Ventacity Systems VSCM Series User manual

Rev. 01.01
VSCM
Installation and Operation Manual
Rev. 01.01
03/04/19
VS1200 CMh/e
VS900 CMh/e
VS400 CMh/e
VS250 CMh/e

2Rev. 01.01

3
Rev. 01.01
INTRODUCTION UNPACKING INSTALLATION COMMISSIONING REFERENCESPECIFICATIONS
TABLE OF CONTENTS
1. INTRODUCTION
1.1 Acceptable Environment 5
1.2 Access Distance 5
1.3 Safe Installation Distance 5
2. SPECIFICATIONS
2.1 Main Components 6
2.2 Dimensions 7
2.3GeneralSpecications 8
2.4 Sound Power 12
3. UPACKING
3.1 Inspect Delivery 13
3.2 Unpack the Unit 13
4. INSTALLATION
4.1 Hanging the Unit 14
4.2 Connecting Ductwork 15
4.3 Electrical Installation 16
4.4 Damper Installation 17
. 4.5 Condensate Installation 17
4.6PostheaterInstallation 18
4.7 SBC100 Installation 19
4.8ElectricalAccessories 20
5. COMMISSIONING
5.1 Activation 24
5.2 Main Display 25
5.3 Main Menu 25
5.4 Service Menu 25
6. REFERENCE
6.1 Maintenance (Filters and Core) 33
6.2 Troubleshooting 34
6.3Service 38
6.4 Conclusion 39

4Rev. 01.01
INTRODUCTION
1. INTRODUCTION
This manual includes the following symbols.
Symbol Meaning
ATTENTION! Warning or notication
READ CAREFULLY! Important instructions
YOU WILL NEED Advice and practical information
TECHNICAL DATA Detailed technical information
This manual includes important instructions for safe connection of the Heat Recovery Ventilator unit (HRV). Be-
fore connecting the unit, please read carefully and follow all the instructions below! The manufacturer reserves
the right to make changes, including changes in the technical documentation, without previous notication.
Please keep this manual for further reference. Consider this manual a permanent part of the product.
• This manual shows manufacturer-recommended installation methods. Local codes and regulations override
these recommendations.
• The installation must follow local codes and standards as approved by local permitting authorities and Na-
tional Electrical Code (NEC), The National Fire Protection Agency (NFPA), and the Canadian Electrical Code
(CEC) in Canada.
• Installation must be performed by qualied and accredited professional engineers and skilled tradesmen in
conformance with local and national codes, standards, and licensing requirements.
EC DECLARATION OF CONFORMITY
The product was designed, manufactured, and placed on the market, and complies with all relevant provisions
and requirements of the European Parliament and the Council, including amendments, which it was classied
under. The product is safe under normal conditions of installation and use. The conditions are dened in the
Operating Instructions. The product’s safety evaluation was based on the harmonized European standards
listed in the relevant EC declaration of conformity.
During installation it is necessary to consider the weight of the unit, including all associated peripherals. The
heat recovery unit project shall be always developed by an HVAC designer.

5
Rev. 01.01
INTRODUCTION
1. INTRODUCTION
1.1 ACCEPTABLE ENVIRONMENT
TECHNICAL DATA
The unit is intended for indoor installation and must
be installed in a dry environment with the temperature
+41 °F to +104 °F (+5 °C to +40 °C)
For proper operation the temperature in-
side the HRV should range from -4 °F to
+104 °F (-20 °C to +40 °C), maximum humid-
ity 90%. Damage to the heat exchanger struc-
ture may result if operated outside these limits.
The unit is not designed for air containing ammable
or explosive mixtures, chemical vapors, heavy dust,
soot, grease, toxins, pathogenic organisms, etc.
Minimally ammable materials
1.3 SAFE INSTALLATION DISTANCE
ATTENTION!
Non-ammable materials
• All materials used within 4 inches (100 mm)
oftheHRVunitmustbenon-ammable(they
donotburn,ameup,burnout)orminimally
ammable (they do not burn or decompose,
e.g. drywall). Moreover, these materials must
not cover the unit’s inlets or outlets.
• The minimum safe distance of ammable
materials from the unit’s outlets is 20 inches
(500 mm).
• The minimum safe distance of ammable
materials in other directions is 4 inches (100
mm).
+40°C
+5°C
1.2 ACCESS DISTANCE
The unit should be installed so as to provide ac-
cess for maintenance, service or disassembly. This
includes, in particular, access to the cover of the
control cabinet, to duct openings, and to the cover
of the of the air lters.
a
c
b
d
UNIT a b c d
VS250 CM 30" 0" 4" 12.5"
VS400 CM 30" 0" 4" 14.5"
VS900 CM 30" 0" 4" 18.5"
VS1200 CM 30" 0" 4" 22"
4"
4"
4"
4"
4"
4"
20"
20"

6Rev. 01.01
SPECIFICATIONS
2. SPECIFICATIONS
2.1 MAIN COMPONENTS
Control Panel
Communication Cable
RS-485 (33 ft)
Fan
Main power switch
Regulator (Control)
Condensate drain
Service Access Doors
Return Air Filter
Outside Air Filter
Supply Fan
Exhaust Fan
Bypass
Core(s)
2 for VS1200/900
1 for VS400/250
Preheater
Internal CO2 Sensor
Mount Location
Main power switch
Power Wire Entry
(Mains)

7
Rev. 01.01
SPECIFICATIONS
2. SPECIFICATIONS
2.2 DIMENSIONS
a
b
B
K
k
18
2x1/2"
C
D
c
d
h
i
j
H
x z
X
Z
Y
y
INDOOR ENVIROMENT
OUTDOOR ENVIROMENT
a
b
B
K
k
18
2x1/2"
C
D
c
d
h
i
j
H
x z
X
Z
Y
y
INDOOR ENVIROMENT
OUTDOOR ENVIROMENT
UNIT H h a B b i j K k c d C D X x Y y Z z
VS250 CM 30.7 26.4 46.9 12.2 11.8 44.1 27.6 19.1 0.8 9.8 5.9 10.8 6.9 6.5 6.5 13.1 13.1 6.5 6.5
VS400 CM 42.5 38.2 55.1 12.2 11.8 52.4 39.4 23.2 0.8 11.8 7.9 12.8 8.8 9.5 9.5 20.4 20.4 9.5 9.5
VS900 CM 54.5 50.0 66.9 15.4 15.0 64.2 51.4 28.3 0.8 19.7 9.8 20.6 10.8 12.7 12.7 24.6 24.6 12.7 12.7
VS1200 CM 67.3 63.0 78.7 18.5 18.1 56.3 64.2 35.5 0.8 23.6 11.8 24.6 12.8 17.0 17.0 28.9 28.9 17.0 17.0
a
b
B
K
k
18
2x1/2"
C
D
c
d
h
i
j
H
x z
X
Z
Y
y
INDOOR ENVIROMENT
OUTDOOR ENVIROMENT
INDOOR OUTDOOR
0.71" OD (Condensate)
1/2" Flex-Conduit
Connector (Mains)

8Rev. 01.01
SPECIFICATIONS
2. SPECIFICATIONS
VS1200 CMh/e SPECIFICATIONS
Flow Rate 300 - 1200 cfm / 510 - 2040 m3/h Increments: 50 cfm / 85 m3/h
Max. External Static Pressure 2.0 inch W.C. / 498 Pa
Exchanger Efficiency (AHRI 1060) HRV: 90.6% Sensible ERV: 86.1% Sensible; 77.9% Latent; 82.9% Total
Temperature Conditions Outdoor: -4°to 104° F / -20°to 40°C Ambient: 41°to 104° F / 5°to 40°C
Max. Return Air Humidity 90%
Dimensions (L x W x D) 67.3” x 18.5” x 78.7” / 1.71 m x 0.47 m x 2 m
Shipping Dimensions (L x W x D) 75” x 25” x 91” / 1.91 m x 0.64 m x 2.3 m
Weight (Shipping) HRV: 529 lbs / 240 kg (Shipping: 678 lbs / 308 kg)
ERV: 547 lbs / 248 kg (Shipping: 701 lbs / 318 kg)
Fans (EC, Variable Speed Control) Aluminum Impeller; 1890 RPM; IP54
Filters Outside Air: MERV13 (29.53 x 15.55 x 3.78 in. / 750 x 395 x 96 mm)
Return Air: MERV9 (29.53 x 15.55 x 3.78 in. / 750 x 395 x 96 mm)
Preheater Integrated Preheater for Frost Prevention
Core Bypass PID Bypass Damper for Temperature Control
Insulation & Thermal Conductivity 2” Foam @ 0.042 W/mK / 0.024 BTU/(hr ft °F); 0.8mm Galvanized Steel Inner/Outer Casing
Duct Connection 23.62” x 11.81” / 600 mm x 300 mm; Diameter 15.75” / 400 mm
Operation Modes CAV, DCV, VAV, BMS, Economizer (Freecooling)
Certifications TUV SUD (UL 1812, CSA 22.2 No. 113) Pending
Passive Haus: Pending
FCC Pending
Sensors Temperature (10Kohm NTC Thermistors):
Outside Air, Supply Air, Supply Duct, Return Air, Exhaust Air
Pressure:
OA and RA Filter Pressure Drop
Pressure Differential at Supply Fan and Exhaust Fan (CAV)
Pressure Differential of Supply to Atmosphere (VAV)
Optional Accessories
(Provided by Ventacity)
External Outside Air and Exhaust Air Damper Modules
External DX or WCO Postheater Modules
Internally Mounted CO2 Sensor (Room CO2 Sensor Recommendations Available)
External Condensate Pump
ELECTRICAL
Voltage
Phase
Power Supply
FLA – Max
MCA
MOP
De-Ice Preheater
Preheater Temp Rise
Maximum Power
per Fan
208 VAC
1
6.2 kW
29.8 A
36.7 A
35 A
5.2 kW
7.7°C
503 W (0.67 hp)
240 VAC
1
7.9 kW
33.1 A
40.7 A
40 A
6.9 kW
10.3° C
FAN OPERATING RANGE
3.5
3.0
2.5
2.0
1.5
1.0
0.5
0.0
External Static Pressure [in W.C.]
0200 400 600 800 1,000
Flow Rate [CFM]
300 – 1,200 CFM
0 – 2.0" W.C. ESP
1,200
100% FAN SPEED
(recommended operating range)
1,400

9
Rev. 01.01
SPECIFICATIONS
2. SPECIFICATIONS
VS900 CMh/e SPECIFICATIONS
Flow Rate 200 - 900 cfm / 340 - 1529 m3/h Increments: 50 cfm / 85 m3/h
Max. External Static Pressure 2.0 inch W.C. / 498 Pa
Exchanger Efficiency (AHRI 1060) HRV: 91.2% Sensible ERV: 86.1% Sensible; 79.2% Latent; 82.3% Total
Temperature Conditions Outdoor: -4°to 104° F / -20°to 40°C Ambient: 41°to 104° F / 5°to 40°C
Max. Return Air Humidity 90%
Dimensions (H x W x D) 54.53” x 15.35” x 66.93” / 1.39 m x 0.39 m x 1.7 m
Shipping Dimensions (H x W x D) 63” x 22” x 79” / 1.6 m x 0.56 m x 2 m
Weight (Shipping) HRV: 364 lbs / 165 kg (Shipping: 467 lbs / 212 kg)
ERV: 375 lbs / 170 kg (Shipping: 481 lbs / 218 kg)
Fans (EC, Variable Speed Control) Galvanized Steel Impeller; 2600 RPM; IP54
Filters Outside Air: MERV13 (23.03 x 12.2 x 3.78 in. / 585 x 310 x 96 mm)
Return Air: MERV9 (23.03 x 12.2 x 3.78 in. / 585 x 310 x 96 mm)
Preheater Integrated Preheater for Frost Prevention
Core Bypass PID Bypass Damper for Temperature Control
Insulation & Thermal Conductivity 2” Foam @ 0.042 W/mK / 0.024 BTU/(hr ft °F); 0.8mm Galvanized Steel Inner/Outer Casing
Duct Connection 19.69” x 9.84” / 500 mm x 250 mm; Diameter 12.4” / 315 mm
Operation Modes CAV, DCV, VAV, BMS, Economizer (Freecooling)
Certifications TUV SUD (UL 1812, CSA 22.2 No. 113) Pending
Passive Haus: Pending
FCC Pending
Sensors Temperature (10Kohm NTC Thermistors):
Outside Air, Supply Air, Supply Duct, Return Air, Exhaust Air
Pressure:
OA and RA Filter Pressure Drop
Pressure Differential at Supply Fan and Exhaust Fan (CAV)
Pressure Differential of Supply to Atmosphere (VAV)
Optional Accessories
(Provided by Ventacity)
External Outside Air and Exhaust Air Damper Modules
External DX or WCO Postheater Modules
Internally Mounted CO2 Sensor (Room CO2 Sensor Recommendations Available)
External Condensate Pump
ELECTRICAL
Voltage
Phase
Power Supply
FLA – Max
MCA
MOP
De-Ice Preheater
Preheater Temp Rise
Maximum Power
per Fan
208 VAC
1
4.95 kW
23.8 A
29.1 A
30 A
3.99 kW
7.9°C
470 W (0.63 hp)
240 VAC
1
6.26 kW
26.1 A
32 A
35 A
5.3 kW
10.5° C
FAN OPERATING RANGE
3.5
3.0
2.5
2.0
1.5
1.0
0.5
0.0
External Static Pressure [in W.C.]
0100 200 300 400 500 600 700 800 900
Flow Rate [CFM]
200 – 900 CFM
0 – 2.0" W.C. ESP
(recommended operating range)
100% FAN SPEED
1,000

10 Rev. 01.01
SPECIFICATIONS
2. SPECIFICATIONS
VS400 CMh/e SPECIFICATIONS
Flow Rate 120 - 480 cfm / 204 - 816 m3/h Increments: 30 cfm / 51 m3/h
Max. External Static Pressure 2.0 inch W.C. / 498 Pa
Exchanger Efficiency (AHRI 1060) HRV: 89.7% Sensible ERV: 86.1% Sensible; 79.2% Latent; 82.3% Total
Temperature Conditions Outdoor: -4°to 104° F / -20°to 40°C Ambient: 41°to 104° F / 5°to 40°C
Max. Return Air Humidity 90%
Dimensions (L x W x D) 42.52” x 12.2” x 55.12” / 1.08 m x 0.31 m x 1.4 m
Shipping Dimensions (L x W x D) 51” x 18” x 67” / 1.3 m x 0.46 m x 1.7 m
Weight (Shipping) HRV: 198 lbs / 90 kg (Shipping: 254 lbs / 115 kg)
ERV: 203 lbs / 92 kg (Shipping: 260 lbs / 118 kg)
Fans (EC, Variable Speed Control) Galvanized Steel Impeller; 2530 RPM; IP44
Filters Outside Air: MERV13 (17.9 x 9.25 x 3.78 in. / 455 x 235 x 96 mm)
Return Air: MERV9 (17.9 x 9.25 x 3.78 in. / 455 x 235 x 96 mm)
Preheater Integrated Preheater for Frost Prevention
Core Bypass PID Bypass Damper for Temperature Control
Insulation & Thermal Conductivity 2” Foam @ 0.042 W/mK / 0.024 BTU/(hr ft °F); 0.8mm Galvanized Steel Inner/Outer Casing
Duct Connection 11.81” x 7.87” / 300 mm x 200 mm; Diameter 9.84” / 250 mm
Operation Modes CAV, DCV, VAV, BMS, Economizer (Freecooling)
Certifications TUV SUD (UL 1812, CSA 22.2 No. 113) Pending
Passive Haus: Pending
FCC Pending
Sensors Temperature (10Kohm NTC Thermistors):
Outside Air, Supply Air, Supply Duct, Return Air, Exhaust Air
Pressure:
OA and RA Filter Pressure Drop
Pressure Differential at Supply Fan and Exhaust Fan (CAV)
Pressure Differential of Supply to Atmosphere (VAV)
Optional Accessories
(Provided by Ventacity)
External Outside Air and Exhaust Air Damper Modules
External DX or WCO Postheater Modules
Internally Mounted CO2 Sensor (Room CO2 Sensor Recommendations Available)
External Condensate Pump
ELECTRICAL
Voltage
Phase
Power Supply
FLA – Max
MCA
MOP
De-Ice Preheater
Preheater Temp Rise
Maximum Power
per Fan
208 VAC
1
2.57 kW
12.2 A
15.1 A
15 A
2.21 kW
9.4°C
170 W (0.23 hp)
240 VAC
1
3.29 kW
13.7 A
16.8 A
20 A
2.93 kW
12.5° C
3.5
3.0
2.5
2.0
1.5
1.0
0.5
0.0
050 100 150 200 250 300 350 400 450 500
100% FAN SPEED
External Static Pressure [in W.C.]
Flow Rate [CFM]
120 – 480 CFM
0 – 2.0" W.C. ESP
FAN OPERATING RANGE
(recommended operating range)

11
Rev. 01.01
SPECIFICATIONS
2. SPECIFICATIONS
VS250 CMh/e SPECIFICATIONS
Flow Rate 60 - 270 cfm / 102 - 459 m3/h Increments: 15 cfm / 25.5 m3/h
Max. External Static Pressure 2.0 inch W.C. / 498 Pa
Exchanger Efficiency (AHRI 1060) HRV: 91.2% Sensible ERV: 85.7% Sensible; 75.9% Latent; 82.3% Total
Temperature Conditions Outdoor: -4°to 104° F / -20°to 40°C Ambient: 41°to 104° F / 5°to 40°C
Max. Return Air Humidity 90%
Dimensions (L x D x W) 30.7” x 12.2” x 46.9” / 0.780 m x 0.31 m x 1.19 m
Shipping Dimensions (L x D x W) 39” x 18” x 59” / 0.99 m x 0.46 m x 1.5 m
Weight (Shipping) HRV: 154 lbs / 70 kg (Shipping: 197 lbs / 89 kg)
ERV: 159 lbs / 72 kg (Shipping: 204 lbs / 93 kg)
Fans (EC, Variable Speed Control) Plastic Impeller; 3653 RPM; IP54
Filters Outside Air: MERV13 (11.2 x 9.25 x 3.78 in. / 285 x 235 x 96 mm)
Return Air: MERV9 (11.2 x 9.25 x 3.78 in. / 285 x 235 x 96 mm)
Preheater Integrated Preheater for Frost Prevention
Core Bypass PID Bypass Damper for Temperature Control
Insulation & Thermal Conductivity 2” Foam @ 0.042 W/mK / 0.024 BTU/(hr ft °F); 0.8mm Galvanized Steel Inner/Outer Casing
Duct Connection 9.84” x 5.91” / 250 mm x 150 mm; Diameter 7.87” / 200 mm
Operation Modes CAV, DCV, VAV, BMS, Economizer (Freecooling)
Certifications TUV SUD (UL 1812, CSA 22.2 No. 113) Pending
Passive Haus: Pending
FCC Pending
Sensors Temperature (10Kohm NTC Thermistors):
Outside Air, Supply Air, Supply Duct, Return Air, Exhaust Air
Pressure:
OA and RA Filter Pressure Drop
Pressure Differential of Supply to Atmosphere (VAV)
Optional Accessories
(Provided by Ventacity)
External Outside Air and Exhaust Air Damper Modules
External DX or WCO Postheater Modules
Internally Mounted CO2 Sensor (Room CO2 Sensor Recommendations Available)
External Condensate Pump
ELECTRICAL
Voltage
Phase
Power Supply
FLA – Max
MCA
MOP
De-Ice Preheater
Preheater Temp Rise
Maximum Power
per Fan
208 VAC
1
1.41 kW
6.8 A
8.2 A
10 A
1.14 kW
8.5°C
125 W (0.17 hp)
240 VAC
1
1.78 kW
7.4 A
9 A
10 A
1.51 kW
11.3° C
3.5
3.0
2.5
2.0
1.5
1.0
0.5
0.0
050 100 150 200 250 300
100% FAN SPEED
External Static Pressure [in W.C.]
Flow Rate [CFM]
60 – 250 CFM
0 – 2.0" W.C. ESP
FAN OPERATING RANGE
(recommended operating range)

12 Rev. 01.01
SPECIFICATIONS
2. SPECIFICATIONS
VS1200CM @ 1100 CFM / 0.28" W.C.
f (Hz) 63 125 250 500 1000 2000 4000 8000 Total
Ambient 42.1 55.4 57.3 52.5 51.1 47.8 43.5 31.6 61.1
Exhaust 53.9 65.4 66.6 66.7 69.0 65.2 58.3 52.6 74.0
Supply 57.5 68.4 72.1 71.0 72.7 67.9 61.5 55.7 78.0
Return (Extract) 40.1 55.7 55.3 47.3 46.4 44.1 34.0 22.7 59.3
Outside 45.1 58.9 58.7 52.5 49.2 46.2 36.6 25.9 62.7
VS900CM @ 800 CFM / 0.34" W.C.
f (Hz) 63 125 250 500 1000 2000 4000 8000 Total
Ambient 44.9 55.8 57.4 57.6 56.6 57.2 51.0 41.8 64.3
Exhaust 62.6 56.9 65.9 77.4 71.0 72.3 65.6 60.4 79.8
Supply 62.9 63.7 73.2 79.9 73.8 75.4 68.4 64.3 82.8
Return (Extract) 48.6 46.2 49.6 56.0 51.7 46.0 41.4 28.2 59.1
Outside 53.4 55.7 58.8 60.4 56.6 49.7 45.7 31.7 64.8
VS400CM @ 350 CFM / 0.5" W.C.
f (Hz) 63 125 250 500 1000 2000 4000 8000 Total
Ambient 38.4 45.9 51.6 52.2 47.1 45.8 40.1 30.7 56.6
Exhaust 51.5 60.7 68.3 70.6 64.4 63.9 59.5 51.6 74.1
Supply 52.6 61.8 68.7 71.4 65.0 64.6 60.2 52.4 74.8
Return (Extract) 43.6 50.3 57.7 52.4 43.2 35.5 29.1 20.7 59.6
Outside 45.3 51.7 58.5 53.1 43.8 36.1 29.6 21.4 60.5
VS250CM @ 225 CFM / 0.5" W.C.
f (Hz) 63 125 250 500 1000 2000 4000 8000 Total
Ambient 35.7 42.7 53.1 55.6 46.3 43.8 37.2 33.9 58.2
Exhaust 52.7 58.5 65.0 67.5 63.0 62.5 59.5 59.4 71.8
Supply 52.6 59.3 65.0 69.1 64.9 64.0 61.2 60.4 73.1
Return (Extract) 44.3 50.6 55.1 54.6 44.7 40.0 32.8 43.7 59.1
Outside 46.6 52.8 55.2 56.0 46.0 41.4 34.7 46.8 60.3
2.4 SOUND POWER LEVEL LwA (dBA)

13
Rev. 01.01
UNPACKING
3. UNPACKING
VSXXXXCMx
3.1 INSPECT DELIVERY 3.2 UNPACK THE UNIT
READ CAREFULLY!
READ CAREFULLY!
● Inspectthepackagingfordamagesimmediate-
ly upon delivery. In case of damage in the pack-
aging, notify the carrier. If a complaint is not
submitted in due time, it will be disregarded.
● Ensuretheproductcorrespondstotheorder.If
it doesn’t, do not unpack it and contact the sup-
plier immediately.
● After unpacking, check the condition of the
unit and all the components thereof. In case of
doubt, contact the supplier.
● Donotuseadamagedunit.
● Iftheunitisn’tunpackedupondelivery,storeit
indoors, in a dry place, at temperatures ranging
from +41 °F to +104 °F.
● Ifduringtransporttheunitwasexposedtotem-
peratures lower than 0°C, leave it unpacked for
at least two hours at room temperature before
connecting it in order to level the temperature
inside the unit.
The product must be disposed
of pursuant to the local
regulations.
The product contains batteries
that must be recycled or
disposed of apart from the
common waste.
When the batteries or the
product reach the end of
their lifespan, contact the
distributor or the local
authorities for recycling.
The separate collection and
recycling of product and
batteries contribute with the
care of natural resources
and ensures that they will be
recycled in a health-conscious
and environmentally friendly
manner.
●AlltheVSCMunitsmustbeplacedhorizontally.
Any other position is forbidden.
TECHNICAL DATA
The unit must be installed so that the direction of the air
exhaust corresponds to that of the distribution system.
The unit should be installed so as to provide access for
maintenance, service or disassembly. This includes, in
particular, access to the inspection aps and their open-
ing, access to the cover of the control unit’s cabinet, to
connect side units and to the cover of the of the air lter.

14 Rev. 01.01
INSTALLATION
4. INSTALLATION
•Thesupportoftheunitshouldbesufciently
strong, it must correspond to the unit’s weight!
• Given its weight, lifting equipment will be re-
quired when installing the unit (e.g. a forklift)
or at least two more people to hold it.
●4M8locknuts
●4threadedrods
●4dowelsofsuitabletypeandsize(dependingon
the material of the ceiling and the weight of the
unit)
●drillwithbitsofsuitabletypeandsize
●pliersandwrenches
Place the unit horizontally and then tilt it
3° to drain the condensate.
YOU WILL NEED
UNIT A B
VS250 CM 27.6 44.1
VS400 CM 39.4 52.4
VS900 CM 51.2 64.2
VS1200 CM 64.2 76.0
Use the drilling template below
to place the anchoring points.
A
B
Drill the openings in the ceiling, check the strength
of the material and fasten the unit to the side
brackets
with the ZTZ-M8/1,0 threaded rods.
ATTENTION!
UNIT
Weight of unit (lbs) Weight of accessories (lbs)
Standard W.C.O. module DX module
VS250 CM 154.3 56.2 52.9
VS400 CM 198.4 70.5 66.1
VS900 CM 363.8 81.6 77.2
VS1200 CM 529.1 94.8 88.2
4.1 HANGING THE UNIT

15
Rev. 01.01
INSTALLATION
4. INSTALLATION
4.2 CONNECTING DUCTWORK
• The connected ductwork must have the same dimen-
sions as the intake and exhaust openings of the unit.
Ductsofasmallerdiametermayreducetheefcien-
cy of the unit and, in some cases, also its lifespan.
• Connect the intake and exhaust openings (rectangu-
lar/circular opening) with exible joints in order to
reduce vibrations.
READ CAREFULLY!
All the connections to the ductwork must be sealed
with sealant or tape.
The minimum distance between bends in the duc-
twork or adapters and the neck of the unit is 20".
4.2-1 Protective grille for openings
(not included)
If the unit’s opening is not connected to the duct-
work, rain blinds will be required to prevent water
and moving particles coming into contact with the
fan, the heating rods, etc.

16 Rev. 01.01
INSTALLATION
4. INSTALLATION
4.3 ELECTRICAL INSTALLATION
ATTENTION!
• Before beginning repair or modication of
the HRV unit, make sure the main power
switch is off!
• The wiring must be done by a person authorized
to perform electrical installations. It is neces-
sary to follow all instructions in this manual and
to comply with local laws and regulations.
• Before connecting the wiring, make sure that
terminal indications match the diagram. If in
doubt, do not connect the unit, and contact the
supplier!
• The unit must be connected to the mains using
a heat-protected, insulated cable with a cross-
section that meets local regulations.
• To maintain electrical protection, all cables must
t in the hole on the sides of the control unit
casing (1/2" ex-conduit connector).
• Any changes or modications to the internal
wiring of the unit are prohibited and will void
the warranty!
• The unit’s correct operation can be guaranteed
only if original accessories are used.
• If it is necessary to install a sensor or control
component in the unit or on its casing, consult
beforehand with the unit manufacturer or rep-
resentative.
4.3.1 SUPPLY WIRING
Adjacent to the main power switch is a 7/8" hole
through the regulator box and a pre-installed 1/2"
ex-conduit connector. If the electrical installer
decides, the pre-installed connector can be re-
moved and supplanted with an appropriate tting
rated for:
• The listed Maximum Overcurrent Protection of
the device.
• The listed voltage of the device.
• 3 10AWG insulated wires: Line 1,
Line 2 (Neutral), and Protective Earth Ground.
• Compliance with local laws and regulations.
Route the power wires in an appropriate conduit
from the service to the unit. Fix the conduit the
the regulator box power wire entry connector.
Terminate the power supply wires to the terminal
blocks labeled:
"MAIN POWER SUPPLY"
Wire the mains (PE, L1, L2) to the appropriate ter-
minal block (PE, L, N).
MAIN POWER
SUPPLY
Power Switch
Terminal Blocks
Conduit Connector
PE
N
L

17
Rev. 01.01
INSTALLATION
4. INSTALLATION
Accessories ordered separately
4.4 DAMPER MODULE INSTALL
These rectangular air aps are used to close the
air supply connected to the unit. See Specica-
tions section for duct connection dimensions.
●2rectangularaps(ofsuitabledimensions)
●2actuators*(withoneortwo230Vwires)
●8M8screwsandnuts
●16washers
●suitablewrench
●Flat and Phillips screwdriver, sealing tape and
sealant
*IncludedwithVentacitysupplieddampermodule
YOU WILL NEED
Install the ap in the ductwork at a distance of
about 7 feet before the fresh air intake and at
about 7 feet from the exhaust neck. Connect the
actuators to the appropriate terminals in the con-
trol cabinet. See Connecting the wiring and elec-
trical accessories
Place the ap so it will be fully closed when the
unit is off and fully open when the unit is on. Any
other position could damage the unit.
4.5 CONDENSATE DRAIN INSTALL
It is recommended to connect the condensate
drain to the drainage piping. The siphon has built-
in antifreeze protection.
YOU WILL NEED
• 1 siphon
• PVC drainage pipes
• sealing for the drainage piping
h2h1
h1
Siphon courant Ball Siphon
The tank’s neck is located on the
side/sides of the unit.
Attach to it the siphon or to a hose
connected to the drainage.
- Make sure that the unit is tilted 3° in order to
drain the condensate.
5.12"

18 Rev. 01.01
INSTALLATION
4. INSTALLATION
The external module includes sensors, PE grounding conductor and fasteners.
MODUL
JEDNOTKA
3D-Intelliclamp
4 x SR-ISO7380-5,0x25
(NA 1 UZAVER 3D-Intelliclamp)
A
DETAIL A
MĚŘÍTKO 1 : 1
SR-ISO7380-5,0x25
M8x35 DIN 912
3.
1. 2.
4. Wiring
See subsequent diagrams
Wiring example of extrnal water change-over (WCO) module
Temperaturte sensor
Supply duct after post-heater/cooler
Temperaturte sensor
Water-IN
Temperaturte sensor
Water-OUT
4.6 POSTHEATER MODULE INSTALLATIONS

19
Rev. 01.01
INSTALLATION
4. INSTALLATION
Wiring example of extrnal DX module
Temperaturte sensor
Supply duct after post-heater/cooler
Temperaturte sensor
Coil-IN
5. Enable external coil module in service menu (more info in Commissioning)
Route cat5e/6 cable from the SBC100 (ETH1) through the building and into the regulator box
via the grommet. Terminate the cat5e/6 cable at the ethernet port on the Module A board.
1001
QUICK START INSTRUCTIONS:
For more help at each step, scan this QR code
or go to: ventacity.com/qr/1001
1. Mount the SBC100 on a wall (see Installation Guide) with either:
a. Good Verizon LTE signal (3 bars or more of LTE signal on a phone) or,
b. Within close proximity of an Ethernet connection with internet service
(if used, plug into the ETH0 port of the Gateway).
2. If you are connecting any external Modbus devices, wire the Modbus
cable to the RS-485 terminals of the Gateway. Be sure to review the
QR code help for advanced wiring considerations.
3. If there are any Ethernet devices (such as Ventacity HRV/ERVs) under the
control of the SBC100:
a. For exactly one Ethernet device, plug it directly into the ETH1 port of
the Gateway.
b. For more than one Ethernet device, plug each device into an
Optional Ethernet Switch which is connected to the ETH1 port of
the Gateway.
4. Connect the power cord, powering on the SBC100.
5. You are now ready to begin using the SBC100. Refer to the QR code
help for next steps.
SBC100
eth1 eth0
RS-485
SBG100 Gateway
OPTIONAL: MODBUS
CONVERTER MOUNTING
LOCATION
OPTIONAL: ETHERNET
SWITCH MOUNTING
LOCATION
EXTERNAL MODBUS DEVICES (OPTIONAL)
ETHERNET FOR INTERNET (OPTIONAL)
ETHERNET FOR DEVICES (OPTIONAL)
POWER
SUPPLY
100-240VAC
50-60 HZ
1PH
CELL ANTENNA
WIFI ANTENNA
POWER CORD
IEC CONNECTOR TO OUTLET
QUICK START LABEL – SEPT 2018
ETH1 ETH0
SCHEMATIC
VENTILATOR
Module A
4.7 SBC100 INSTALLATION
Module A Board
Regulator Box

20 Rev. 01.01
INSTALLATION
4. INSTALLATION
Electrical accessories must be connected to the terminals located in the control cabinet according to the
wiring diagram and the markings on the terminals.
1. A (1,4) SAFETY THERMOSTAT POSTHEATING
2. A (2,3) SAFETY PREHEATING THERMOSTAT
3. A (5-6) LF1 - FLAP INLET (output L-open), LF2 - FLAP OUTLET ( output
L-open)
4. A (7-8) RUN CONTACT (output -NO/NC settable)
5. A (9-10) ERROR CONTACT (output NO)
6. A (11-12) PREHEATER WATER PUMP (11 - Lint, 12 - Lout)
7. A (13-14) BOOST (input NO)
8. A (15-16) FIRE (input NC)
9. A (17-18) EXTERNAL CONTROL ON/OFF (input NC)
10. A (19,20) OUTPUT PERFORMANCE OF POSTHEATING (0-10V OR PWM)
11. A (43,44) AQS SENSOR 0-10V (input)
3-050-D13490
Control panel
1
1.
1
5.
1
6.
1
2.
1
7.
1
8.
1
9. 1
10. 1
11. 1
12. 1
13. 1
14. 1
15. 1
16. 1
17.
1
3.
1
4.
1
20. 1
21. 1
22.
1
18. 1
19.
EN RU CZ
1. A (5-6) LF1 - FLAP INLET (output L-open), LF2 - FLAP OUTLET ( output L-open) LF1 ( L-), LF2 - ( L-) LF1 - KLAPKA PŘÍVOD (výstup L-open), LF2 - KLAPKA ODVOD ( výstup L-open)
2. A (7-8) RUN CONTACT (output -NO/NC settable) RUN ( - NO/NC ) RUN KONTACT (výstup -NO/NC nastavitelné)
3. A (9-10) ERROR CONTACT (output NO) ( NO) ERROR KONTACT (výstup NO)
4. A (11-12) PREHEATER WATER PUMP (11 - Lint, 12 - Lout) (11 - Lint,12 - Lout) VODNÍ ČERPADLO PŘEDEHŘEVU (11 - Lint, 12 - Lout)
5. A (13-14) BOOST (input NO) BOOST ( NO) BOOST (vstup NO)
6. A (15-16) FIRE (input NC) FIRE - ( NC) FIRE (vstup NC)
7. A (17-18) EXTERNAL CONTROL ON/OFF (input NC) ON/OFF ( NC) EXTERNÍ OVLÁDÁNÍ ON/OFF (vstup NC)
8. A (18-19) AQS SENSOR 0-10V (input) 0-10 () ČIDLO KVALITY VZDUCHU 0-10V (vstup)
9. B (1-2) WATER PUMP (1 - Lint, 2 - Lout) (1 - Lint, 2 - Lout) VODNÍ ČERPADLO (1 - Lint, 2 - Lout)
10. B (3-4) HEAT PUMP CONTROL settable (output - ON/OFF) ( - ON/OFF) ŘÍZENÍ TEPELNÉHO ČERPADLA nastavitelné (výstup - ON/OFF)
11. B (5-6) ADIABATIC MODULE output - ON/OFF ( - ON/OFF) ADIABATICKÝ MODUL výstup - ON/OFF
12. B (7-8) COOL / HEAT settable (CO = NC/NO - DX = output settable) / (CO = NC/NO - DX = ) CHLAZENÍ / TOPENÍ nastavitelné (CO = NC/NO - DX = výstup nastavitelné)
13. B (9-10) ADIABATIC MODULE ERROR input NO ERROR ( NO) ADIABATICKÝ MODUL ERROR vstup NO
14. B (11-12) HEAT PUMP DEFROST settable (input NC/NO) ( NC/NO) ODMRAŽOVÁNÍ TEPELNÉHO ČERPADLA nastavitelné (vstup NC/NO)
15. B (13-14) HEAT PUMP ERROR settable (input NC/NO) ( NC/NO) CHYBA TEPELNÉHO ČERPADLA nastavitelné (vstup NC/NO)
16. B (15-16) PIR (input NC) PIR ( NC) POHYBOVÉ ČIDLO PIR (vstup NC)
17. B (17-18) CONDENSATE OVERFLOW (input NC) ( NC) ČIDLO PŘETEČENÍ KONDENZÁTU (vstup NC)
18. B (46-47) EXTERNAL TEMPERATURE SENSOR (external postheater - input) ( - ) EXTERNÍ TEPLOTNÍ ČIDLO (externí dohřev - vstup)
19. B (44-45) EXTERNAL TEMPERATURE SENSOR (adiabatic module / recirc. chamber - input) ( / - ) EXTERNÍ TEPLOTNÍ ČIDLO (adiabatický modul / recirkulační komora - input)
20. B (38-39) EXTERNAL PREHEATER (output - Water= 0-10V, electric=PWM) ( - =0-10, =PWM) EXTERNÍ PŘEDEHŘEV (výstup - vodní=0-10V, elektrický=PWM)
21 B (36-37) EXTERNAL POSTHEATER (output - Water= 0-10V, electric=PWM) ( - =0-10, =PWM) EXTERNÍ DOHŘEV (výstup - vodní=0-10V, elektrický=PWM)
22 B (34-35) RECIRCULATION CHAMBER (output 0-10V) ( 0-10) RECIRKULAČNÍ KOMORA (výstup 0-10V)
A
B
Control panel
1
1.
1
5.
1
6.
1
2.
1
7.
1
8.
1
9.
1
10.
1
11.
1
12.
1
13.
1
14.
1
15.
1
16.
1
17.
1
3.
1
4.
1
20.
1
21.
1
22.
1
18.
1
19.
EN RU CZ
1. A (5-6) LF1 - FLAP INLET (output L-open), LF2 - FLAP OUTLET ( output L-open) LF1 ( L-), LF2 - ( L-) LF1 - KLAPKA PŘÍVOD (výstup L-open), LF2 - KLAPKA ODVOD ( výstup L-open)
2. A (7-8) RUN CONTACT (output -NO/NC settable) RUN ( - NO/NC ) RUN KONTACT (výstup -NO/NC nastavitelné)
3. A (9-10) ERROR CONTACT (output NO) ( NO) ERROR KONTACT (výstup NO)
4. A (11-12) PREHEATER WATER PUMP (11 - Lint, 12 - Lout) (11 - Lint,12 - Lout) VODNÍ ČERPADLO PŘEDEHŘEVU (11 - Lint, 12 - Lout)
5. A (13-14) BOOST (input NO) BOOST ( NO) BOOST (vstup NO)
6. A (15-16) FIRE (input NC) FIRE - ( NC) FIRE (vstup NC)
7. A (17-18) EXTERNAL CONTROL ON/OFF (input NC) ON/OFF ( NC) EXTERNÍ OVLÁDÁNÍ ON/OFF (vstup NC)
8. A (18-19) AQS SENSOR 0-10V (input) 0-10 () ČIDLO KVALITY VZDUCHU 0-10V (vstup)
9. B (1-2) WATER PUMP (1 - Lint, 2 - Lout) (1 - Lint, 2 - Lout) VODNÍ ČERPADLO (1 - Lint, 2 - Lout)
10. B (3-4) HEAT PUMP CONTROL settable (output - ON/OFF) ( - ON/OFF) ŘÍZENÍ TEPELNÉHO ČERPADLA nastavitelné (výstup - ON/OFF)
11. B (5-6) ADIABATIC MODULE output - ON/OFF ( - ON/OFF) ADIABATICKÝ MODUL výstup - ON/OFF
12. B (7-8) COOL / HEAT settable (CO = NC/NO - DX = output settable) / (CO = NC/NO - DX = ) CHLAZENÍ / TOPENÍ nastavitelné (CO = NC/NO - DX = výstup nastavitelné)
13. B (9-10) ADIABATIC MODULE ERROR input NO ERROR ( NO) ADIABATICKÝ MODUL ERROR vstup NO
14. B (11-12) HEAT PUMP DEFROST settable (input NC/NO) ( NC/NO) ODMRAŽOVÁNÍ TEPELNÉHO ČERPADLA nastavitelné (vstup NC/NO)
15. B (13-14) HEAT PUMP ERROR settable (input NC/NO) ( NC/NO) CHYBA TEPELNÉHO ČERPADLA nastavitelné (vstup NC/NO)
16. B (15-16) PIR (input NC) PIR ( NC) POHYBOVÉ ČIDLO PIR (vstup NC)
17. B (17-18) CONDENSATE OVERFLOW (input NC) ( NC) ČIDLO PŘETEČENÍ KONDENZÁTU (vstup NC)
18. B (46-47) EXTERNAL TEMPERATURE SENSOR (external postheater - input) ( - ) EXTERNÍ TEPLOTNÍ ČIDLO (externí dohřev - vstup)
19. B (44-45) EXTERNAL TEMPERATURE SENSOR (adiabatic module / recirc. chamber - input) ( / - ) EXTERNÍ TEPLOTNÍ ČIDLO (adiabatický modul / recirkulační komora - input)
20. B (38-39) EXTERNAL PREHEATER (output - Water= 0-10V, electric=PWM) ( - =0-10, =PWM) EXTERNÍ PŘEDEHŘEV (výstup - vodní=0-10V, elektrický=PWM)
21 B (36-37) EXTERNAL POSTHEATER (output - Water= 0-10V, electric=PWM) ( - =0-10, =PWM) EXTERNÍ DOHŘEV (výstup - vodní=0-10V, elektrický=PWM)
22 B (34-35) RECIRCULATION CHAMBER (output 0-10V) ( 0-10) RECIRKULAČNÍ KOMORA (výstup 0-10V)
AB
F1 2A
Control panel
1
1.
1
5.
1
6.
1
2.
1
7.
1
8.
1
9.
1
10.
1
11.
1
12.
1
13.
1
14.
1
15.
1
16.
1
17.
1
3.
1
4.
1
20.
1
21.
1
22.
1
18.
1
19.
1.
Control panel
1
1.
1
5.
1
6.
1
2.
1
7.
1
8.
1
9.
1
10.
1
11.
1
12.
1
13.
1
14.
1
15.
1
16.
1
17.
1
3.
1
4.
1
20.
1
21.
1
22.
1
18.
1
19.
Control panel
1
1.
1
5.
1
6.
1
2.
1
7.
1
8.
1
9.
1
10.
1
11.
1
12.
1
13.
1
14.
1
15.
1
16.
1
17.
1
3.
1
4.
1
20.
1
21.
1
22.
1
18.
1
19.
2. 3. 4. 5. 6. 7. 8. 9. 10.
11.
EN RU CZ
1. A (1,4) SAFETY THERMOSTAT POSTHEATING BEZPEČNOSTNÍ TERMOSTAT DOHŘEVU
2. A (2,3) SAFETY PREHEATING THERMOSTAT BEZPEČNOSTNÍ TERMOSTAT PŘEDEHŘEVU
3. A (5-6) LF1 - FLAP INLET (output L-open), LF2 - FLAP OUTLET ( output L-open) LF1 ( L-), LF2 - ( L-) LF1 - KLAPKA PŘÍVOD (výstup L-open), LF2 - KLAPKA ODVOD ( výstup L-open)
4. A (7-8) RUN CONTACT (output -NO/NC settable) RUN ( - NO/NC ) RUN KONTACT (výstup -NO/NC nastavitelné)
5. A (9-10) ERROR CONTACT (output NO) ( NO) ERROR KONTACT (výstup NO)
6. A (11-12) PREHEATER WATER PUMP (11 - Lint, 12 - Lout) (11 - Lint,12 - Lout) VODNÍ ČERPADLO PŘEDEHŘEVU (11 - Lint, 12 - Lout)
7. A (13-14) BOOST (input NO) BOOST ( NO) BOOST (vstup NO)
8. A (15-16) FIRE (input NC) FIRE - ( NC) FIRE (vstup NC)
9. A (17-18) EXTERNAL CONTROL ON/OFF (input NC) ON/OFF ( NC) EXTERNÍ OVLÁDÁNÍ ON/OFF (vstup NC)
10. A (19,20) OUTPUT PERFORMANCE OF POSTHEATING 010V OR PWM 010 PWM VÝSTUP REGULACI VÝKONU DOHŘEVU 010V nebo PWM
11. A (43,44) AQS SENSOR 0-10V (input) 0-10 () ČIDLO KVALITY VZDUCHU 0-10V (vstup)
Control panel
1
1.
1
5.
1
6.
1
2.
1
7.
1
8.
1
9.
1
10.
1
11.
1
12.
1
13.
1
14.
1
15.
1
16.
1
17.
1
3.
1
4.
1
20.
1
21.
1
22.
1
18.
1
19.
EN RU CZ
1. A (5-6) LF1 - FLAP INLET (output L-open), LF2 - FLAP OUTLET ( output L-open) LF1 ( L-), LF2 - ( L-) LF1 - KLAPKA PŘÍVOD (výstup L-open), LF2 - KLAPKA ODVOD ( výstup L-open)
2. A (7-8) RUN CONTACT (output -NO/NC settable) RUN ( - NO/NC ) RUN KONTACT (výstup -NO/NC nastavitelné)
3. A (9-10) ERROR CONTACT (output NO) ( NO) ERROR KONTACT (výstup NO)
4. A (11-12) PREHEATER WATER PUMP (11 - Lint, 12 - Lout) (11 - Lint,12 - Lout) VODNÍ ČERPADLO PŘEDEHŘEVU (11 - Lint, 12 - Lout)
5. A (13-14) BOOST (input NO) BOOST ( NO) BOOST (vstup NO)
6. A (15-16) FIRE (input NC) FIRE - ( NC) FIRE (vstup NC)
7. A (17-18) EXTERNAL CONTROL ON/OFF (input NC) ON/OFF ( NC) EXTERNÍ OVLÁDÁNÍ ON/OFF (vstup NC)
8. A (18-19) AQS SENSOR 0-10V (input) 0-10 () ČIDLO KVALITY VZDUCHU 0-10V (vstup)
9. B (1-2) WATER PUMP (1 - Lint, 2 - Lout) (1 - Lint, 2 - Lout) VODNÍ ČERPADLO (1 - Lint, 2 - Lout)
10. B (3-4) HEAT PUMP CONTROL settable (output - ON/OFF) ( - ON/OFF) ŘÍZENÍ TEPELNÉHO ČERPADLA nastavitelné (výstup - ON/OFF)
11. B (5-6) ADIABATIC MODULE output - ON/OFF ( - ON/OFF) ADIABATICKÝ MODUL výstup - ON/OFF
12. B (7-8) COOL / HEAT settable (CO = NC/NO - DX = output settable) / (CO = NC/NO - DX = ) CHLAZENÍ / TOPENÍ nastavitelné (CO = NC/NO - DX = výstup nastavitelné)
13. B (9-10) ADIABATIC MODULE ERROR input NO ERROR ( NO) ADIABATICKÝ MODUL ERROR vstup NO
14. B (11-12) HEAT PUMP DEFROST settable (input NC/NO) ( NC/NO) ODMRAŽOVÁNÍ TEPELNÉHO ČERPADLA nastavitelné (vstup NC/NO)
15. B (13-14) HEAT PUMP ERROR settable (input NC/NO) ( NC/NO) CHYBA TEPELNÉHO ČERPADLA nastavitelné (vstup NC/NO)
16. B (15-16) PIR (input NC) PIR ( NC) POHYBOVÉ ČIDLO PIR (vstup NC)
17. B (17-18) CONDENSATE OVERFLOW (input NC) ( NC) ČIDLO PŘETEČENÍ KONDENZÁTU (vstup NC)
18. B (46-47) EXTERNAL TEMPERATURE SENSOR (external postheater - input) ( - ) EXTERNÍ TEPLOTNÍ ČIDLO (externí dohřev - vstup)
19. B (44-45) EXTERNAL TEMPERATURE SENSOR (adiabatic module / recirc. chamber - input) ( / - ) EXTERNÍ TEPLOTNÍ ČIDLO (adiabatický modul / recirkulační komora - input)
20. B (38-39) EXTERNAL PREHEATER (output - Water= 0-10V, electric=PWM) ( - =0-10, =PWM) EXTERNÍ PŘEDEHŘEV (výstup - vodní=0-10V, elektrický=PWM)
21 B (36-37) EXTERNAL POSTHEATER (output - Water= 0-10V, electric=PWM) ( - =0-10, =PWM) EXTERNÍ DOHŘEV (výstup - vodní=0-10V, elektrický=PWM)
22 B (34-35) RECIRCULATION CHAMBER (output 0-10V) ( 0-10) RECIRKULAČNÍ KOMORA (výstup 0-10V)
A
B
12. 13. 14. 15. 16. 17. 18. 19. 20.
21. 22. 23. 24. 25.
12. B (1-2) WATER PUMP (1 - Lint, 2 - Lout) (1 - Lint, 2 - Lout) VODNÍ ČERPADLO (1 - Lint, 2 - Lout)
13. B (3-4) HEAT PUMP CONTROL settable (output - ON/OFF) ( - ON/OFF) ŘÍZENÍ TEPELNÉHO ČERPADLA nastavitelné (výstup - ON/OFF)
14. B (5-6) ADIABATIC MODULE output - ON/OFF ( - ON/OFF) ADIABATICKÝ MODUL výstup - ON/OFF
15. B (7-8) COOL / HEAT settable (CO = NC/NO - DX = output settable) / (CO = NC/NO - DX = ) CHLAZENÍ / TOPENÍ nastavitelné (CO = NC/NO - DX = výstup nastavitelné)
16. B (9-10) ADIABATIC MODULE ERROR input NO ERROR ( NO) ADIABATICKÝ MODUL ERROR vstup NO
17. B (11-12) HEAT PUMP DEFROST settable (input NC/NO) ( NC/NO) ODMRAŽOVÁNÍ TEPELNÉHO ČERPADLA nastavitelné (vstup NC/NO)
18. B (13-14) HEAT PUMP ERROR settable (input NC/NO) ( NC/NO) CHYBA TEPELNÉHO ČERPADLA nastavitelné (vstup NC/NO)
19. B (15-16) PIR (input NC) PIR ( NC) POHYBOVÉ ČIDLO PIR (vstup NC)
20. B (17-18) CONDENSATE OVERFLOW (input NC) ( NC) ČIDLO PŘETEČENÍ KONDENZÁTU (vstup NC)
21. B (46-47) EXTERNAL TEMPERATURE SENSOR (external postheater - input) ( - ) EXTERNÍ TEPLOTNÍ ČIDLO (externí dohřev - vstup)
22. B(44-45) EXTERNAL TEMPERATURE SENSOR (adiabatic module / recirc. chamber
- input)
( / - ) EXTERNÍ TEPLOTNÍ ČIDLO (adiabatický modul / recirkulační komora - input)
23. B (38-39) EXTERNAL PREHEATER (output - Water= 0-10V) ( - =0-10) EXTERNÍ PŘEDEHŘEV (výstup - vodní=0-10V)
24. B (36-37) EXTERNAL POSTHEATER (output - Water= 0-10V) ( - =0-10) EXTERNÍ DOHŘEV (výstup - vodní=0-10V)
25. B(34-35) RECIRCULATION CHAMBER (output 0-10V) ( 0-10) RECIRKULAČNÍ KOMORA (výstup 0-10V)
4.8 ELECTRICAL ACCESSORIES