manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Veris Industries
  6. •
  7. Switch
  8. •
  9. Veris Industries Hawkeye H608 User manual

Veris Industries Hawkeye H608 User manual

Z201757-0J Page 1 of 4 ©2019 Veris Industries USA 800.354.8556 or +1.503.598.4564 / suppor[email protected] 0619
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.
Other companies’ trademarks are hereby acknowledged to belong to their respective owners.
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
• Follow safe electrical work practices.
See NFPA 70E in the USA, or applicable local codes.
• This equipment must only be installed and serviced by qualified electrical personnel.
• Read, understand and follow the instructions before installing this product.
• Turn off all power supplying equipment before working on or inside the equipment.
• Use a properly rated voltage sensing device to confirm power is off.
DO NOT DEPEND ON THIS PRODUCT FOR VOLTAGE INDICATION
• Only install this product on insulated conductors.
Failure to follow these instructions will result in death or serious injury.
A qualified person is one who has skills and knowledge related to the construction and
operation of this electrical equipment and the installation, and has received safety
training to recognize and avoid the hazards involved. NEC Article 100
No responsibility is assumed byVeris Industries for any consequences arising out of the
use of this material.
DANGER
NOTICE
• This product is not intended for life or safety applications.
• Do not install this product in hazardous or classied locations.
• The installer is responsible for conformance to all applicable codes.
• Mount this product inside a suitable re and electrical enclosure.
Installation Guide
Current Monitoring TM
Product Overview
The H608 is a current-sensitive switching device that monitors current (amperage) in the conductor passing
through it. A change in amperage in the monitored conductor that crosses the switch (setpoint) threshold plus the
hysteresis value causes the resistance of the FET status output to change state, similar to the action of a mechanical
switch. In this model, the setpoint is adjustable through the action of a 20-turn potentiometer (see the Calibration
section). The status output is suitable for connection to building controllers or other appropriate data acquisition
equipment operating at up to 30 volts. The H608 requires no external power supply to generate its output.
H608
Split-Core Current Switch, Adjustable Trip Point
Specications
Sensor Power Induced from the monitored conductor
Amperage Range 0.5 to 175 A continuous
Status Output Ratings N.O. 1.0 A @ 30 Vac/dc, not polarity sensitive
Insulation Class 600 Vac RMS (UL); 300 Vac (CE)
Setpoint Adjustable, 0.5 A or less
Frequency Range 50/60 Hz
Temperature Range -15 to 60 °C (5 to 140 °F)
Humidity Range 10-90% RH non-condensing
Hysteresis 10% typical
O State Resistance Open switch represents >1 MΩ
On State Resistance Closed switch represents < 200 mΩ
Terminal Block Max. Wire Size 24 to 14 AWG (0.2 to 2.1 mm2)
Terminal Block Torque 3.5 to 4.4 in-lbs (0.4 to 0.5 N-m)
Mounting Location Not suitable for wet locations. For indoor use only.
COMPLIANCE INFORMATION
Agency Approvals UL508 open device listing, CE: EN61010-1
Installation Category Cat. III, pollution degree 2
TM
For applications requiring double or reinforced insulation, please contact the factory.
The product design provides basic insulation only.
Do not use the LED indicators as evidence of applied voltage.
Z201757-0J Page 2 of 4 ©2019 Veris Industries USA 800.354.8556 or +1.503.598.4564 / suppor[email protected] 0619
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.
Other companies’ trademarks are hereby acknowledged to belong to their respective owners.
H608 Installation Guide
TM
Disconnect and lock out power to the enclosure containing the conductor to be
monitored.
1. Locate a mounting surface for the removable mounting bracket
that will allow the monitored conductor to pass through the center
window when it is installed and that will keep the product at least
½” (13 mm) from any uninsulated conductors. Determine cable
routing for the controller connection, allowing the wiring to reach
the mounting location.
2. Drill holes to mount the bracket to the chosen surface using the
included screws.
3. Wire the output connections from the sensor to the controller (solid-
state contact).
4. Snap the sensor over the conductor and clip the assembly to the
mounting bracket. Important: If there is a paper inhibitor
sheet between the contacts, remove before use.
5. Secure the enclosure and reconnect power.
6. Calibrate the sensor with the load running normally.
Installation
Dimensions
2.5"
(64 mm)
2.1"
(54 mm)
3.5"
(89 mm)
2.9"
(74 mm)
0.4”x 0.2”
(10 mm x 5 mm)
Slot (2x)
1.2"
(31 mm)
Removable Mounting Bracket
0.7"
(18 mm)
0.5"
(13 mm)
2.1"
(54 mm)
1.0"
(26 mm)
0.6"
(16 mm)
Motor
Fan
DDC CONTROLLER
DI
CONTACTOR
Insulated Conductor ONLY
Z201757-0J Page 3 of 4 ©2019 Veris Industries USA 800.354.8556 or +1.503.598.4564 / suppor[email protected] 0619
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.
Other companies’ trademarks are hereby acknowledged to belong to their respective owners.
H608 Installation Guide
TM
Notes For load currents greater than sensor maximum rating:
Use a 5 Amp (H68xx series) current transformer (CT) as shown. This technique can be combined with wrapping (see below) to add
range for a low current load on a high current source.
DANGER: 5A CTs can present
hazardous voltages. Install
CTs in accordance with
manufacturer's instructions.
Terminate the CT secondary
before applying current.
CAUTION
RISK OF EQUIPMENT DAMAGE
• Derate the product’s maximum current for the number of turns
through the sensing window using the following formula.
Rated Max. Amps ÷ Number of Turns = Max. monitored Amps
e.g. : 100A ÷ 4 Turns = 25 Amps max. in monitored conductor
• Failure to follow these instructions can result in overheating
and permanent equipment damage.
H68xx-5A CT
>175 A (sensor max.)
< 0.5 A (Sensor Min.)
For load currents less than sensor minimum rating:
Wrap the monitored conductor through the center window and around the sensor body to produce multiple turns. This increases
the current measured by the transducer. Program the controller to account for the extra turns (e.g., if four turns pass through the
sensor (as shown) divide the normal reading by 4).
240 A
300A:5A
4 A
4x
0.5A
0.3 A
Z201757-0J Page 4 of 4 ©2019 Veris Industries USA 800.354.8556 or +1.503.598.4564 / suppor[email protected] 0619
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.
Other companies’ trademarks are hereby acknowledged to belong to their respective owners.
H608 Installation Guide
TM
Before beginning calibration, establish normal load conditions. Then choose either A or B below.
A. To monitor under-current (belt loss, coupling shear, status)
1. Turn setpoint screw clockwise
until Status Open LED turns
on.
Setpoint
Status
OPEN
Status
CLOSED
2. Slowly turn the screw counter
clockwise until the Status
Closed LED turns on.
Setpoint
Status
OPEN
Status
CLOSED
3. Turn the screw an additional
¼ turn counter clockwise for
operational margin.
Setpoint ¼
B. To monitor over-current (mechanical problems, seized impeller)
1. Turn setpoint screw counter
clockwise until Status Closed
LED turns on.
Setpoint
Status
OPEN
Status
CLOSED
2. Slowly turn the setpoint screw
clockwise until the Status
Open LED just turns on.
Setpoint
Status
OPEN
Status
CLOSED
3. Turn the setpoint screw an
additional ¼ turn clockwise
for operational margin.
Setpoint ¼
Calibration
Troubleshooting Problem Solution
No Reading at Controller • Check sensor calibration (see above)
• Check for control voltage at sensor (<30V, <1A)
• Check for amperage in monitored conductor (> 0.5A)
• Assure that sensor core mating surfaces are clean and that the core clamp is completely closed
Setpoint screw has no stops The setpoint screw has a slip-clutch at both ends of its travel to avoid damage.Twenty turns CCW will
reset the sensor to be most sensitive. Repeat calibration above.
Both LEDs are lit Setpoint screw is too far clockwise. See solution above.

Other Veris Industries Switch manuals

Veris Industries Hawkeye H11D User manual

Veris Industries

Veris Industries Hawkeye H11D User manual

Veris Industries Hawkeye 908 User manual

Veris Industries

Veris Industries Hawkeye 908 User manual

Veris Industries Hawkeye H609 User manual

Veris Industries

Veris Industries Hawkeye H609 User manual

Veris Industries Hawkeye 949 User manual

Veris Industries

Veris Industries Hawkeye 949 User manual

Veris Industries Hawkeye 949 User manual

Veris Industries

Veris Industries Hawkeye 949 User manual

Veris Industries Hawkeye 738 User manual

Veris Industries

Veris Industries Hawkeye 738 User manual

Veris Industries Hawkeye 730 User manual

Veris Industries

Veris Industries Hawkeye 730 User manual

Veris Industries Hawkeye 939 User manual

Veris Industries

Veris Industries Hawkeye 939 User manual

Veris Industries Hawkeye 949 User manual

Veris Industries

Veris Industries Hawkeye 949 User manual

Veris Industries H909 User manual

Veris Industries

Veris Industries H909 User manual

Veris Industries Hawkeye H948 User manual

Veris Industries

Veris Industries Hawkeye H948 User manual

Veris Industries Hawkeye 948 User manual

Veris Industries

Veris Industries Hawkeye 948 User manual

Veris Industries Hawkeye H949 User manual

Veris Industries

Veris Industries Hawkeye H949 User manual

Veris Industries Hawkeye H940 User manual

Veris Industries

Veris Industries Hawkeye H940 User manual

Veris Industries Hawkeye 909 User manual

Veris Industries

Veris Industries Hawkeye 909 User manual

Veris Industries Hawkeye H906 User manual

Veris Industries

Veris Industries Hawkeye H906 User manual

Veris Industries Hawkeye H950 User manual

Veris Industries

Veris Industries Hawkeye H950 User manual

Veris Industries Hawkeye 949 User manual

Veris Industries

Veris Industries Hawkeye 949 User manual

Veris Industries Hawkeye 959 User manual

Veris Industries

Veris Industries Hawkeye 959 User manual

Veris Industries Hawkeye 735 User manual

Veris Industries

Veris Industries Hawkeye 735 User manual

Veris Industries H806 User manual

Veris Industries

Veris Industries H806 User manual

Veris Industries Hawkeye H808 User manual

Veris Industries

Veris Industries Hawkeye H808 User manual

Popular Switch manuals by other brands

Burg Wächter BWnet-10931 manual

Burg Wächter

Burg Wächter BWnet-10931 manual

Manhattan 151252 user manual

Manhattan

Manhattan 151252 user manual

Goobay 93893 user manual

Goobay

Goobay 93893 user manual

Atlantis Land AO2-F5P quick guide

Atlantis Land

Atlantis Land AO2-F5P quick guide

Allied Telesis TurboStack AT-TSA2 user manual

Allied Telesis

Allied Telesis TurboStack AT-TSA2 user manual

Belkin Network USB Hub manual

Belkin

Belkin Network USB Hub manual

Analog way NATIX NTX8022A user manual

Analog way

Analog way NATIX NTX8022A user manual

Comtrend Corporation GS-7620 Quick installation guide

Comtrend Corporation

Comtrend Corporation GS-7620 Quick installation guide

Daxten SCOUTCOMBO 16 - installation guide

Daxten

Daxten SCOUTCOMBO 16 - installation guide

Siemens SIRIUS 3SB12 Series operating instructions

Siemens

Siemens SIRIUS 3SB12 Series operating instructions

PABX TC-2000 A instruction manual

PABX

PABX TC-2000 A instruction manual

Elk Products ELK-M1DBHR installation manual

Elk Products

Elk Products ELK-M1DBHR installation manual

Lindy KVM Switch Classic user manual

Lindy

Lindy KVM Switch Classic user manual

Dell Networking S4048 installation guide

Dell

Dell Networking S4048 installation guide

Smart-M DPN-4P user manual

Smart-M

Smart-M DPN-4P user manual

Intel 470F - NetStructure Switch user guide

Intel

Intel 470F - NetStructure Switch user guide

Aeon Labs AEOR Series quick start guide

Aeon Labs

Aeon Labs AEOR Series quick start guide

StarTech.com HDVGADP2HD quick start guide

StarTech.com

StarTech.com HDVGADP2HD quick start guide

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.