starting capacitor should also be added.
A capacitor with low series resistance is required, for it can release
peak value current required by starting. For example, if the lock is started to lock on in case of
+12V, when the resistor is connected, favorable locking status can be maintained when the
voltage is reduced to about +8V.
(2) Power supply time for the electric lock (especially the pulse lock) should be set properly.
For example, as to pulse lock, the power supply time should be set within 0.1-0.5 second in
order to prevent heating from the coil inside the lock.
Programming of the Access Controller
Press ENT and function keys to enter programming mode.
Press ENT, POW ER light (red), OK light (green) and MODE light (orange) are all lit.
Input five-digit system password and you will a chirp from the buzzer. Then POWERlight (red),
OK light (green) and MODE light (orange) all go out and the access controller enters system
programming mode.
Note: The password length of 4-8 bit arbitrary figure, if you forget your password, please do
the hardware system initialization, the initial password is 12345
"0" button to open the door to amend delay time (in the programming mode effective)
(1) "0" button.
(2) According to "5" (for 5 seconds delay, delay here range of 1-255
Note:
This Access Controller supports three types of opening mode, namely, card, password and card
plus password.
When the user is inputting password, no card can be read by the controller at the same time.