Veris G Series User manual

Popular Controllers manuals by other brands

Sunricher SR-ZV9003T3-RGBW-US Installation

Sunricher

Sunricher SR-ZV9003T3-RGBW-US Installation

Ksenia intro Installation and configuration manual

Ksenia

Ksenia intro Installation and configuration manual

Inovance CAN200 Series manual

Inovance

Inovance CAN200 Series manual

Gauzy LC6 FLEX Controller Installation and operation guide

Gauzy

Gauzy LC6 FLEX Controller Installation and operation guide

Viking SLP-1 Technical practice

Viking

Viking SLP-1 Technical practice

CKD KBX-30E-U Series instruction manual

CKD

CKD KBX-30E-U Series instruction manual

Sharp Energy Sun Flux User manual & installation guide

Sharp Energy

Sharp Energy Sun Flux User manual & installation guide

Yamaha RCX40 user manual

Yamaha

Yamaha RCX40 user manual

AB Quality PowerFlex 400 Frames D-H Service bulletin

AB Quality

AB Quality PowerFlex 400 Frames D-H Service bulletin

Yamaha MJC8 owner's manual

Yamaha

Yamaha MJC8 owner's manual

AL-KO ATC operating instructions

AL-KO

AL-KO ATC operating instructions

Savant SmartControl 2 Deployment guide

Savant

Savant SmartControl 2 Deployment guide

GameSir T3S user manual

GameSir

GameSir T3S user manual

Kostal inveor operating manual

Kostal

Kostal inveor operating manual

Emerson Yarway 20-55 Operating and safety instructions

Emerson

Emerson Yarway 20-55 Operating and safety instructions

CoCo ACM-LV24 Quick installation guide

CoCo

CoCo ACM-LV24 Quick installation guide

Brooks SLA5810/20 Installation and operation manual

Brooks

Brooks SLA5810/20 Installation and operation manual

SIGMA TEK SR 011 Technical manual

SIGMA TEK

SIGMA TEK SR 011 Technical manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.

Installation Guide
Air Quality
Z202025-0R Page 1 of 3 ©2013 Veris Industries USA 800.354.8556 or +1.503.598.4564 / suppor[email protected] 12131
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.
Other companies’ trademarks are hereby acknowledged to belong to their respective owners.
TM
NOTICE
• This product is not intended for life or safety applications.
• Do not install this product in hazardous or classied locations.
• Read and understand the instructions before installing
this product.
• Turn off all power supplying equipment before working on it.
• The installer is responsible for conformance to all applicable codes.
No responsibility is assumed byVeris Industries for any consequences arising out of the
use of this material.
Product Identification
Product Overview
The G Series carbon monoxide detectors measure CO levels and signal control systems to provide an inlet of fresh
air optimal for the space at a given time. G Series devices are equipped with a relay contact that closes when
the CO level is below 25 ppm and opens when the CO level is above 25 ppm (when used with a normally closed
contactor). Removal of the sensor, interruption of power, or cut wires cause the relay circuit to open and start the
fan. Minimum relay cycle time is 3 minutes to prevent fan short-cycling.
Audible Alarm: An 85 dB alarm sounds if the CO level rises above 100 ppm for 30 minutes.
G Series
Carbon Monoxide Transmier
and Fan Controller
G
D = Duct mount
W = Wall mount
Enclosure Auxiliary Alarm OutputOutput
A = Auxiliary Contact
X = None
= StandardV = Field-selectable,
0-5/0-10VDC
M =4-20mA
R = Relay only
S
US or EU
Specifications
Input Power 15-30VDC/24VAC, 0.3A@24VAC
Sensor Type Digitally profiled metal oxide semiconductor (MOS)
Sensor Life 5-10 years typical, replaceable
Detection Range 0 to 200 ppm
Analog Output 3-wire sourcing, 4-20mA or user selectable 0-5V/0-10V (specify mA
or V)
Output Scaling User-selectable 100 ppm F.S. or 200 ppm F.S.
Response Time 2 min 30 sec sample interval cycle
Relay Output N.O. Form A (SPST) 8A@30VAC/ VDC; (Use with N.C. contactor)
Relay Setpoint 25 ppm
High Limit Setpoint 100 ppm for 30 minutes
High Limit Alarm Audible, 85 dB, resets below 100 ppm (solid-state contact for -AS
version)
High Limit Contact (-AS Models) 250VAC/DC, 120mA max. Ron 35 Ω
LED Indicators Solid Green = Normal; Solid Red = Call for ventilation;
Flashing Green = Sensor life has expired; Flashing Red = High-limit
alarm
Operating Temperature Range -20° to 50°C (-4° to 122°F)
Operating Humidity Range 0 to 90% RH non-condensing
Coverage 5000-7500 sq ft typical (465-697 sq m)
Housing White powder coat over steel
Z202025-0R Page 2 of 3 ©2013 Veris Industries USA 800.354.8556 or +1.503.598.4564 / suppor[email protected] 12131
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.
Other companies’ trademarks are hereby acknowledged to belong to their respective owners.
Installation Guide
Air Quality
GSeries TM
2.4"
(55 mm)
2.5"
(63 mm)
0.9" dia.
(22 mm)
4.5”
(114 mm) 4"
(102 mm)
5.0"
(127 mm)
2.25"
(57 mm)
Dimensions
1. Lock out all power supplies prior to installation.
2. Select a location for the sensor in a secure area where it will be accessible only to qualied service personnel. Install the G Series
sensor centrally in the parking structure, near the main trac paths, but away from outside air vents and excessive drafts.
Mount the unit securely to a wall or column at a height of about 5 ft. (1.52 m) from the oor.
3. Connect wiring as shown below. If using a voltage output model, use the output jumper to select 0-5 V or 0-10 V.
-+
-+
0-10V/0-5V
or
4-20mA
DDC
SYSTEM
V in
COMM
SENSOR
CONTACTOR
POWER
FAN
POWER
N.C.
CONTACTOR
ALARM
N.O.
OUT
SENSOR DETAIL
Common
Out 0-5V/10V or 4-20mA
IN V+ 15-30VDC, 24VAC
N.O. Relay
N.O. Relay
OUTPUT
10V 5V
PPM
100
200
4. Apply power to the unit. A green LED on the circuit board indicates proper operation of the power supply.
Coverage is not dependent on the sensor. Coverage is a function of the building structure and air ow patterns. Wide open areas where the air is well mixed may
require multiple sensors.
Installation
Z202025-0R Page 3 of 3 ©2013 Veris Industries USA 800.354.8556 or +1.503.598.4564 / suppor[email protected] 12131
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.
Other companies’ trademarks are hereby acknowledged to belong to their respective owners.
Installation Guide
Air Quality
GSeries TM
For any service or installation, consult qualied service personnel. To ensure continued reliable operation, replace the sensor
module every ve years with a Veris Industries CO sensor replacement module (Veris part number AA09).
Replacement instructions:
1. Disconnect power from the unit.
2. Carefully remove the old sensor module.
3. Install the new module rmly into the socket.
4. Reconnect power to the unit.
5. The replacement sensor requires 96 hours to stabilize after initial power application.
The sensor module is factory calibrated. No eld calibration is required or possible. Verify proper operation by observing the LED
indicators.
Problem Solution
4-20 mA output does not function • Verify that the unit is a 4-20 model.
• Verify that the unit is wired for sourcing output.
Output is half or twice what is
expected
• Verify span jumper is set to desired scale.
• For voltage units, verify jumper is set to desired
voltage output scale.
Output is inaccurate or unstable • Allow 96 hours for sensor to burn in and stabilize.
Service
Troubleshooting