Vega VEGAMET 625 User manual

Operating Instructions
VEGAMET 625
Double channel HART signal conditioning instrument
Document ID:
28970
Signal
conditioning instruments
and communication

Contents
1About this document
1.1Function.................................. 4
1.2Target group .............................. 4
1.3Symbolism used............................ 4
2For your safety
2.1Authorised personnel ........................ 5
2.2Appropriate use ............................ 5
2.3Warning about misuse ....................... 5
2.4General safety instructions . . . . . . . . . . . . . . . . . . . . 5
2.5Safety label on the instrument . . . . . . . . . . . . . . . . . . 6
2.6CE conformity ............................. 6
2.7Safety instructions for Ex areas . . . . . . . . . . . . . . . . . 6
2.8Overfill protection according to WHG . . . . . . . . . . . . . 6
2.9Environmental instructions..................... 6
3Product description
3.1Structure ................................. 7
3.2Principle of operation ........................ 8
3.3Configuration .............................. 8
3.4Packaging,transport and storage ............... 9
4Mounting
4.1General instructions ......................... 10
4.2Mounting instructions ........................ 10
5Connecting to power supply
5.1Preparing the connection ..................... 12
5.2Connection procedure........................ 12
5.3Wiring plan................................ 14
6Setup with the integrated indicating and adjustment unit
6.1Adjustment system .......................... 16
6.2Setup steps ............................... 17
6.3Menu schematic ............................ 29
7Setup with PACTware
7.1Connecting the PC .......................... 37
7.2Parameter adjustment with PACTware . . . . . . . . . . . . 40
7.3Setup web server/e-mail,remote enquiry . . . . . . . . . . 41
8Application examples
8.1Level measurement in a cylindrical tank with overfill
protection/dry run protection . . . . . . . . . . . . . . . . . . . 42
8.2Weir control of a water power station. . . . . . . . . . . . . 43
8.3Interface measurement with VEGAFLEX 67 . . . . . . . . 45
8.4Pump control 1/2(running time controlled) . . . . . . . . . 47
8.5Tendency recognition ........................ 49
2VEGAMET 625 •Double channel HART signal conditioning instrument
Contents
28970-EN-110801

8.6Flow measurement .......................... 50
9Maintenance and fault rectification
9.1Maintenance .............................. 53
9.2Fault rectification ........................... 53
9.3Instrument repair ........................... 56
10 Dismounting
10.1Dismounting steps .......................... 57
10.2Disposal ................................. 57
11 Supplement
11.1Technical data ............................. 58
11.2Overview applications/functionality............... 62
11.3Dimensions ............................... 64
Supplementary documentation
Information:
Supplementary documents appropriate to the ordered version come
with the delivery.You can find them listed in chapter "Product
description".
Editing status:2011-07-06
VEGAMET 625 •Double channel HART signal conditioning instrument 3
Contents
28970-EN-110801

1About this document
1.1Function
This operating instructions manual provides all the information you
need for mounting,connection and setup as well as important
instructions for maintenance and fault rectification.Please read this
information before putting the instrument into operation and keep this
manual accessible in the immediate vicinity of the device.
1.2Target group
This operating instructions manual is directed to trained qualified
personnel.The contents of this manual should be made available to
these personnel and put into practice by them.
1.3Symbolism used
Information,tip,note
This symbol indicates helpful additional information.
Caution:If this warning is ignored,faults or malfunctions can
result.
Warning:If this warning is ignored,injury to persons and/or serious
damage to the instrument can result.
Danger:If this warning is ignored,serious injury to persons and/or
destruction of the instrument can result.
Ex applications
This symbol indicates special instructions for Ex applications.
lList
The dot set in front indicates a list with no implied sequence.
àAction
This arrow indicates a single action.
1Sequence
Numbers set in front indicate successive steps in a procedure.
4VEGAMET 625 •Double channel HART signal conditioning instrument
1About this document
28970-EN-110801

2For your safety
2.1Authorised personnel
All operations described in this operating instructions manual must be
carried out only by trained specialist personnel authorised by the plant
operator.
During work on and with the device the required personal protective
equipment must always be worn.
2.2Appropriate use
VEGAMET 625 is a universal signal conditioning instrument and power
supply unit for connection of two HART sensors.
You can find detailed information on the application range in chapter
"Product description".
Operational reliability is ensured only if the instrument is properly used
according to the specifications in the operating instructions manual as
well as possible supplementary instructions.
For safety and warranty reasons,any invasive work on the device
beyond that described in the operating instructions manual may be
carried out only by personnel authorised by the manufacturer.Arbitrary
conversions or modifications are explicitly forbidden.
2.3Warning about misuse
Inappropriate or incorrect use of the instrument can give rise to
application-specific hazards,e.g.vessel overfill or damage to system
components through incorrect mounting or adjustment.
2.4General safety instructions
This is a high-tech instrument requiring the strict observance of
standard regulations and guidelines.The user must take note of the
safety instructions in this operating instructions manual,the country-
specific installation standards as well as all prevailing safety
regulations and accident prevention rules.
The instrument must only be operated in a technically flawless and
reliable condition.The operator is responsible for trouble-free
operation of the instrument.
During the entire duration of use,the user is obliged to determine the
compliance of the necessary occupational safety measures with the
current valid rules and regulations and also take note of new
regulations.
VEGAMET 625 •Double channel HART signal conditioning instrument 5
2For your safety
28970-EN-110801

2.5Safety label on the instrument
The safety approval markings and safety tips on the device must be
observed.
2.6CE conformity
This device fulfills the legal requirements of the applicable EC
guidelines.By attaching the CE mark,VEGA provides a confirmation
of successful testing.You can find the CE conformity declaration in the
download area of www.vega.com.
2.7Safety instructions for Ex areas
Please note the Ex-specific safety information for installation and
operation in Ex areas.These safety instructions are part of the
operating instructions manual and come with the Ex-approved
instruments.
2.8Overfill protection according to WHG
InGermany the WHG (Water Resource Act)stipulates an overfill
protection for systems that deal with substances hazardous to water.
An appropriately certified sensor is the prerequisite for such
protection.The VEGAMET 625 fulfils the construction and testing
principles for overfill protection systems.This is certified by the TÜV
(Technical Control Board)statement "PP 5003/09".You can download
this document from our homepage under "Downloads -Approvals -
Signal conditioning instruments -Overfill protection".
2.9Environmental instructions
Protection of the environment is one of our most important duties.That
is why we have introduced an environment management system with
the goal of continuously improving company environmental protection.
The environment management system is certified according to DIN
EN ISO 14001.
Please help us fulfil this obligation by observing the environmental
instructions in this manual:
lChapter "Packaging,transport and storage"
lChapter "Disposal"
6VEGAMET 625 •Double channel HART signal conditioning instrument
2For your safety
28970-EN-110801

3Product description
3.1Structure
The scope of delivery encompasses:
lVEGAMET 625 signal conditioning instrument
lTerminal socket
lCoded pins and bridges
lRS232 modem connection cable (optional)
lDocumentation
-this operating instructions manual
-Supplementary instruction 30325 "RS232/Ethernet connec-
tion"(optional)
-Supplementary instructions manual 30768 "Modbus-TCP,
VEGA ASCII protocol"(optional)
-Ex-specific"Safety instructions"(with Ex versions)
-if necessary,further certificates
The VEGAMET 625 consists of the components:
lVEGAMET 625 signal conditioning instrument with indicating and
adjustment unit in the front
lTerminal socket
VEGAMET
1 2 3 4
9 10 11 12
17 18 20 21 22
5 6 7 8
13 14 15 16
23 24 25 26 27 28
Ser. No.
12345678
on
OK
ESC
COM
3
2
1
2
3
4
1
6
5
Fig.1:VEGAMET 625
1Ex separating chamber with Ex version
2VEGAMET 625
3Indicating and adjustment unit
4Communication interface for VEGACONNECT (I²C)
5RS232 or Ethernet interface (optional)
6Terminal socket
The type label contains the most important data for identification and
use of the instrument:
lArticle number
lSerial number
lTechnical data
Scope of delivery
Constituent parts
Type label
VEGAMET 625 •Double channel HART signal conditioning instrument 7
3Product description
28970-EN-110801

lArticle numbers,documentation
The serial number allows you to access the delivery data of the
instrument via www.vega.com,"VEGA Tools"and "serial number
search".
3.2Principle of operation
VEGAMET 625 is a universal signal conditioning instrument for a
number of applications such as level,gauge,interface and process
pressure measurement.At the same time,it can serve as power
supply unit for connected sensors.VEGAMET 625 is designed for
connection of two independent VEGA HART sensors.Hence two
independent measurements can be carried out.By means of a third
measurement loop,the difference between the two input values can be
calculated.
On instruments with one of the optional interfaces (RS232/Ethernet),
the measured values can be retrieved via modem or network and
displayed by means of a web browser,Visual VEGA or WEB-VV.It is
also possible to send measured values and messages via e-mail.The
use of VEGAMET 625 is particularly suitable for stocktaking,VMI
(Vendor Managed Inventory)and remote enquiry.
The VEGAMET 625 signal conditioning instrument can power two
HART sensors and process their measured signals via the same
cable.The measured value transmission is carried out via a digital bus
system (HART Multidrop). The requested parameter is displayed and
also sent to the integrated current outputs for further processing.
Hence the measured signal can be transferred to a remote indication
or a superordinate control system.Three level relays for control of
pumps or other actuators are also integrated.
Wide-range power supply unit with 20 …253 V AC/DC for world-wide
use.
Detailed information about the power supply can be found in chapter
"Technical data".
3.3Configuration
The instrument can be adjusted with the following adjustment media:
lWith integrated indicating and adjustment unit
lan adjustment software according to FDT/DTM standard,e.g.
PACTware and a Windows PC
The entered parameters are generally saved in VEGAMET 625,when
used with PACTware and PC also optionally in the PC.
Application area
Functional principle
Voltage supply
8VEGAMET 625 •Double channel HART signal conditioning instrument
3Product description
28970-EN-110801

Information:
When using PACTware and the corresponding VEGA DTM,additional
settings can be carried out which are not possible or only partly
possible with the integrated indicating and adjustment unit.When
using an adjustment software,you either need one of the integrated
interfaces (RS232/Ethernet)or the interface converter VEGA-
CONNECT.
Further instructions for setting up the web server and e-mail functions
can be found in the online help of PACTware or the VEGAMET 625
DTMs as well as the operating instructions manual "RS232/Ethernet
connection".
3.4Packaging,transport and storage
The device was protected by packaging during transport.Its capacity
to handle normal loads during transport is assured by a test according
to DIN EN 24180.
The packaging of standard instruments consists of environment-
friendly,recyclable cardboard.For special versions,PE foam or PE foil
is also used.Dispose of the packaging material via specialised
recycling companies.
Transport must be carried out under consideration of the notes on the
transport packaging.Nonobservance of these instructions can cause
damage to the device.
The delivery must be checked for completeness and possible transit
damage immediately at receipt.Ascertained transit damage or
concealed defects must be appropriately dealt with.
Up to the time of installation,the packages must be left closed and
stored according to the orientation and storage markings on the
outside.
Unless otherwise indicated,the packages must be stored only under
the following conditions:
lNot in the open
lDry and dust free
lNot exposed to corrosive media
lProtected against solar radiation
lAvoiding mechanical shock and vibration
lStorage and transport temperature see chapter "Supplement -
Technical data -Ambient conditions"
lRelative humidity 20 …85 %
Packaging
Transport
Transport inspection
Storage
Storage and transport
temperature
VEGAMET 625 •Double channel HART signal conditioning instrument 9
3Product description
28970-EN-110801

4Mounting
4.1General instructions
Each series 600 instrument consists of the actual signal conditioning
instrument as well as a plug-in socket for carrier rail mounting.
Because it has protection class IP 30 or IP 20,the instrument is
intended to be used in switching cabinets.
4.2Mounting instructions
The plug-in socket is designed for carrier rail mounting according to
EN 50022.The operating voltage is connected to terminals 17 and 18.
For neighbouring series 600 instruments it is possible to continue
connection L1and Ndirectly via the supplied bridges.Max.five
instruments can be connected through in this way.
Danger:
Looping through via bridges is only allowed for operating voltage
(sockets L1and N). The bridges must never be used with single
instruments,at the end of a row of instruments or with other sockets.If
this rule is not heeded,there is a danger of coming into contact with
the operating voltage or causing a short circuit.
A VEGAMET 625 in Ex version is an auxiliary,intrinsically safe
instrument and may not be installed in explosion-endangered areas.
Before setup,the Ex separating chamber must be attached (as shown
below)with Ex versions.Safe operation can be only ensured if the
operating instructions manual and the EG type approval certificate are
observed.VEGAMET 625 must not be opened.
All signal conditioning instruments are provided with different gaps
dependent on type and version (mechanical coding).
The plug-in socket is provided with coded pins that can be inserted to
prevent accidental interchanging of the various instrument types.
With a VEGAMET 625 in Ex version,the supplied coded pins (type
coded pin and Ex coded pin)must be inserted by the user according to
the below chart.
Installation possibilities
Installation
Instrument coding
10 VEGAMET 625 •Double channel HART signal conditioning instrument
4Mounting
28970-EN-110801

A o
B o
C o
1 o
2 o
3 o
o
o
o
7 o
8 o
9 o
o
o
12 o
N
L1
VEGA A o
B o
C o
1 o
2 o
3 o
4 o
5 o
6 o
7 o
8 o
9 o
10 o
11 o
12 o
N
L1
VEGA
12 3 4 56 7 8
1
4 4
2
3
Fig.2:Plug-in socket VEGAMET 625
1Ex separating chamber
2Ex coding with Ex version
3Type coding for VEGAMET 624/625
4Bridges for looping the operating voltage
VEGAMET 625 •Double channel HART signal conditioning instrument 11
4Mounting
28970-EN-110801

5Connecting to power supply
5.1Preparing the connection
Always keep in mind the following safety instructions:
lConnect only in the complete absence of line voltage
lIf voltage surges are expected,install overvoltage arresters
In hazardous areas you must take note of the respective regulations,
conformity and type approval certificates of the sensors and power
supply units.
The voltage supply can be 20 …253 V AC/DC,50/60 Hz.
The operating voltage of VEGAMET 625 is connected with standard
cable according to the national installation standards.
Standard two-wire cable can be used for connecting the sensors.The
screening is absolutely necessary to ensure interference-free oper-
ation with HART sensors.
Connect the cable screen on both ends to ground potential.In the
sensor,the screen must be connected directly to the internal ground
terminal.The ground terminal on the outside of the sensor housing
must be connected to the potential equalisation (low impedance).
If potential equalisation currents are expected,the screen connection
on the side of VEGAMET 625 must be made via a ceramic capacitor
(e.g.1nF,1500 V). The low frequency potential equalisation currents
are thus suppressed,but the protective effect against high frequency
interference signals remains.
Take note of the corresponding installation regulations for Ex
applications.In particular,make sure that no potential equalisation
currents flow over the cable screen.In case of grounding on both sides
this can be achieved by the use of a capacitor or a separate potential
equalisation.
5.2Connection procedure
Note:
Before the actual setup,each HART sensors must be assigned an
address (address range 1-15), (see chapter "Setup"). Address 0
(mode 4…20 mA)must not be used.When assigning an address,
only one sensor should be connected to VEGAMET 625.If connection
is completed already,the wiring must be briefly cancelled for
addressing.Depending on the installation location of the sensors,it
can be advantageous to carry out this addressing before installing and
Note safety instructions
Take note of sa-
fety instructions
for Ex applica-
tions
Select power supply
Select connection cable
Cable screening and
grounding
Select connec-
tion cable for Ex
applications
12 VEGAMET 625 •Double channel HART signal conditioning instrument
5Connecting to power supply
28970-EN-110801

connecting the sensors.This can be conveniently carried out e.g.in
the workshop.You just need a 24 Volt power supply as well as an
indicating and adjustment module PLICSCOM or the adjustment
software PACTware with VEGACONNECT.
Move on to electrical connection and proceed as follows:
1Snap the socket without VEGAMET 625 onto the carrier rail
2Connect sensor cable to terminal 1/2(active input)or 3/4(passive
input), provide a screening
3When using several sockets,loop the power supply by means of
bridges
4Connect power supply (switched off)to terminal 17 and 18
5If necessary,connect relays or other outputs
6Insert VEGAMET 625 into the plug-in socket and screw it down
tightly
Note:
If the addressing of the sensors has not yet been carried out,only one
sensor must be connected.Addressing (see chapter "Setup")of the
first sensor can then be carried out.Afterwards,the first sensor must
be disconnected again and the next sensor connected and provided
with an address.Then all sensors can be connected and setup can be
started.
Before setting up Ex versions,make sure the Ex separating chamber is
plugged on the left housing side (above the sensor terminals). The
pins for type and Ex coding must also be inserted correctly.
Information:
lOn the active input (terminal 1/2), VEGAMET 625 provides power
for the connected sensors.Power supply and measurement data
are transmitted over the same two-wire cable.This mode is
provided for connection of measuring transducers without sepa-
rate operating voltage (sensors in two-wire version).
lOn the passive input (terminals 3/4), the sensors are not supplied
with energy -only the measured value is transmitted.This input is
for instruments with their own separate operating voltage (sensors
in four-wire version or separators such as VEGATRENN 149). On
aVEGAMET 625 in Ex version,the passive input is not available
due to approval/technical reasons.
Note:
VEGAMET 625 is designed for connection of two HART sensors.
Because they are accessed via different addresses in the HART
multidrop mode,both sensors are connected to the same sensor input.
These are either terminals 1/2(active input)or terminals 3/4(passive
input). Simultaneous mixed operation on active and passive input is
not possible.The measured value transmission is carried out via the
VEGAMET 625 •Double channel HART signal conditioning instrument 13
5Connecting to power supply
28970-EN-110801

digital HART signal.An analogue 4…20 mAtransmission is not
possible.Because this is a digital bus system,only one two-wire cable
should lead to the two sensors.Adistributor can be connected directly
in front of the sensors.As an alternative,the connection to the next
sensor can be continued via the second cable entry in the sensor
housing.The addressing of the sensors should be carried out before
connection,see chapter "Set up".
5.3Wiring plan
17 18 19 20 21 22
9 10 11 12
1
2 3 4
23 24 25 26 27 28
13 14 15 16
5 6 7 8
L1 N
+
-
+ - + - + -
+ -
17 2 3
4 5 6
+ -
1211
13
8
9
10
Fig.3:Wiring plan VEGAMET 625 with two-wire sensors
1Internal operating relay 1
2Internal operating relay 2
3Internal operating relay 3
4Internal current output 1
5Internal current output 2
6Internal current output 3
7Voltage supply of VEGAMET 625
8Measurement data input with sensor supply (active input)
9Measurement data input (passive input), not in Ex ia
10 Internal fail safe relay
11 HART two-wire sensor with Multidrop address 1
12 HART two-wire sensor with Multidrop address 2
13 Distributor
Wiring plan for two-wire
sensors
14 VEGAMET 625 •Double channel HART signal conditioning instrument
5Connecting to power supply
28970-EN-110801

17 18 19 20 21 22
9 10 11 12
1
2 3 4
23 24 25 26 27 28
13 14 15 16
5 6 7 8
L1 N
+
-
+ - + - + -
+ -
17 2 3
8
9
4 5 6
+ -
1211
14
13
10
Fig.4:Wiring plan VEGAMET 625 with four-wire sensors
1Internal operating relay 1
2Internal operating relay 2
3Internal operating relay 3
4Internal current output 1
5Internal current output 2
6Internal current output 3
7Voltage supply of VEGAMET 625
8Measurement data input with sensor supply (active input)
9Measurement data input (passive input), not in Ex ia
10 Internal fail safe relay
11 HART four-wire sensor with Multidrop address 1
12 HART four-wire sensor with Multidrop address 2
13 Distributor
14 Power supply for four-wire sensors
Wiring plan for four-wire
sensors
VEGAMET 625 •Double channel HART signal conditioning instrument 15
5Connecting to power supply
28970-EN-110801

6Setup with the integrated indicating and
adjustment unit
6.1Adjustment system
The integrated indicating and adjustment unit is used for measured
value display,adjustment and diagnosis of VEGAMET 625 as well as
the connected sensors.The indication and adjustment are carried out
via four keys and a clear,graphic-capable display with background
lighting.The adjustment menu with selectable language is clearly
structured and enables easy setup.
Certain adjustment options are not possible or only partially available
with the integrated indicating and adjustment unit,e.g.settings for the
e-mail server.For such applications,the use of PACTware with
appropriate DTMs is recommended.
Ser. No.
12345678
on
OK
ESC
COM
3
2
1
3
6
5
7
4
1
2
Fig.5:Indicating and adjustment elements
1LC display
2Adjustment keys
3Communication interface for VEGACONNECT
4Status indication operation
5Status indication fail safe relay
6Status indication interface activity
7Status indication operating relay 1-3
l[OK]key:
-Move to the menu overview
-Confirm selected menu
-Edit parameter
-Save value
l[->]key to select:
-Menu change
-Select list entry
-Select editing position
Function
Indicating and adjust-
ment elements
Key functions
16 VEGAMET 625 •Double channel HART signal conditioning instrument
6Setup with the integrated indicating and adjustment unit
28970-EN-110801

l[+]key:
-Change value of the parameter
l[ESC]key:
-interrupt input
-jump to the next higher menu
Note:
Approx.10 minutes after the last pressing of a key,an automatic reset
to measured value indication is triggered.Any values not confirmed
with [OK]will not be saved.
6.2Setup steps
Through parameter adjustment,the instrument is adapted to the
individual application conditions.Ameasurement loop calibration is
the most important step and should always be carried out.Ascaling of
the measured value to the desired physical variable and unit,possibly
including a linearization curve,is often useful.The adaptation of the
relay switching points or the setting of an integration time to smooth the
measured value are further standard adjustment options.
For instruments with Ethernet interface,the instrument must be
provided with an IP address and subnet mask suitable for the
instrument.As an alternative,addressing via DHCP and a host name
is also possible.If necessary,the e-mail/webserver can be also
configured with PACTware.
Information:
When using PACTware and the corresponding VEGA DTM,additional
settings can be carried out which are not possible or only partly
possible with the integrated indicating and adjustment unit.When
using an adjustment software,you either need one of the integrated
interfaces (RS232/Ethernet)or the interface converter VEGA-
CONNECT.
Further instructions for setting up the web server and e-mail functions
are stated in the online help of PACTware or the VEGAMET 625 DTMs
as well as the supplementary instructions manual "RS232/Ethernet
connection".
VEGAMET 625 can process measured values of more than one HART
sensor.The measured values are transmitted as digital HART signals
to the same cable (bus). An analogue 4…20 mAtransmission is not
possible,the current is limited to 4mA.An own,unambiguous address
(address range 1-15)must be assigned to each connected sensor.
This mode is also called HART multidrop mode.Address 0(mode
4…20 mA)must not be used.
Parameter adjustment
Set HART address
VEGAMET 625 •Double channel HART signal conditioning instrument 17
6Setup with the integrated indicating and adjustment unit
28970-EN-110801

Note:
When addresses are being assigned,only one sensor must be
connected on the bus.If this is not the case,no sensor can be
accessed and it is not possible to assign an address.
The addressing can be carried out directly on each HART sensor via
the respective adjustment unit or adjustment software.As an
alternative,the setting of the sensor address can be also carried out
via the VEGAMET menu under "Service -Sensor address"(see
chapter "Setup procedure"under "Service -Change sensor address").
After being switched on,VEGAMET 625 first of all carries out a short
self-check.The following steps are carried out:
lInternal check of the electronics
lindication of the instrument type,firmware version as well as the
instrument TAG (instrument name)
lThe output signals jump briefly to the set fault value
After the assignment of the addresses to the sensors,the current
measured values will be displayed and outputted.
As requested,the measured value display shows the individual
measurement loops separately or in a joint overview.The respective
digital display value,the measurement loop name (meas.loop TAG)
and the unit are shown.With the separate presentation,an analogue
bar graph is also displayed and the measured values appear in bigger
font size.By pushing the [>]key,you move between the different
indicating options.
Note:
Depending on the configuration and use of all measurement loops,the
cycle time for the measured value transmission can take up to five
seconds.
By pushing [OK]you move from the measured value indication to the
main menu.
The main menu is divided into six areas with the following functions:
lDevice settings:Includes the device-TAG,settings for network
connection such as date/time setting, …
Switch on phase
Measured value indica-
tion
Main menu
18 VEGAMET 625 •Double channel HART signal conditioning instrument
6Setup with the integrated indicating and adjustment unit
28970-EN-110801

lMeasurement loop:Includes settings for input selection,adjust-
ment,damping,linearization,scaling,outputs, …
lDisplay:Includes settings to the displayed measured value
lDiagnosis Includes information to the device status,error
messages
lService Includes simulation,reset,PIN,selectable language,
sensor address, …
lInfo:Shows serial number,software version,last change,instru-
ment features,MAC addr., …
àSelect the menu item "Device settings"with [->]and confirm with
[OK].
Under the menu item "Device settings",you can select the requested
application.For all level,gauge and differential measurements,the
application "Standard"is correct.
If an interface measurement should be carried out with a VEGAFLEX
67,you have to choose the menu item "Interface measurement"as
application.After the configuration of the inputs,the exact DK value for
the upper medium must be entered.For further information see
chapter "Application examples".
àSelect the requested application with [->]and save your setting
with [OK].Finally change to the menu item "Input"with [->].
Because VEGAMET 625 has two inputs,the measurement loops must
be assigned to the inputs.After the addresses of the HART sensors
are assigned,a list of the existing sensors can be prepared and
displayed via "Sensor selection -Sensor search".Now you can assign
the requested sensor to each measurement loop.
For transmission,VEGAMET 625 must be informed which "Sensor
value"should be used for further processing.Depending on the sensor
type this can be distance,pressure,interface or temperature.You will
find further information under the menu item "Meas.loop -Input".
àAllocate the requested inputs to the appropriate measurement
loops,select the suitable sensor value and save your settings with
Device settings -Appli-
cation
Device settings -Input
VEGAMET 625 •Double channel HART signal conditioning instrument 19
6Setup with the integrated indicating and adjustment unit
28970-EN-110801

[OK].After the first setup,you can modify the inputs also under
"Meas.loop -Input".
You can assign an unambiguous name to VEGAMET 625 via the
Device-TAG.This function is recommended when several instruments
are implemented and a good documentation of larger systems is
required.
àEnter the requested values via the appropriate keys and save your
settings with [OK].
For instruments with integrated Ethernet interface,the instrument must
be provided with an IP address/Subnet mask suitable for your network.
Depending on the network,a gateway address may also be required.
As an alternative,addressing via DHCP and a host name is also
possible.These data are available from your network administrator.
Keep in mind that your settings are only effective after a restart of
VEGAMET 625.Further information on these network parameters is
available in the supplementary instructions manual "RS232/Ethernet
connection"and in the online help of the corresponding DTMs.
Carry out your settings via the appropriate keys and save with [OK].
àCarry out your settings via the appropriate keys and save with
[OK].Disconnect briefly the operating voltage so that the modified
settings become effective.
Date and time can be entered in this menu item for instruments with
integrated RS232/Ethernet interface.These time settings are buffered
in case of power failure for approx.3days.
àEnter the values via the appropriate keys and save your settings
with [OK].
Device settings -Device-
TAG
Device settings -Host
Name/IP addr.
Device settings -Time/
Date
20 VEGAMET 625 •Double channel HART signal conditioning instrument
6Setup with the integrated indicating and adjustment unit
28970-EN-110801