Vega VEGAPULS 61 Series User manual

2VEGAPULS 61
37991-EN-200303
Contents
1 Area of applicability................................................................................................................. 4
2 General information................................................................................................................. 4
3 Importantspecicationinthetypecode............................................................................... 5
4 Technicaldata .......................................................................................................................... 6
5 Applicationconditions ............................................................................................................ 7
6 Protection against static electricity ....................................................................................... 8
7 Use of an overvoltage arrester ............................................................................................... 9
8 Grounding................................................................................................................................. 9
9 Impactandfrictionsparks ...................................................................................................... 9
10 Material resistance .................................................................................................................. 9
11 MountingwithexternaldisplayunitVEGADIS61/81............................................................ 9
12 Removingandreplacingtheredthreaded/dustcover ...................................................... 10
Supplementary documentation:
• Operating Instructions VEGAPULS 61
• EU-type approval certicate PTB 03 ATEX 2089 X (Document ID: 37990)
• EU declaration of conformity (Document ID: 43634)
Editing status: 2020-02-28

3
VEGAPULS 61
37991-EN-200303
DE Sicherheitshinweise
für den Einsatz in explosionsgefährdeten Bereichen
EN Safety instructions
for the use in hazardous areas
FR Consignes de sécurité
pour une application en atmosphères explosibles
IT Normative di sicurezza
per l'impiego in luoghi con pericolo di esplosione
ES Instrucciones de seguridad
para el empleo en áreas con riesgo de explosión
PT Normas de segurança
para utilização em zonas sujeitas a explosão
NL Veiligheidsaanwijzingen
voor gebruik op plaatsen waar ontplongsgevaar kan heersen
SV Säkerhetsanvisningar
för användning i explosiionsfarliga områden
DA Sikkerhedsforskrifter
til anvendelse i explosionsfarlig atmosfare
FI Turvallisuusohjeet
räjähdysvaarallisisssa tiloissa käyttöä varten
EL Υποδείξεις ασΦαλείας
για τη χρησιμοποίηση σε περιοχές που υπάρχει κίνδυνος έκρηξης
DE Die vorliegenden Sicherheitshinweise sind im Download unter www.vega.com standard-
mäßig in den Sprachen deutsch, englisch, französisch und spanisch verfügbar.Weitere
EU-Landessprachen stellt VEGA nach Anforderungen zur Verfügung.
EN These safety instructions are available as a standard feature in the download area under
www.vega.com in the languages German, English, French and Spanish. Further EU languag-
es will be made available by VEGA upon request.
FR Les présentes consignes de sécurité sont disponibles au téléchargement sous
www.vega.com en standard en allemand, en anglais, en francais et en espagnol.VEGA met à
disposition d'autres langues de l'Union Européenne selon les exigences.
ES Las indicaciones de seguridad presentes están disponibles en la zona de descarga de
www.vega.com de forma estándar en los idiomas inglés, francés y español.VEGA pone a dis-
posición otros idiomas de la UE cuando son requeridos.

4VEGAPULS 61
37991-EN-200303
1 Area of applicability
These safety instructions apply to the radar sensor VEGAPULS 61 series VEGAPULS
PS61(*).C****P/K/F/L**** according to EU type approval certicate PTB 03 ATEX 2089 X (certicate
number on the type label) and the number of the safety instruction (37991) on the type label.
The electronics module PS60PAK is integrated in the VEGAPULS PS61(*).C****P****.
The electronics module PS60PAS is integrated in the VEGAPULS PS61(*).C****K****.
The electronics module PS60FFK is integrated in the VEGAPULS PS61(*).C****F****.
The electronics module PS60FFS is integrated in the VEGAPULS PS61(*).C****L****.
2 General information
The level measuring instrument VEGAPULS PS61(*).C****P/K/F/L**** is based on radar technology
and is used to detect the distance between product surface and sensor by means of high frequency
electromagnetic waves in the GHz range. The electronics uses the running time of the signals
reected by the product surface to calculate the distance to the product surface.
The VEGAPULS PS61(*).C****P/K/F/L**** consist of an electronics housing, a process connection
element and a sensor (the antenna). As an option the display and adjustment module can also be
integrated.
The measured products can also be combustible liquids, gases, mist or vapour.
The VEGAPULS PS61(*).C****P/K/F/L**** are suitable for use in hazardous atmospheres of all
combustible materials of explosion group IIA, IIB and IIC for applications requiring instruments of
category 1G, category 1/2G or category 2G.
If the VEGAPULS PS61(*).C****P/K/F/L**** are installed and operated in hazardous areas, the gen-
eral Ex installation regulations EN 60079-14 as well as these safety instructions must be observed.
The operating instructions as well as the installation regulations or standards that apply for explo-
sion protection of electrical systems must generally be observed.
The installation of explosion-endangered systems must always be carried out by qualied person-
nel.
Category 1G instruments
The VEGAPULS PS61(*).C****P/K/F/L**** are installed in hazardous areas requiring an instrument
of category 1G.
Category1/2Ginstruments
The electronics housing is installed in hazardous areas requiring instruments of category 2G. The
process connection element is installed in the separating wall, which separates areas requiring in-
struments of category 2G or 1G. The antenna system with the mechanical xing element is installed
in hazardous areas requiring instruments of category 1G.
Category 2G instruments
The VEGAPULS PS61(*).C****P/K/F/L**** are installed in hazardous areas requiring an instrument
of category 2G.
Ignition protection type:
II 1G, 1/2G, 2G Ex ia IIC T6 … T1 Ga, Ga/Gb, Gb

5
VEGAPULS 61
37991-EN-200303
3 Importantspecicationinthetypecode
VEGAPULSPS61(*).abcdefghij
Position Feature Description
ab Approval
CX ATEX II 1G, 1/2G, 2G Ex ia IIC T6
CA ATEX II 1G, 1/2G, 2G Ex ia IIC T6 + WHG
CM ATEX II 1G, 1/2G, 2G Ex ia IIC T6 + Ship approval
cVersion / Material / Pro-
cess temperature
Awith encapsulated horn antenna (ø 40 mm) / PVDF / -40 … +80 °C
B with plastic horn antenna (ø 80 mm) / PP / -40 … +80 °C
de Process tting / Material
** Threaded connection, Clamp, anges; two-digit alphanumeric code
for metallic process ttings, industrial anges according to ASME,
BS, DIN, EN, GOST, HG/T, JIS and for other international, national or
industrial standards, guidelines or standards with suitable pressure
and temperature specications
f Electronics
PTwo-wire Probus PA
K Two-wire Probus PA with increased sensitivity
FTwo-wire Foundation Fieldbus
LTwo-wire Foundation Fieldbus with increased sensitivity
gHousing / Protection K Plastic single chamber / IP66/IP67
AAluminium single chamber / IP66/IP68 (0.2 bar)
HSpecial colour Aluminium single chamber / IP66/IP68 (0.2 bar)
3Aluminium single chamber / IP66/IP68 (1 bar)
DAluminium double chamber / IP66/IP68 (0.2 bar)
SSpecial colour Aluminium double chamber / IP66/IP68 (0.2 bar)
YAluminium double chamber / IP66/IP67 with M12 x 1 for VEGADIS
61/81
VStainless steel single chamber (precision casting) / IP66/IP68
(0.2 bar)
5Stainless steel single chamber (precision casting) / IP66/IP68 (1 bar)
8 Stainless steel single chamber (electropolished) / IP66/IP68 (0.2 bar)
WStainless steel double chamber / IP66/IP68 (0.2 bar)
QStainless steel double chamber / IP66/IP67 with M12 x 1 for
VEGADIS 61/81
RPlastic double chamber / IP66/IP67
X Plastic double chamber / IP66/IP67 with M12 x 1 for VEGADIS 61/81
hCable entry / Cable
gland, Plug connection
MM20 x 1.5 / without
N½ NPT / without
* One-digit alphanumerical code for further suitable ttings, cable en-
tries and closing screws.

6VEGAPULS 61
37991-EN-200303
Position Feature Description
iDisplay and adjustment
module PLICSCOM
Xwithout
A mounted
Fwithout; lid with inspection window
BLaterally mounted
K mounted; with Bluetooth, magnetic pen operation
Llaterally mounted; with Bluetooth, magnetic pen operation
Umounted; with Bluetooth, magnetic pen operation, battery
Slaterally mounted; with Bluetooth, magnetic pen operation, battery
j Additional equipment Xwithout
*with equipment
In the following, all above mentioned versions are called VEGAPULS PS61(*).C****P/K/F/L****. If
parts of these safety instructions refer only to certain versions, then these will be mentioned explic-
itly with their type code.
4 Technicaldata
Electricaldata
TypeofprotectionintrinsicsafetyExi
Power supply and signal circuit: (termi-
nals 1[+], 2[-] in electronics compartment
or for the double chamber housing ver-
sion in termination compartment)
In type of protection intrinsic safety Ex ia IIC
For connection to a certied, intrinsically safe circuit.
Maximum values:
• Ui= 17.5 V
• Ii= 500 mA
• Pi= 5.5 W
Cinegligibly small.
Li ≤ 10 µH.
The instrument is suitable for connection to a Fieldbus
system according to the FISCO model, e.g. Probus PA
or Foundation Fieldbus.
or
• Ui= 24 V
• Ii= 250 mA
• Pi= 1.2 W
Cinegligibly small.
Li ≤ 10 µH.
In the version with x mounted connection cable, Li=
Li'cable (0,55 µH/m) + 10 µH, Ci= Ci'wire/wire (159 pF/m) +
Ci'wire/screen (270 pF/m) must be taken into account.

7
VEGAPULS 61
37991-EN-200303
Indicating and adjustment circuit: (termi-
nals 5, 6, 7, 8 in electronics compartment
or plug connection; with double chamber
housing version in the connection com-
partment)
In type of protection intrinsic safety Ex ia IIC
For connection to the intrinsically safe circuit of the
associated external indicating unit VEGADIS 61/81
(PTB 02 ATEX 2136 X).
The rules for the interconnection of intrinsically safe
circuits between VEGAPULS PS61(*).C****P/K/F/L****
and the external indicating unit VEGADIS 61/81 are
fullled, provided that the total inductance and total ca-
pacitance of the connection cable between VEGAPULS
PS61(*).C****P/K/F/L**** and the external indicating unit
VEGADIS 61/81 Lcable = 310 µH and Ccable = 2 µF are not
exceeded.
When using the delivered VEGA connection cable
between VEGAPULS PS61(*).C****P/K/F/L**** and the
external indicating unit VEGADIS 61/81, the following
listed cable inductances Liand cable capacitances Ci
must be taken into account with a cable length ≥ 50 m.
• Li' = 0.62 µH/m
• Ci'wire/wire = 132 pF/m
• Ci'wire/screen = 208 pF/m
• Ci'screen/screen = 192 pF/m
Circuit of the display and adjustment
module: (spring contacts in the electron-
ics compartment; with double chamber
housing version also in the connection
compartment)
In type of protection intrinsic safety Ex ia IIC
Only for connection to the display and adjust-
ment module PLICSCOM or VEGACONNECT
(PTB 07 ATEX 2013 X).
With the double chamber housing version, the display
and adjustment module may be mounted either in the
electronics compartment or in the termination compart-
ment.
For applications requiring instruments of category 2G, the intrinsically safe power supply and signal
circuit can correspond to protection class ia or ib. For connection to a circuit with protection class ib,
the ignition protection type identication is Ex ib IIC T6.
For applications requiring instruments of category 1G or 1/2G, the intrinsically safe power supply
and signal circuit must correspond to protection class ia.
For applications requiring instruments of category 1G or 1/2G the VEGAPULS PS61(*).C****P/K/
F/L**** is preferably connected to appropriate equipment with galvanically isolated, intrinsically safe
circuits.
The metal parts of the level measuring instruments on radar basis type VEGAPULS PS6* are electri-
cally connected to the earth terminals.
In the versions of the radar sensors VEGAPULS PS61(*).C****P/K/F/L**** the intrinsically safe
circuits are electrically isolated from elements that may be earthed.
5 Applicationconditions
The max. permissible ambient temperatures depending on the temperature classes are specied in
the following tables.
For assessment and reduction of the explosion risk, valid standards such as for example EN 1127-1
must be taken into account.

8VEGAPULS 61
37991-EN-200303
Category 1G instruments
Temperature class Temperatureontheantenna Ambienttemperatureontheelec-
tronics
T5 -20 … +42 °C -20 … +42 °C
T4, T3, T2, T1 -20 … +60 °C -20 … +60 °C
For applications requiring instruments of category 1G the process pressure of the media must be
between 0.8 … 1.1 bar. The application conditions when operating in the absence of explosive
mixtures can be found in the manufacturer information.
Category1/2Ginstruments
Temperature class Temperatureontheantenna Ambienttemperatureontheelec-
tronics
T6 -20 … +60 °C -40 … +46 °C
T5 -20 … +60 °C -40 … +61 °C
T4, T3, T2, T1 -20 … +60 °C -40 … +80 °C
For applications requiring instruments of category 1G the process pressure of the media must be
between 0.8 … 1.1 bar. If the VEGAPULS PS61(*).C****P/K/F/L**** are operated at temperatures
higher than those specied in the above table, please make sure by means of appropriate measures
that there is no danger of ignition from the hot surfaces. The max. permissible temperature on the
electronics/housing should not exceed the values according to the above table.
Please make sure that the sensor also in case of failure does not generate heat itself. Responsibility
for safe operation of the equipment, with respect to pressures/temperatures of the materials used,
rests with the operator.
The prerequisites for operation in the absence of explosive mixtures can be found in the manufac-
turer specications.
Category 2G instruments
Temperature class Temperatureontheantenna Ambienttemperatureontheelec-
tronics
T6 -60 … +80 °C -40 … +46 °C
T5 -60 … +80 °C -40 … +61 °C
T4, T3, T2, T1 -60 … +80 °C -40 … +80 °C
If the VEGAPULS PS61(*).C****P/K/F/L**** are operated at higher temperatures than those speci-
ed in the above table, please make sure by means of appropriate measures that there is no danger
of ignition from hot surfaces. The max. permissible temperature on the electronics/housing must not
exceed the values specied in the above table.
Please make sure that the sensor also in case of failure does not generate heat itself. Responsibility
for safe operation of the equipment, with respect to pressures/temperatures of the materials used,
rests with the operator.
The prerequisites for operation in the absence of explosive mixtures can be found in the manufac-
turer specications.
6 Protection against static electricity
The VEGAPULS PS61(*).C****P/K/F/L**** in versions with electrostatically chargeable plastic parts,

9
VEGAPULS 61
37991-EN-200303
such as e.g. plastic housing, metal housing with inspection window or plastic antenna, have a cau-
tion label pointing out the safety measures that must be taken with regard to electrostatic charges
during operation.
WARNING - POTENTIAL ELECTROSTATIC
CHARGING HAZARD - SEE INSTRUCTIONS
Caution: Plastic parts! Danger of electrostatic charging!
• Avoid friction
• No dry cleaning
• Construction/Installation: The VEGAPULS PS61(*).C****P/K/F/L**** must be constructed/
installed in such a way that
– electrostatic charges are ruled out during operation, maintenance and cleaning.
– process-related electrostatic charges, e.g. by measuring media owing past, are ruled out
7 Use of an overvoltage arrester
If necessary, a suitable overvoltage arrester can be connected in front of the VEGAPULS
PS61(*).C****P/K/F/L****.
When used as category 1G or 1/2G instrument, a suitable overvoltage arrester must be connected
in between as protection against overvoltages, as far as required according to EN 60079-14.
8 Grounding
In order to avoid the danger of electrostatic charging of the metallic parts, the VEGAPULS
PS61(*).C****P/K/F/L**** must be electrostatically connected to the local potential equalisation
(transfer resistance ≤ 1 MΩ), e.g. via the ground terminal, when used as category 1G or 1/2G instru-
ments.
Metallic adapter anges must be earthed, especially when installed on non-conductive plastic ves-
sels or non-earthed vessels. Earthing can be realised with cable lug via the ange gland.
9 Impactandfrictionsparks
When used as category 1G instruments, the VEGAPULS PS61(*).C****P/K/F/L**** in aluminium/
titanium versions must be mounted in such a way that sparks from impact and friction between alu-
minium/titanium and steel (except stainless steel, if the presence of rust particles can be excluded)
cannot occur.
10 Material resistance
For applications requiring instruments of category 1G or category 1/2G the VEGAPULS
PS61(*).C****P/K/F/L**** must only be used in products against which the wetted materials are suf-
ciently resistant.
11 MountingwithexternaldisplayunitVEGADIS61/81
The intrinsically safe signal circuit between VEGAPULS PS61(*).C****P/K/F/L**** and the external
indicating unit VEGADIS 61/81 should be set up without grounding. The required insulation voltage
is > 500 V AC. When using the VEGA connection cable included with the delivery, this requirement
is fullled. If grounding of the cable screen is required, it must be carried out according to EN 60079-
14.

10 VEGAPULS 61
37991-EN-200303
12 Removingandreplacingtheredthreaded/dustcover
When the VEGAPULS PS61(*).C****P/K/F/L**** are delivered, depending on the version, the red
threaded or dust protection caps must be removed before installing the device and the openings
must be sealed according to the requirements of the type of protection and the IP protection type
specied on the type label.
When using certied i.e. suitable cable glands, sealing plugs or plug connectors, they must be
mounted correctly and the respective certicates/documents must be observed.
The sealing plugs included in the delivery by VEGA meet the necessary requirements.
1
1 Red threaded or dust protection cap

11
Notes
VEGAPULS 61
37991-EN-200303
This manual suits for next models
1
Table of contents
Other Vega Laser Level manuals
Popular Laser Level manuals by other brands

ABB
ABB LLT100 Functional safety guide

RedBack Lasers
RedBack Lasers BASIC614 instruction manual

Hilti
Hilti PML 42 operating instructions

LMI Technologies
LMI Technologies Gocator 1100 Series user manual

Bosch
Bosch GLL 2-10 Professional Original instructions

Parkside Performance
Parkside Performance PKLLP 360 B2 Operation and safety notes