VersaMax IC200EBI001-AC User manual

September 2001
GFK-1859B
IMPORTANT PRODUCT INFORMATION
READ THIS INFORMATION FIRST
Product: VersaMaxEthernet Network Interface Unit
IC200EBI001-AC with Firmware Release 1.20
Introduction
This document contains important information not available in any other publication; therefore, we strongly
advise you first read and then save this document. This document discusses firmware release 1.20, which
corrects the problems described in the sections “Problems Resolved in this Firmware Release (1.20)” and
“Important Operational Notes” below.
Important Operational Notes for Firmware Release 1.20
Number of Allowed Connections for Modbus Protocol Mode Reduced from 10 to 1
For the Modbus Protocol mode, the number of allowed connections has been reduced from ten to one. This is
required to facilitate the message timeout function, described below.
Addition of Message Loss Timeout Function for Loss of Communications Problems
In previous releases, if the Ethernet connection was broken or the application failed to communicate, outputs
held their last state values for a fixed time of 10 to 11 seconds, then reverted to their configured default state
values. For applications where this behavior is not acceptable, a new “message loss timeout” function has
been added to the ENIU.
Configuration of this function was facilitated by extending the use of the existing Update Timeout parameter,
found on the Consumed Exchange tab of the ENIU hardware configuration window. Starting with Release
1.2, the Update Timeout parameter has dual functionality. In EGD mode, its function has not changed. In
Modbus mode, it is now used to set a message loss timeout period. If the ENIU does not receive a valid read or
write message within that timeout period, the ENIU commands its controlled outputs to go to their configured
default state values.
During normal operation, each new read or write message resets the timer. So the Update Timeout parameter
must be set to a value 2 to 2.5 times greater than the message rate to ensure that a timeout does not occur
under normal operation. In the case where a timeout occurs due to a loss of communications, the ENIU waits
for a new Modbus connection to open and for receipt of a write message before bringing outputs out of their
default state.
Note that the Update Timeout parameter will be automatically set to 2 seconds if Autoconfiguration is used or
if a new default configuration is stored from the configuration software. Also note that if the Update Timeout
parameter is set to 0 (zero), the message loss timeout function is disabled, and the ENIU will hold its last state
for 10-11 seconds as in previous releases of the module. The range of time values allowed for the Update
Timeout parameter is 10 to 3,600,000 milliseconds. This timer operates at the Application layer.

2 Important Product Information
GFK-1859B
Problems Resolved in this Firmware Release (1.20)
Outputs Hold Last Values in Modbus Mode if Application Hangs up
The problem of outputs holding their last values if the controlling application hangs up, but the TCP/IP
connection remains alive, is corrected by using the “message loss timeout”function in this release (1.20),
described in the Important Operational Notes section above. However, this also requires that you use no more
than one connection in Modbus Mode and that you set an appropriate value in the Update Timeout parameter,
both of which are described above in the Special Operational Notes section.
Outputs Hold Last Values in Modbus Mode for 10-11 Seconds if Ethernet Connection is Lost
In ENIU releases prior to Release 1.2, Outputs hold their last values for 10-11 seconds if the Ethernet
connection is broken. This behavior can be changed by using the new “message loss timeout”function,
described above in the Important Operational Notes section.
ENIU Stopped Producing EGD Exchanges if Broadcast Exchange was 256 Bytes or Greater
This release (1.20) has fixed the problem in which, in EGD mode only, the ENIU stopped producing
exchanges when it received a broadcast exchange that had a length greater than 256 bytes.
Rejection of Invalid Network Parameters
Starting with Release 1.2, certain invalid network parameters, such as IP address of zero in the local subnet
are rejected by the ENIU.
Rejection of Configuration where Consumption IP Matches ENIU IP
Starting with Release 1.2, the ENIU will reject a configuration in which the Consumption IP address is the
same as the ENIU’s IP address. This applies to unicast, multicast, and broadcast conditions.
Product Identification
Module Catalog Number: IC200EBI001-AC
Firmware version: 1.20
Firmware upgrades: The Ethernet Network Interface Unit (ENIU) firmware resides in FLASH memory. This
firmware may be upgraded with future versions via a download from an appropriate personal
computer connected to the Ethernet connector (RJ-45) on the ENIU. The download uses an FTP
session to the ENIU.
To upgrade earlier versions of this product, which is required, order firmware upgrade kit
44A751424-G02 from your distributor, or obtain it on the Internet at
www.gefanuc.com/support/plc/r-versamax.htm under IC200EBI001-AC.

Important Product Information 3
GFK-1859B
Product Specifications
Ethernet IP address Any Valid IP Address
Default is 195.0.0.x, where x is selected on the rotary switches.
Ethernet network data rate 10Base-T or 100Base-TX, auto-negotiated
I/O data 1024 bytes maximum. Up to 512 bytes of inputs or 512 bytes of outputs.
Fault data 128 bytes maximum
Indicators (5) Power LED indicates presence of input power
OK LED indicates health of the ENIU
Faults LED indicates presence of faults
LAN LED indicates health of Ethernet network
Stat LED solid green indicates Modbus connection present or receipt of EGD exchanges;
flashing Amber indicates invalid IP address
Number of I/O modules Release 1.0 supports 8 I/O modules and no expansion racks
Release 1.1 (and later releases) supports 64 I/O modules and 7 expansion racks.
Power Consumption +5V@175mA, +3.3V@425mA
Protocols Modbus Ethernet, Class 0 & 1 (all releases)
Ethernet Global Data (Release 1.1 and later releases)
High density analog modules Supported in Release 1.1 and later releases (requires VersaPro 2.0 or later, Remote I/O
Manager 2.0 or later, or Logic Developer PLC 2.10 or later to configure)
Hot Insertion for I/O modules Supported in Release 1.1 and later releases
Firmware Update Order kit Number 44A751424-G02 to update to Release 1.20
Features Introduced in Previous Release 1.1
1. Ethernet Global Data (EGD). Supports one produced exchange and one consumed exchange. All
configured input data are in the produced exchange, and all configured output data are in the consumed
exchange. EGD must be configured explicitly and is not available when the ENIU is autoconfigured.
2. Expansion I/O. Up to seven expansion racks may be connected to one ENIU with a total of 64 modules
supported.
3. Hot Insertion. I/O modules may be inserted or removed with power applied to the rack.
4. High Density Analog Modules. These may be used in an ENIU rack. However, VersaPro 2.0 or later is
required to configure these modules.
General Operation Notes
Power Cycle Conditions.
For both discrete and analog Output or Mixed modules, if the ENIU loses power but the Output or Mixed
modules do not lose power, the Hold Last State parameter does not work as might be expected. Upon ENIU
power loss, outputs configured for Hold Last State go to the Last State value on modules that still have power.
When power is restored to the ENIU, outputs go to the Default value. When communications are reestablished
and the ENIU receives a Write message, outputs go to the values in the ENIU’s Output Table.
Restrictions and Open Problems
Verify or Clear Operations Fail Occasionally
On rare occasions, a verify or clear operation from the programmer will fail. Retry to correct.

4 Important Product Information
GFK-1859B
Product Overview
The Ethernet Network Interface Unit (ENIU) is an Ethernet slave module that acts as controller for a set of I/O
modules. Power for module operation is provided by a power supply that installs directly on the ENIU.
Ethernet NIU power supply
ENIU Physical Features
0
5
0
764
891
1
X1
NODE
X100
3
2
EBI001
LAN
STAT
PWR
FAULTS
OK
X10
I
C200EBI001- XX
5
0
764
893
2
1
5
76
4
893
2
10/100
BASET
IPADDR A.B.C.x
;;;
',15DLO /DWFK
3DQHO 0RXQWLQJ
+ROH
5- (WKHUQHW
3RUW 3RUW
&RQQHFWRU
5RWDU\ 6ZLWFKHV
/(' ,QGLFDWRU
/LJKWV
5RWDU\ 6ZLWFK
7UDQVSDUHQW 'RRU
3RZHU 6XSSO\
/RFNLQ
J
+ROH
&DUULHU &RQQHFWRU
RQ 6LGH RI (1,8
([SDQVLRQ
&RQQHFWRU
RQ 6LGH RI (1,8
0$& [[[[[[[[[[[[
(1,8 6HULDO 1XPEHU
0$& $GGUHVV
3RZHU 6XSSO\
&RQQHFWRU
Preinstallation Check
Carefully inspect all shipping containers for damage. If any equipment is damaged, notify the delivery service
immediately. Save the damaged shipping container for inspection by the delivery service. After unpacking the
equipment, record all serial numbers. Save the shipping containers and packing material in case it is necessary
to transport or ship any part of the system.
Quick Start Guide
1. Install the ENIU on the DIN-rail by simply clicking it into place.

Important Product Information 5
GFK-1859B
Note: The ENIU and connecting carriers must be installed on the same section
of 35mm x 7.5mm DIN-rail.
The DIN-rail must have a conductive (unpainted) finish for proper grounding.
(Refer to the heading Module Installation for information about space requirements or module
orientation, or if you are installing the ENIU in an area of excessive vibration).
2. Install the Power Supply on the ENIU.
The latch on the power supply must be in the unlocked position.
Align the connectors and the latch post and press the power supply module down
until the two tabs on the bottom of the power supply click into place.
Turn the latch to the locked position to secure the power supply to the top of the
ENIU.
Complete the power supply wiring as described in the installation instructions provided with the Power
Supply.
3. Set the IP Address - Adjust the rotary switches on the front of the ENIU using a 2.44mm (3/32in) flat
screwdriver. These switches, marked IP Address A.B.C.x / X100, X10 and X1, select the hundreds, tens,
and ones digits of the last field in the Ethernet IP address. The first three fields in the IP address, A.B.C.,
are fixed to 195.0.0. when the unit is shipped from the factory. For the last field, select any valid address
in the range 1-254. Always cycle power to the ENIU after changing the switch settings.
0
0
0
7
6
4
5
8
9
1
1
X
1
I
P ADDRESS A.B.C.x
X
100
3
2
X
10
7
6
4
5
8
9
1
3
2
2
3
4
5
6
7
8
9
4. Alternate Method to set Temporary IP Address using Telnet
NOTE: This step is an alternate to Step 3 above. Be aware that the address set with this method is
temporary. It will be lost if power is cycled.
a. The ENIU and the personal computer must be operational and interconnected via an Ethernet connection.
At the computer’s DOS command prompt, type in the following, then press the Enter key:
arp –s (IP address you want to assign to ENIU) (MAC address of the ENIU) (IP address of your
computer)

6 Important Product Information
GFK-1859B
FOR EXAMPLE: arp –s 3.16.27.5 08-00-19-01-48-64 3.16.88.139
NOTE: You will not see any reply on the screen.
b. To verify that the ARP table entry was accepted, type the following at the command prompt, then press
the Enter key:
arp –a
An entry matching the desired ENIU IP address (“Internet Address”) and MAC address (“Physical
Address”) should be seen in the ARP table, with the “Type”listed as 'static.' ARP TABLE ENTRY
EXAMPLE:
Internet
Address Physical Address Type
3.16.27.5 08-00-19-01-48-64 static
c. Next, create a Telnet connection to the ENIU (Port 1) by typing in the following command at the
computer’s MS-DOS prompt, then pressing the Enter key:
telnet (IP Address) 1
FOR EXAMPLE: telnet 3.16.27.5 1
A Telnet window will appear. After several seconds, a “Connect Failed!”dialog box will appear;
regardless, the ENIU will change its IP address to the one designated in the Telnet command. (NOTE: If
it takes more than 15 seconds for the Connect Failed box to appear, the Telnet command probably didn’t
work.)
NOTE: Step 4 sets a temporary IP address that will be lost if power is cycled. To set a permanent (non-
volatile) address, use VersaPro 1.5 (or later) or Remote I/O Manager 1.5 (or later) software and “store”a
configuration containing the correct IP address. NOTE: A device will need to be configured in the
VersaPro communications setup for the temporary IP address to allow you to perform the configuration
store.
5. Connect the communications bus to the connector on the front of the ENIU. (Refer to the heading Bus
Installation Guidelines for detailed bus installation instructions.)
6. Remove the connector cover on the right-hand side of the ENIU. Do not discard this cover; you will
need to install it on the last carrier. It protects the connector pins from damage and ESD during handling
and use. Do not remove the connector cover on the left-hand side.
7. Install additional modules. Mount a module on its carrier and slide it to the left along the DIN-rail to
fully engage the connector on the adjacent carrier or ENIU. Repeat for other modules, and install the
connector cover (see Step 6) on the last carrier.
DIN-Rail
ENIU
M
odule/Carrier
M
odule/Carrier

Important Product Information 7
GFK-1859B
8. Configuration. A configuration can be stored by VersaPro or Remote I/O Manager software, or the
ENIU can be autoconfigured. When power is applied to the ENIU for the very first time, the ENIU will
autoconfigure the modules physically present in the I/O station, starting at Slot 1. Autoconfiguration stops
at the first empty slot or faulted module. If the autoconfiguration is unsuccessful or a new
autoconfiguration is required, it is necessary to first clear the existing configuration from the ENIU. This
is done by powering down the ENIU, disconnecting the ENIU from the first I/O carrier, and powering up
the ENIU.
Note: If the I/O station includes any additional power supplies, those power supplies must be turned on either
before the ENIU Power Supply or at the same time to assure accurate autoconfiguration.
9. Observe the Module LEDs. The LEDs indicate the presence of power and show the operating mode and
status of the ENIU. The following section discusses LED operation.
LED Operation
LAN
STAT
PWR
FAULTS
OK
PWR Green indicates power is applied to the ENIU.
OK Green indicates the ENIU firmware is operational.
FAULTS Amber indicates the ENIU has detected a fault with itself or an I/O module. Blinking amber
indicates a Fatal Fault with the ENIU
LAN Green (solid or blinking) indicates network packets are being received or transmitted.
Indicates received data addressed to ENIU as well as broadcast data.
STAT Modbus Mode. Solid Green indicates a Modbus connection. Amber blinking at 1/sec rate
indicates an IP address problem.
EGD Mode. Solid Green indicates exchanges are being received. Amber blinking at 1/sec
rate indicates an IP address problem.
NOTE: Refer to Chapter 6 of the User’s Manual for details on using the LEDs for troubleshooting.
Module Installation
133.35mm
(5.25in)
1
2
3
85.85mm
(3.38in)
Modules must be mounted on a horizontal DIN-rail.
•Allow sufficient finger clearance for opening ENIU door.
•Allow adequate clearance for Ethernet cable.
•Allow adequate space for power wiring.
The ENIU, with power supply attached, fits into a 70mm (minimum) deep
enclosure.
Rated thermal specifications are based on a clearance of 5.1cm (2in) above and
below the equipment and 2.54cm (1in) to the left of the ENIU module.
Panel-Mounting
For best stability, the DIN-rail should be installed on a panel using screws spaced approximately 5.24cm (6in)
apart.
If excessive vibration is a factor the ENIU should also be screwed down to the mounting panel.

8 Important Product Information
GFK-1859B
•Tolerances are +/- 0.13mm (0.005in) non-cumulative.
•1.1-1.4Nm (10-12 in/lbs) of torque should be applied to M3.5 (#6-32) steel screw threaded into
material containing internal threads and having a minimum thickness of 2.4mm (0.093in).
S
EE NOTE 2.
M
3.5 (#6) SCREW
1
5.9mm
0
.62in REF
S
PLIT LOCK
W
ASHER
F
LAT WASHER
N
IU
TAPPED HOLE
IN PANEL
5.1mm
0.200in
4
.3mm
0
.170in
4
.3mm
0
.170in
Removing the ENIU from the DIN-rail
1. Turn off power to the power supply.
2. Remove the power supply module. If the ENIU is attached to the panel with a screw, remove the panel-
mount screw.
3. Slide the ENIU to the left, until the connector on the ENIU’s right side disengages from the next carrier.
4. Use a small flathead screwdriver to pull the DIN-rail latch downward to release it, then pull the bottom of the
ENIU forward until it is free of the rail; finally, lift the ENIU off the top rail.

Important Product Information 9
GFK-1859B
Bus Installation Guidelines
The proper cable for an Ethernet 10Base-T/100Base-TX network is a four twisted-pair, Category 5 Ethernet
cable. The following table summarizes key characteristics of the Ethernet network and cable.
Network
Topology Point-to point Ethernet 10Base-T/100Base-TX connections with no termination. “Points”
can be hubs or switches. If only 2 nodes are present, a crossover cable should be used
to connect them.
Point-to point
distance Maximum of 100 meters.
Medium Four twisted-pair unshielded cable. Shielding is permissible, but not required.
Transmission
Speed 10 Mbit/s (10Base-T) or 100 Mbit/s (100Base-TX)
Connector RJ-45
Cable Type Category 5 (“Cat 5”)
Termination No termination required
Bus Connector
RJ-45 Connector Pin Assignment
Pin Signal I/O Description
1 Tx+ O +Transmit output
2 Tx- O - Transmit output
3 Rx+ I + Receive input
4 FGND - Frame Ground
5 FGND - Frame Ground
6 Rx- I - Receive Input
7 FGND - Frame Ground
8 FGND - Frame Ground
P
in 1
ENIU Connector Front View
Ethernet MAC Address
The MAC physical address for the ENIU is labeled on the ENIU module.
Table of contents
Other VersaMax Network Hardware manuals