The H609 is a current-sensitive switching device which monitors current (amperage)
in the conductor passing through it. A change in amperage in the monitored
conductor which crosses the switch (setpoint) threshold plus the hysteresis value will
cause the resistance of the status output to change state, similar to the action of a
mechanical switch. In this model, the setpoint is adjustable through the action of a
twenty (20) turn potentiometer (see the CALIBRATION section). The status output is
suitable for connection to building controllers, or other appropriate data acquisition
equipment operating at up to 120 volts. The H609 requires no external power supply
to generate its output.
operation
notes
troubleshooting
calibration
For load currents less than sensor minimum rating:
Wrap the monitored conductor through the center hole and around the sensor body
to produce multiple turns through the "window." This increases the current measured
by the transducer.
• Controller must be
programmed to account
for the extra turns. e.g., if
four turns pass through
the sensor (as shown) the
normal controller reading
must be divided by 4.
DANGER: 5A CTs CAN pREsENT hAzARDous volTAGEs.
INsTAll CTs IN ACCoRDANCE wITh mANufACTuRER's
INsTRuCTIoNs.
TERmINATE ThE CT sECoNDARy bEfoRE ApplyING CuRRENT.
H6800-5A CT
> 50A (H609 max.)
For load currents greater than sensor maximum rating:
Use a 5 Amp (H681x series) Current Transformer (CT) as shown.
Problem Solution
No Reading at Controller • Check sensor calibration (see above)
• Check for control voltage at sensor (<120V)
• Check for amperage in monitored conductor (> 1.25A)
• Assure that sensor core mating surfaces are clean and
that the core clamp is completely closed
Setpoint screw has no stops The setpoint screw has a slip-clutch at both ends of its
travel to avoid damage.Twenty turns CCW will reset
the sensor to be most sensitive. Repeat calibration
above.
Both LEDs are lit Setpoint screw is too far clockwise. See solution above.
Establish normal load conditions.
A. To monitor under-current (belt loss, coupling shear, status)
Turn setpoint screw clockwise until Status OPEN LED turns ON.
S-l-o-w-l-y turn the screw counter-clockwise until the Status CLOSED LED just turns ON.
Turn the screw an
additional ¼ turn
counter-clockwise for
operational margin.
B. To monitor over-current (mechanical problems, seized impeller)
3.Turn the setpoint
screw an additional
¼ turn clockwise for
operational margin.
1.Turn setpoint screw counter-clockwise
until Status CLOSED LED turns ON.
2.S-l-o-w-l-y turn the setpoint screw clockwise
until the Status OPEN LED just turns ON.
4FUQPJOU
4UBUVT
0QFO 4UBUVT
$MPTFE
3.
+
Find Setpoint
adjustment screw 1.
2.
4FUQPJOU
4UBUVT
0QFO 4UBUVT
$MPTFE
Find Setpoint
adjustment screw
+
240A
300A:5A
4A
VERIS INDUSTRIES
Portland, Oregon 97223
1-800-354-8556
Hawkeye
®
VERIS INDUSTRIES
Portland, Oregon 97223
1-800-354-8556
Hawkeye
®
< 1.25A (sensor min.) 4x
1.0A
$"65*0/
3*4,0'&26*1.&/5%"."(&
t %FSBUFUIFQSPEVDUTNBYJNVNDVSSFOUGPSUIFOVNCFSPGUVSOT
UISPVHIUIFTFOTJOHXJOEPXVTJOHUIFGPMMPXJOHGPSNVMB
3BUFE.BY"NQT/VNCFSPG5VSOT.BYNPOJUPSFE"NQT
FH"5VSOT"NQTNBYJONPOJUPSFEDPOEVDUPS
t 'BJMVSFUPGPMMPXUIFTFJOTUSVDUJPOTDBOSFTVMUJOPWFSIFBUJOH
BOEQFSNBOFOUFRVJQNFOUEBNBHF