Vertiv NetSure 7200 Series User manual

Return Bus Load Shunt Monitoring Cable
Assembly Kit
Installation Manual
Kit Specification Number: 559404
For Use in Spec. No. 582127200 Power Systems

Vertiv™ Return Bus Load Shunt Monitoring Cable Assembly Kit Installation Manual
Vertiv™ Return Bus Load Shunt Monitoring Cable Assembly Kit Installation Manual
The information contained in this document is subject to change without
notice and may not be suitable for all applications. While every precaution has
been taken to ensure the accuracy and completeness of this document, Vertiv
assumes no responsibility and disclaims all liability for damages resulting from
use of this information or for any errors or omissions. Refer to other local
practices or building codes as applicable for the correct methods, tools, and
materials to be used in performing procedures not specifically described in
this document.
The products covered by this instruction manual are manufactured and/or
sold by Vertiv. This document is the property of Vertiv and contains
confidential and proprietary information owned by Vertiv. Any copying, use or
disclosure of it without the written permission of Vertiv is strictly prohibited.
Names of companies and products are trademarks or registered trademarks of
the respective companies. Any questions regarding usage of trademark
names should be directed to the original manufacturer.
Technical Support Site
If you encounter any installation or operational issues with your product, check the pertinent section of this
manual to see if the issue can be resolved by following outlined procedures.
Visit https://www.vertiv.com/en-us/support/ for additional assistance.

Vertiv™ Return Bus Load Shunt Monitoring Cable Assembly Kit Installation Manual
Proprietary and Confidential © 2022 Vertiv Group Corp.
iii
TABLE OF CONTENTS
Admonishments Used in this Document......................................................................................................................... iv
Important Safety Instructions ............................................................................................................................................. v
Safety Admonishments Definitions..........................................................................................................................................................................................................................v
Safety and Regulatory Statements...........................................................................................................................................................................................................................v
Déclarations de Sécurité et de Réglementation...........................................................................................................................................................................................v
1Vertiv™ Return Bus Load Shunt Monitoring Cable Assembly Kit ...................................................................... 1
1.1 Kit Description..................................................................................................................................................................................................................................................................1
1.2 Kit Contents ........................................................................................................................................................................................................................................................................1
1.3 Tools and Material Required...............................................................................................................................................................................................................................1
1.4 Installation Procedure................................................................................................................................................................................................................................................1
2SM-DU External Shunt Connections........................................................................................................................... 4

Vertiv™ Return Bus Load Shunt Monitoring Cable Assembly Kit Installation Manual
Proprietary and Confidential © 2022 Vertiv Group Corp.
iv
Admonishments Used in this Document
DANGER
! Warns of a hazard the reader
will
be exposed to that will
likely
result
in death or serious injury if not avoided. (ANSI, OSHA)
WARNING
! Warns of a potential hazard the reader
may
be exposed to that
could
result in
death or serious injury if not avoided. This admonition is not used for situations that pose a
risk o
nly to equipment, software, data, or service. (ANSI)
CAUTION
! Warns of a potential hazard the reader
may
be exposed to that
could
result in minor or moderate injury if not avoided. (ANSI, OSHA) This admonition is not
used for situations that pose a risk only to equipment, data, or service, even if such use
appears to be permitted in some of the applicable standards. (OSHA)
ALERT
! Alerts the reader to an action that
must be avoided
in order to protect
equipment, software, data, or service. (ISO)
ALERT
! Alerts the reader to an action that
must be performed
in order to prevent
equipment damage, software corruption, data lo
ss, or service interruption. (ISO)
FIRE SAFETY
! Informs the reader of fire safety information, reminders, precautions,
or policies, or of the locations of fire
-fighting and fire-safety equipment. (ISO)
SAFETY
! Informs the reader of general safety information, reminders, precautions, or
policies not related to a particular source of hazard or to fire safety. (ISO, ANSI, OSHA)

Vertiv™ Return Bus Load Shunt Monitoring Cable Assembly Kit Installation Manual
Proprietary and Confidential © 2022 Vertiv Group Corp.
v
Important Safety Instructions
Safety Admonishments Definitions
Definitions of the safety admonishments used in this document are listed under “Admonishments Used in this Document” on page iv.
Safety and Regulatory Statements
Refer to Section 4154 (provided with your customer documentation) for Safety and Regulatory Statements.
Déclarations de Sécurité et de Réglementation
Reportez-vous à la Section 4154 (fourni avec les documents de votre client) pour les déclarations de sécurité et de réglementation.

Vertiv™ Return Bus Load Shunt Monitoring Cable Assembly Kit Installation Manual
Proprietary and Confidential © 2022 Vertiv Group Corp.
vi
This page intentionally left blank.

Vertiv™ Return Bus Load Shunt Monitoring Cable Assembly Kit Installation Manual
Proprietary and Confidential © 2022 Vertiv Group Corp.
1
1Vertiv™ Return Bus Load Shunt Monitoring Cable Assembly
Kit
1.1 Kit Description
These instructions provide a step-by-step procedure to field install this kit into Power System Spec. No. 582127200. Installation of this
kit in other equipment should not be attempted.
This kit provides a wire harness to reverse the shunt reference voltage to the SM-DU Shunt Monitoring Module located in the primary
power bay. The SM-DU module mounted in the primary power bay contains connections for the internal load shunts provided in each
power bay (the system can consist of up to three power bays). The SM DU module also provides two (2) additional external shunt
monitoring inputs. When used as shipped, any external shunt needs to be installed in the hot (-48V) bus. Use this kit to connect up
to five (5) external shunts located in the return bus. This requires all internal shunts connected to the SM-DU module to be
disconnected and the associated shunt leads isolated.
1.2 Kit Contents
Table 1.1 lists the items furnished with this kit. Before starting the procedure, check the items furnished against those listed to ensure
that there are no shortages.
Table 1.1 Kit Contents
Qty. Description P/N
1 Reverse Shunt Reference
Voltage Wire Harness Pigtail 559353
1 These Instructions IM559404
1.3 Tools and Material Required
Table 1.2 lists the items required to install this kit.
Table 1.2 Tools and Material Required
Description
Small Straight-Blade Screwdriver to Disconnect and Connect Shunt Leads.
Material to Tie-Back and Insulate Existing Shunt Leads.
1.4 Installation Procedure
THESE INSTRUCTIONS SHOULD BE READ THROUGH COMPLETELY BEFORE INSTALLING THE KIT.
The following is a step-by-step procedure to install the kit. The procedure has been written for ease of use and to minimize the
possibility of contact with potentially hazardous energy. This procedure should be performed in the sequence given, and each step
should be completely read and fully understood before performing that step. Observe all “Important Safety Instructions” presented at
the beginning of this document as this procedure is being performed. As each step of the procedure is completed, the box adjacent
to the respective step should be checked. This will minimize the possibility of inadvertently skipping any steps. If the step is not
required to be performed for your site, also check the box to indicate that it was read.

Vertiv™ Return Bus Load Shunt Monitoring Cable Assembly Kit Installation Manual
Proprietary and Confidential © 2022 Vertiv Group Corp.
2
NOTE!
When performing any step in this procedure which requires removal of existing hardware, retain all hardware for use
in subsequent steps, unless otherwise stated.
1.4.1 Procedure
DANGER! Observe the Important Safety Instructions located at the beginning of this document.
NOTE!
Refer to Figure 1.1 as this procedure is performed.
[ ] 1. Locate the J2 connector on the shunt input terminal block board. See Figure 1.1.
[ ] 2. Remove the J2 connector from the shunt input terminal block board.
[ ] 3. Insert J2 into P2 of the kit supplied wire harness pigtail assembly (P/N 559353).
[ ] 4. Insert the opposite end of the kit supplied wire harness pigtail assembly (P/N 559353) into the shunt input terminal
block board where J2 was removed in step 2.
[ ] 5. Remove all existing shunt leads from the SM-DU module. Insulate and tie back these leads.
[ ] 6. Refer to the next section to connect external shunts.

Vertiv™ Return Bus Load Shunt Monitoring Cable Assembly Kit Installation Manual
Proprietary and Confidential © 2022 Vertiv Group Corp.
3
Figure 1.1 Installing the Kit
SM-DU
J2
P2
Front
Primary Power Bay
Primary Power Bay
SM-DU Shunt Input
Terminal Block Board
Components removed in
illustration for clarity only.
P/N 559353 Wire Harness
Provided in Kit P/N 559404
Disconnect
this connector.
and
Place kit supplied wire
harness pigtail between
the two connectors
just separated.

Vertiv™ Return Bus Load Shunt Monitoring Cable Assembly Kit Installation Manual
Proprietary and Confidential © 2022 Vertiv Group Corp.
4
2SM-DU External Shunt Connections
You just installed wire harness pigtail P/N 559353 that was included in kit P/N 559404. This allows you to connect external shunts
which are located in the return bus to the SM-DU module. The SM-DU module provides five (5) shunt monitoring inputs. Refer to the
following procedure and Figure 2.1 for connections details.
2.1.1 Procedure
DANGER! Observe all “Important Safety Instructions” presented at the beginning of this document.
NOTE!
Refer to Figure 2.1 as this procedure is performed.
[ ] 1. Connect up to five (5) external shunts to the SM-DU module. Observe proper polarity. See Figure 2.1.
NOTE!
With kit P/N 559404 installed, all shunts connected to the SM-DU module must be located in the return bus.
Connect the plus side of the shunt to the positive shunt input on the SM-DU. Connect the negative side of the shunt to the
negative shunt input on the SM-DU.
[ ] 2. Refer to the ACU+ Instructions (UM1M820BNA) and program the SM-DU module’s shunt inputs.

Vertiv™ Return Bus Load Shunt Monitoring Cable Assembly Kit Installation Manual
Proprietary and Confidential © 2022 Vertiv Group Corp.
5
Figure 2.1 External Shunt Connections to the SM-DU Module
TB3
TB3
+ - + - + - + - + -
SM-DU Shunt Input
Terminal Block
TB3
Wire Size Capacity:
22-12 AWG.
Torque: 6 in-lbs.
Shunt 5 Shunt 1 Shunt 2 Shunt 3 Shunt 4
Components removed in
illustration for clarity only.
Front
Primary Power Bay
Primary Power Bay Disconnect and insulate all factory installed shunt leads.
Connect external shunt leads.
WHEN USING KITP/N 559404,
ALLSHUNTS CONNECTED TOTHE SM-DU
MUSTBE LOCATED IN THE RETURN BUS.

Vertiv™ Return Bus Load Shunt Monitoring Cable Assembly Kit Installation Manual
Proprietary and Confidential © 2022 Vertiv Group Corp.
6
This page intentionally left blank.

Vertiv™ Return Bus Load Shunt Monitoring Cable Assembly Kit Installation Manual
Proprietary and Confidential © 2022 Vertiv Group Corp.
Connect with Vertiv on Social Media
https://www.facebook.com/vertivI
https://www.instagram.com/vertiv/
https://www.linkedin.com/company/vertiv/
https://www.twitter.com/vertiv/

Vertiv.com | Vertiv Headquarters, 1050 Dearborn Drive, Columbus, OH, 43085, USA
© 2022 Vertiv Group Corp. All rights reserved. Vertiv™ and the Vertiv logo are trademarks or registered trademarks of Vertiv Group
Corp. All other names and logos referred to are trade names, trademarks or registered trademarks of their respective owners. While
every precaution has been taken to ensure accuracy and completeness here, Vertiv Group Corp. assumes no responsibility, and
disclaims all liability, for damages resulting from use of this information or for any errors or omissions. Specifications, rebates and
other promotional offers are subject to change at Vertiv’s sole discretion upon notice.
IM559404_REVD
Proprietary and Confidential © 2022 Vertiv Group Corp.