIN LVRS cannot
be programmed directly. Programmed Buttons, Time Controls or
Host Commands in InFusion and V-Commands in QLink are used to
control the relays. The relays are accessed by selecting the relay
load in Programming.
Configuration with Wired Models
When the station is first connected to the Station Bus, the
diagnostic LED will blink twice followed by a pause, meaning that
the station is connected correctly but not yet configured. From
Design Center, click on the Configure Stations button on the
toolbar or from QLink, select System | Configure Stations and click
on the radio Configure button in the Online Configuration section
from the pull down menu. Highlight the DIN LVRS. The Status LED
will blink 5 times followed by a pause and the button LEDs will
blink rapidly indicating that the station is in configuration mode. To
finish configuring press any button on the Station 3 times. The
station may also be configured by typing the serial number in the
project file, using this method the station will automatically be
configured when the system is programmed. Once configured the
Status LED will blink evenly and the buttons stop blinking.
Configuration with RadioLink*
RadioLink DIN LVRSRL stations need to be configured to associate
which physical station goes with the station in software.
When the station is initially powered-up, the Status LED will blink
three times followed by a pause - this means the station is
powered correctly but not yet on the network. Before uploading
the file to the Vantage system, do the following: From Design
Center, click in the Serial Number section in the Object Editor and
type in the serial number. From the menu bar in QLink, select
System/Configure Stations. A list of all stations will be displayed on
the screen. Manually enter the serial number for each RadioLink
station to match it with the corresponding programming in QLink.
The serial number of each station is located on a permanent sticker
on the front of the station. Record the number for easy reference
when programming. The Main Controller will add to its network
and configure all the RadioLink stations that it has serial numbers
for. This may take several minutes depending on the number of
RadioLink stations on the network. The Status LED will blink
steadily when a station has been added to the network and
configured.
I N S T A L L A T I O N
©Vantage, 8/17/2016 / IS-0585-B WireLink and RadioLink DIN LVRS — MODEL: LVRS8-DIN & STOLER821 page 2 of 2
NOTE: RadioLink Model – Power Input Connection is 9-12V
AC/DC, 200mA IN
RadioLink Model FCC Information
This device contains transmitter module:
FCC ID: PII-VSUB075-1
IC: 3505A-VSUB0751
This device complies with Part 15 of the FCC Rules. Operation
is subject to the following two conditions: (1) This device may
not cause harmful interference, and (2) this device must accept
any interference received, including interference that may cause
undesired operation.
Changes or modifications to this product not expressly approved
by Vantage Controls could void the user’s authority to operate
this product.
Side
Label
Enlarged
*NOTE: A new feature with Design Center 2.3 and up is the ability
to configure RadioLink stations the same way WireLink stations are
configured, e.g., 3-button press. When configuring stations, if the
Exclude RadioLink Bus check box, under Settings | System
Preferences, is not checked, all RadioLink stations go back to non-
programmed mode when the Configure Stations button on the tool
bar is clicked. The station’s LEDs will all blink while in configure
station mode. After configuring stations and clicking the Configure
Stations button again to turn configure stations mode off, all
RadioLink stations need to log back on to the system before
working as programmed. Allow time for this to occur.
Local Control
Local control of each relay is provided by pressing the
corresponding actuator button on the front of the station. This
allows testing of the DIN LVRS connections before it is
programmed. Each relay has an LED to indicate if it is in the SET or
RESET position.
Diagnostic and Test Information
Each DIN LVRS station has a status LED. The Status LED blinks
steady on and off or 2, 3 or 4 blinks followed by a pause.
One Even Blink: LVRS is operating correctly and is configured.
Two Blinks: LVRS is operating correctly but is not
configured (wired model).
Three Blinks: LVRS is not communicating with the Main
Controller, verify station bus wiring or if
RadioLink it is not yet configured.
Four Blinks: Factory problem. Please contact the factory.
Five Blinks: Configuration mode.
Line Drawings

This manual suits for next models

1

Other Vantage Hearth Relay manuals

Vantage Hearth WireLink EasyTouch II ScenePoint SR1 Series User manual

Vantage Hearth

Vantage Hearth WireLink EasyTouch II ScenePoint SR1 Series User manual

Vantage Hearth RadioLink ScenePoint RDR Series User manual

Vantage Hearth

Vantage Hearth RadioLink ScenePoint RDR Series User manual

Vantage Hearth RadioLink ScenePoint RDR1 Series User manual

Vantage Hearth

Vantage Hearth RadioLink ScenePoint RDR1 Series User manual

Vantage Hearth RadioLink ScenePoint RR1 Series User manual

Vantage Hearth

Vantage Hearth RadioLink ScenePoint RR1 Series User manual

Vantage Hearth RadioLink AccentPoint Relay Station II APREL User manual

Vantage Hearth

Vantage Hearth RadioLink AccentPoint Relay Station II APREL User manual

Popular Relay manuals by other brands

Neets 4 Relay box manual

Neets

Neets 4 Relay box manual

IFM efector100 G1503S operating instructions

IFM

IFM efector100 G1503S operating instructions

Pilz PNOZ X2.3P operating manual

Pilz

Pilz PNOZ X2.3P operating manual

Trinity Newton+ user manual

Trinity

Trinity Newton+ user manual

Siemens 3RU7116 Series operating instructions

Siemens

Siemens 3RU7116 Series operating instructions

Allen-Bradley 140G Series quick start guide

Allen-Bradley

Allen-Bradley 140G Series quick start guide

TERASAKI TemTripPRO instruction manual

TERASAKI

TERASAKI TemTripPRO instruction manual

Sonoff Sonoff-BASICR3 user manual

Sonoff

Sonoff Sonoff-BASICR3 user manual

LS DMP Series instruction manual

LS

LS DMP Series instruction manual

Pilz PNOZ e3.1p operating instructions

Pilz

Pilz PNOZ e3.1p operating instructions

Moeller ETR4-70A installation instructions

Moeller

Moeller ETR4-70A installation instructions

Plejd LED-10 installation manual

Plejd

Plejd LED-10 installation manual

ABB CM-MSS Safety instruction

ABB

ABB CM-MSS Safety instruction

Pepperl+Fuchs KD0-RSH-1.1E.1 Series manual

Pepperl+Fuchs

Pepperl+Fuchs KD0-RSH-1.1E.1 Series manual

Leuze MSI-TR1B Original operating instructions

Leuze

Leuze MSI-TR1B Original operating instructions

Eaton EDR-5000 Installation, operation and maintenance

Eaton

Eaton EDR-5000 Installation, operation and maintenance

Honeywell NOTIFIER FW-RM Installation and maintenance instructions

Honeywell

Honeywell NOTIFIER FW-RM Installation and maintenance instructions

gefran GS quick start guide

gefran

gefran GS quick start guide

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.