Viconics VT7600A User manual

1 | PIR Ready VT76x7 Series-Installation Guide
CONTENTS
Installation 2
Location 2
Installation 2
Theory of operation 3
Features overview 4
Model Chart 5
Network ready 6
Terminal, Identification and Function 6
Wiring 6
Screw terminal arrangement 7
Typical applications 8
Remote humidity sensor accessories 9
Configuring and Status Display Instructions 10
Status display 10
User Interface 12
User configuring instructions menu 12
Local keypad interface 13
Occupied setpoints adjustments 14
Dehumidification process 16
Installer Configuration Parameter Menu 21
Troubleshooting guide 32
Humidity Control 34
Humidity reset 34
High limit humidity sensor 34
Specifications 35
Drawing & Dimensions 36
PIR Ready VT76x7 Series
With & Without Local Schedule &
With Humidification & Dehumidification
Strategy Terminal Equipment Controllers
Installation Guide
For Commercial HVAC Applications
May 3rd, 2012 / 028-0229-R4
April 26, 2011 / 028-0190-R6
May 5, 2011 / 028-0228-R3

2 | PIR Ready VT76x7 Series-Installation Guide
INSTALLATION
Remove the security screw on the bottom of
Terminal Equipment Controller cover.
Open unit by pulling on the bottom
side of Terminal Equipment
Controller (fig. 1).
Remove wiring terminals from sticker.
Please read the FCC ID and IC label
installed in the cover upon removal of
cover for the wireless products.
Location
1. Should not be installed on an outside
wall.
2. Must be installed away from any
direct heat source.
3. Should not be installed near an air
discharge grill.
4. Should not be affected by direct
sun radiation.
5. Nothing should restrict vertical air
circulation to the Terminal
Equipment Controller.
Installation
1. Swing open the Terminal
Equipment Controller PCB to the
left by pressing the PCB locking
tabs (fig. 2).
2. Pull out cables 6” out from the
wall.
3. Wall surface must be flat and
clean.
4. Insert cable in the central hole of
the base.
5. Align the base and mark the
location of the two mounting
holes on the wall. Install proper
side of base up.
6. Install anchors in the wall.
7. Insert screws in mounting holes
on each side of the base (fig. 2).
8. Gently swing back the circuit
board on the base and push on it
until the tabs lock it.
9. Strip each wire 1/4 inch from end.
10. Insert each wire according to
wiring diagram.

3 | PIR Ready VT76x7 Series-Installation Guide
11. Gently push excess wiring back into hole (fig. 3).
12. Re-Install wiring terminals in their correct locations (fig. 3).
13. Re-install the cover (top side first) and gently push extra wire length back into
the hole in the wall.
14. Install security screw.
THEORY OF OPERATION
The VT7600 uses a Viconics proprietary adaptive logic algorithm to control the space
temperature. This algorithm controls the heating / air conditioning system to minimize
overshoot while still providing comfort. It provides exceptional accuracy due to its unique
PI time proportioning control algorithm, which virtually eliminates temperature offset
associated with traditional, differential-based on/off Terminal Equipment Controllers.
Fig.2 - On/Off mechanical control vs. PI electronic control.
If replacing an existing Terminal Equipment Controller, label the wires
before removal of the Terminal Equipment Controller.
Electronic controls are static sensitive devices. Discharge yourself
properly before manipulating and installing the Terminal Equipment
Controller.
A short circuit or wrong wiring may permanently damage the Terminal
Equipment Controller or the equipment.
All VT7000 series Terminal Equipment Controllers are designed for use
as operating controls only and are not safety devices. These instruments
have undergone rigorous tests and verification prior to shipping to ensure
proper and reliable operation in the field. Whenever a control failure
could lead to personal injury and/or loss of property, it becomes the
responsibility of the user / installer / electrical system designer to
incorporate safety devices (such as relays, flow switch, thermal
protections, etc…) and/or an alarm system to protect the entire system
against such catastrophic failures. Tampering with the devices or
unintended application of the devices will result in a void of warranty.

4 | PIR Ready VT76x7 Series-Installation Guide
Features overview
7 day schedule models, 2 or 4 events
Gas/oil or electric system compatibility for all type of applications
Internal RH sensor and remote RH input with humidification and dehumidification
sequence of operation embedded
Remote outdoor sensing capability for added flexibility
- System mode lock out
- Humidity setpoint reset
High limit input to prevent over-humidification
Lockable keypads for tamper proofing. No need for Terminal Equipment Controller
guards
Automatic frost protection to prevents costly freeze damage
Anti short cycle and minimum on/off run time protection. Reduces wear and maximizes
life span of mechanical equipment.
Configurable digital input for added flexibility. The input can be configured as the
following:
None: No function will be associated with the input
Service: a backlit flashing Service alarm will be displayed on the Terminal
Equipment Controller LCD screen when the input is energized. It can be tied in
to the AC unit control card, which provides an alarm in case of malfunction.
Filter: a backlit flashing Filter alarm will be displayed on the Terminal
Equipment Controller LCD screen when the input is energized. It can be tied to a
differential pressure switch that monitor filters
Rem NSB: remote NSB timer clock input. Will disable the internal scheduling of
the Terminal Equipment Controller. The scheduling will now be set as per the
digital input. The menu part related to scheduling is disabled and no longer
accessible. It provides low cost setback operation via occupancy sensor or from
a dry contact
RemOVR: temporary occupancy contact. Disables all override menu function of
the Terminal Equipment Controller. . The override function is now controlled by a
manual remote momentarily closed contact. When configured in this mode, the
input operates in a toggle mode.
With this function enabled it is now possible to toggle between unoccupied &
occupied setpoints for the amount of time set by parameter (TOccTime)
temporary occupancy time.
Fan lock: used in conjunction with a local air flow sensor connected to the input.
Locks out the Terminal Equipment Controller heating and cooling action and
displays a local alarm if no air flow is detected 10 seconds after the fan (G
terminal) is energized.
Configurable smart fan operation saves energy during night mode
Non volatile EEPROM memory prevents loss of parameters during power shortage
Built in default profile set-up for easier start up and commissioning
Configurable SPST output relay on scheduling models for lighting, exhaust fan or
fresh air control
6 hour typical reserve time for clock in case of power loss
Built in proportional humidity Terminal Equipment Controller
Proportional humidity high limit when used with the analog input for supply humidity
Automatic humidity setpoint reset when outside air temperature value is used.

5 | PIR Ready VT76x7 Series-Installation Guide
MODEL CHART

6 | PIR Ready VT76x7 Series-Installation Guide
Network ready
All Viconics VT76x7 series Terminal Equipment Controllers are designed for
stand-alone (Network Ready) operation.
They can be fully integrated into your choice of automation systems using the
available communication adapter options.
If required, stand-alone (Network Ready) Terminal Equipment Controllers can be
field retrofitted with the following communication adapters:
oVCM7607V5000B, Terminal Equipment Controller BACnet™ MS-TP®
communication adapter
oVCM7607V5000E, Terminal Equipment Controller Echelon™
LonTalk® communication adapter
oVCM7000V5000W Terminal Equipment Controller wireless Zigbee™
communication adapter
TERMINAL,IDENTIFICATION AND FUNCTION
Wiring
Part Number
VT7657B5x00(X)
VT7607B5x00(X)
Schedule
Yes
No
Top left terminal block
Y2
X
X
Y1
X
X
G
X
X
RC
X
X
C
X
X
Top right terminal block
RH
X
X
W1
X
X
W2
X
X
Bottom terminal block
HUM
X
X
AUX
X
X
DEHUM
X
X
DI
X
X
HS
X
X
SCOM
X
X
OS
X
X
HL
X
X

7 | PIR Ready VT76x7 Series-Installation Guide
Screw terminal arrangement
Wiring notes:
Note 1: If the same power source is used for the heating stages, install jumper across RC &
RH. Maximum current is 2.0 amps.
Note 2: If auxiliary output is used to toggle occupancy of the electronic control card inside
the equipment, configure the relay parameter (Aux cont ) to the N.O. setting. A
second relay can be added for additional functionality of the occupancy output.
Note 3: Humidifier output uses a half bridge rectifier. Reference of the control signal is the
common of the power supply of the Terminal Equipment Controller. (Terminal C)
Note 4: Electromechanical contacts are to be used with the digital inputs. Electronic triacs
cannot be used as mean of switching for the input. The switched leg to the input for
the input to activate is terminal C (common)
Note 5: The transformer of the unit provides power to the t Terminal Equipment Controller
and the additional loads that will be wired to the Terminal Equipment Controller.
HM
AU
DH
DI
HS
Scom
OS
HL
Y2
Y1
G
RC
C
RH
W1
5 pole left top connector
3 pole left top connector
8 pole bottom connector
W2

8 | PIR Ready VT76x7 Series-Installation Guide
TYPICAL APPLICATIONS

9 | PIR Ready VT76x7 Series-Installation Guide
Remote humidity sensor accessories
Model no.
Description
VH2020W1000
Wall mounted humidity sensor
VH2020D10000
Duct mounted humidity sensor
VH2020W1000, remote wall mounted room humidity
sensor.
This sensor can be used for:
Remote return or room air humidity sensing
with the sensor mounted on the wall.
VH2020W1000
VH2020D1000, remote duct mounted humidity
sensor c/w junction box.
This sensor can be used for:
Remote return air humidity sensing with the sensor
mounted on the return air duct.
Supply air humidity sensor used as high limit
protection
VH2020W1000
Wiring example of remote room
humidity sensor:
Wiring example of duct humidity
sensor:

10 | PIR Ready VT76x7 Series-Installation Guide
User menu flow chart:
NOTE: Prompts may not all be present depending on model selected
S c h e d u l e
s e t ? Y/ N
S y s mo d e
s e t ? Y/ N Cl o c k
s e t ? Y/ N
T e mpe r a t
s e t ? Y/ N Sc h e d u l e
h o l d Y/ N Ex i t ?
Y/ N
Un o c c HT
s e t ? Y/ N ° F/ ° C
s e t ? Y/ N
He a t i ng
s e t ? Y/ N Un o c c CL
s e t ? Y/ N
Co o l i n g
s e t ? Y/ N
°C
°F
Temperature Temperature Temperature Temperature
MENU
1 2 / 2 4 h r s
s e t ? Y/ N
12 / 24
T i me
s e t ? Y/ N
Time
Da y
s e t ? Y/ N
Day
F a n mo d e
s e t ? Y/ N
On
Smart
Auto
S u n d a y
s e t ? Y/ N Sa t u r d a y
s e t ? Y/ N F r i d a y
s e t ? Y/ N T h u r s d a y
s e t ? Y/ N We d n e s d a
s e t ? Y/ N T u e s d a y
s e t ? Y/ N Mo n d a y
s e t ? Y/ N
Ex i t ?
Y/ N
Oc c u pi e d
d a y ? Y/ N
Oc c u pi e d
1 2 : 0 0 p m
Time
Un o c c u p
1 2 : 0 0 p m
Time
Oc c u pi e d
d a y ? Y/ N
Oc c u pi e d
1 2 : 0 0 p m
Time
Un o c c u p
1 2 : 0 0 p m
Time
Oc c u pi e d
d a y ? Y/ N
Oc c u pi e d
1 2 : 0 0 p m
Time
Un o c c u p
1 2 : 0 0 p m
Time
Oc c u pi e d
d a y ? Y/ N
Oc c u pi e d
1 2 : 0 0 p m
Time
Un o c c u p
1 2 : 0 0 p m
Time
Oc c u pi e d
d a y ? Y/ N
Oc c u pi e d
1 2 : 0 0 p m
Time
Un o c c u p
1 2 : 0 0 p m
Time
Oc c u pi e d
d a y ? Y/ N
Oc c u pi e d
1 2 : 0 0 p m
Time
Un o c c u p
1 2 : 0 0 p m
Time
Oc c u pi e d
d a y ? Y/ N
Oc c u pi e d
1 2 : 0 0 p m
Time
Un o c c u p
1 2 : 0 0 p m
Time
Resume
Occ Hold
Uno Hold
Ex i t ?
Y/ N
Off
Heat
Cool
Auto
Ov e r r i d e
s c h d Y/ N
Re s u me
s c h d Y/ N
If status is:
Unoccupied
If status is:
Temporary Occupied Time,
Occupied hold or
Unoccupied hold
Hu mi d i f i
s e t ? Y/ N
De h u mi d i
s e t ? Y/ N
RH% RH%
Hu mi d i t y
s e t ? Y/ N
Ex i t ?
Y/ N
Ex i t ?
Y/ N
On stand-alone
models only
CONFIGURING AND STATUS DISPLAY INSTRUCTIONS
Status display
The Terminal Equipment Controller features a two-line, eight-character display. There is a
low level backlight level that is always active and can only be seen at night.
When left unattended, the Terminal Equipment Controller has an auto scrolling display
that shows the actual status of the system.
Each item is scrolled one by one with the back lighting in low level mode. Pressing any
key will cause the back light to come on to high level.
Manual scroll of each menu item is achieved by pressing the Yes (scroll) key repetitively.
The last item viewed will be shown on the display for 30 seconds before returning to
automatic scrolling. Temperature is automatically updated when scrolling is held.

11 | PIR Ready VT76x7 Series-Installation Guide
Sequence of auto-scroll status display:
ROOM
TEMP & RH
CLOCK
STATUS
SYSTEM
MODE
SCHEDULE
STATUS
OUTDOOR
TEMPERATURE
ALARMS
x.x °C
or °F
XX % RH
Monday
12:00
AM
Sys mode
auto
Occupied
Outdoor
x.x °C or°F
Service
Sys mode
off
Occupied
hold
Frost
ON
Sys mode
heat
Unoccup
SetClock
Sys mode
cool
Filter
Sys mode
emergency
Fan lock
Outdoor air temperature
Outdoor air temperature display is only enabled when outdoor air temperature sensor
is connected.
A maximum range status display of 50 °C ( 122 °F ) indicates a shorted sensor.
Associated functions, such as mode lockouts and economizer function are
automatically disabled.
A minimum range status -40 °C ( -40 °F ) is not displayed and indicates a opened
sensor or a sensor not connected. Associated functions, such as mode lockouts are
automatically disabled.
Alarms
If alarms are detected, they will automatically be displayed at the end of the status
display scroll.
During an alarm message display, the back lit screen will light up at the same time as
the message and shut off during the rest of the status display.
Two alarms maximum can appear at any given time.
The priority for the alarms is as follows:
Frost ON
Indicates that the heating is energized by the low limit frost protection room
temperature setpoint 5.6 °C ( 42 °F )
SetClock
Indicates that the clock needs to be reset. There has been a power failure
which has lasted longer than 6 hours
Service
Indicates that there is a service alarm as per one of the configurable digital
input ( DI1 or DI2 )
Filter
Indicates that the filters are dirty as per one of the configurable digital input (
DI1 or DI2 )
Fan lock
Indicates that the heating and cooling action are locked out due to a defective
fan operation

12 | PIR Ready VT76x7 Series-Installation Guide
Three status LEDs on the Terminal Equipment Controller cover are used to indicate
the status of the fan, a call for heat, or a call for cooling.
When any of the fan is ON, the FAN LED will illuminate
When heating is ON, the HEAT LED will illuminate
When cooling is ON, the COOL LED will illuminate
LED
operation
Heatpump models
VT76xxH
Multistage and single
stage models
VT7600A, VT7652A,
VT7600B & VT7652B
Multistage
economizer models
VT7605B & VT7656B
Fan LED
on
When G Fan terminal
operates
When G Fan terminal
operates
When G Fan terminal
operates
Heating
LED on
When Y1 and / or W1
terminal(s) operate in
heating mode
When W1 terminal
operate in heating
mode
When W1 terminal
operate in heating
mode
Cooling
LED on
When Y1 terminal
operate in cooling
mode
When Y1 terminal
operate in cooling
mode
When Y1 terminal
operate in cooling
mode and or
economizer output is in
function
USER INTERFACE
User configuring instructions menu
The VT76x7 series of Terminal Equipment Controller
feature an intuitive, menu-driven, back-lit LCD display
that walks users through the configuring steps, making
the configuring process extremely simple. This menu
is typically accessed by the user to set the parameters
such as temperature and time events, system mode,
fan mode, etc.
It is possible to bring up the user menu at any time by depressing the MENU key. The
status display automatically resumes after exiting the user-configuring menu.
If the user pauses at any given time during configuring, Auto Help text is displayed to help
and guide the user through the usage and configuring of the Terminal Equipment
Controller.
Ex.:
Press yes key to change cooling temperature setpoint
Use the up or down arrow to adjust cooling setpoint

13 | PIR Ready VT76x7 Series-Installation Guide
Local keypad interface
Each of the sections in the menu is accessed and configured using 5 keys on the
Terminal Equipment Controller cover.
The priority for the alarms is as follows:
The YES key is used to confirm a selection, to move onto the next menu item
and to manually scroll through the displayed information.
The NO key is used when you do not desire a parameter change, and to
advance to the next menu item. Can also be used to toggle between heating
and cooling setpoints.
The MENU key is used to access the Main User Menu or exit the menu.
The down arrow key is used to decrease temperature setpoint and to adjust
the desired values when configuring the Terminal Equipment Controller.
The up arrow key is used to increase temperature setpoint and to adjust the
desired values when configuring the Terminal Equipment Controller.
When left unattended for 45 seconds, the display will resume automatic status display
scrolling.
To turn on the back light, press any key on the front panel. The back lit display will turn off
when the Terminal Equipment Controller is left unattended for 45 seconds
Sequence of user menu:
Override
Resume
Temperature
setpoints
Humidity
setpoints
System
mode
setting
Fan
mode
setting
Schedules
setting
Clock
setting
Schedule
hold
Override
schd Y/N
Temperat
Set Y/N
Humidity
Set Y/N
Sys
mode
set
Y/N
Fan
mode
set
Y/N
Schedule
set Y/N
Clock
set
Y/N
Schedule
hold Y/N
Appears
only in
unoccupied
mode
Appears
only on
stand-alone
(Network
Ready)
models
Cancel
ovrd Y/N
Appears
only in
override
mode

14 | PIR Ready VT76x7 Series-Installation Guide
Occupied setpoints adjustments
There is a default profile set in the Terminal Equipment Controller from the factory.
This enables the Terminal Equipment Controller to operate as a non-scheduling unit in
day mode operation at start up.
Default temperature
setpoints:
Default modes:
Occupied cooling setpoint =
24 °C ( 75 °F )
System mode = Auto
Occupied heating setpoint =
22 °C ( 72 °F )
Fan mode = Smart (for models with a communication
module or scheduling network
ready models)
Fan mode = Auto (for non-scheduling network ready
models)
Unoccupied cooling setpoint
= 28 °C ( 82 °F )
Unoccupied heating setpoint
= 18 °C ( 65 °F )
Default schedules:
Fahrenheit scale
Monday through Sunday
Setpoint type = permanent
Occupied time is: 12 00 AM
Unoccupied time is: 11:59 PM
There will be a 1 minute unoccupied period every night at 11:59 PM with this default
configuration.
A) Override an unoccupied period
Override
schd Y/N
This menu will appear only when the Terminal Equipment Controller is in unoccupied
mode. The unoccupied mode is enabled either by the internal timer scheduling or by a
remote NSB contact via DI1 or DI2.
If DI1 or DI2 is configured to operate as a remote temporary override contact, this menu
will be disabled.
Answering yes to this prompt will cause the Terminal Equipment Controller to go into
occupied mode for an amount of time equal to the parameter “TOccTime” (1 to 12 hours).
B) Resume regular scheduling
Cancel
ovrd Y/N
This menu does not appear in regular operation. It will appear only when the Terminal
Equipment Controller is in unoccupied override mode.
Answering “Yes” to this question will cause the Terminal Equipment Controller to resume
the regular setpoints & scheduling.

15 | PIR Ready VT76x7 Series-Installation Guide
C) Temperature setpoints
Permanent setpoint changes
Temperat
set Y/N
This menu permits the adjustment of all permanent temperature setpoints (occupied and
unoccupied) as well as the desired temperature units (°F or °C). Permanent setpoints are
written to RAM and EEPROM.
Cooling
setpoint
Occupied mode
Heating
setpoint
Occupied mode
Cooling
setpoint
Unoccupied
mode
Heating setpoint
Unoccupied
mode
°F or °C
display setting
Cooling
set? Y/N
No next
Yes down
Heating
set? Y/N
No next
Yes down
Unocc CL
set? Y/N
No next
Yes down
Unocc HT
set? Y/N
No next
Yes down
°F or °C
set? Y/N
No next
Yes down
Use ▲▼ keys to set value, Yes key to confirm
Cooling
70.0 °F
Use ▲▼
To set
value
Heating
68.00 °F
Use ▲▼
To set
value
Unocc CL
80.0 °F
Use ▲▼
To set
value
Unocc HT
60.0 °F
Use ▲▼
To set
value
Units
°F
Use ▲▼
To set
value
Temporary setpoint changes
Temporary setpoints can be modified through the Up arrow key (▲) and the Down arrow
keys (▼).
User will be prompted with the present mode (Heating or Cooling) of the Terminal
Equipment Controller and its setpoint.
The Up (▲) arrow key will increment the setpoint by 0.5 degree (F or C).
The Down (▼) arrow key will decrement the setpoint by 0.5 degree (F or C).
Press the Yes key to accept the new setpoint.
Local changes to the heating or cooling setpoints made by the user directly using the up
or down arrow are temporary.
They will remain effective for the duration specified by ToccTime.
Setpoints will revert back to their default value after internal timer ToccTime expires.
If a permanent change to the setpoints is required, use the Temperat set ? menu
D) Humidity setpoints
Humidity
set Y/N
This menu permits the adjustment of humidification and dehumidification setpoints.
Dehumidification
setpoint
Humidification
setpoint
Dehumidi
set? Y/N
No next
Yes down
Humidifi
set? Y/N
No next
Yes down
Use ▲▼ keys to set value, Yes key to confirm
Dehumidi
70 %
Use ▲▼
To set value
Humidifi
50 %
Use ▲▼
To set value
To prevent overlap, a minimum fixed deadband of 5% RH will always prevail between the
humidification and dehumidification setpoints. For example, if the humidification setpoint is

16 | PIR Ready VT76x7 Series-Installation Guide
50% RH and the dehumidification setpoint is changed from 70% RH to 45% RH, the
humidification setpoint will be modified to 45% RH by the Terminal Equipment Controller.
Humidification process
Humidification process will only be allowed when the Terminal Equipment Controller is in
heating mode (System Mode = Heat or System Mode = Auto and effective mode at the
Terminal Equipment Controller is heat). If there is a humidification demand and the fan is
OFF, the fan is first turned ON and the humidifier output is then activated.
Other than having the RH setpoint, the following events can stop the humidification
process at any time: RH sensor is out of range, System Mode is switched to Off or Cool
and the System Mode = Auto but the room’s effective mode changes from Heat to Cool
Dehumidification process
If (Dhu LCK) Dehumidification Lockout Functions is set to On (Enabled):
Dehumidification process will only be allowed when the Terminal Equipment Controller is
in cooling mode (System Mode = Cool or System Mode = Auto and effective mode at the
Terminal Equipment Controller is cool). If there is a dehumidification demand and the fan
is OFF, the fan is first turned ON and the dehumidification output is then activated.
Other than having reach the dehumidification setpoint, the following events can stop the
dehumidification process at any time:
RH sensor is out of range
System Mode is switched to Off, Heat or System Mode = Auto and effective
mode at the Terminal Equipment Controller is Heat
The room temp drops below the cooling setpoint minus the deadband value
The Outside air temp is below the Dhu OALK parameter
If (Dhu LCK) Dehumidification Lockout Functions is set to Off (Disabled):
Other than having reach the dehumidification setpoint, the following events can stop the
dehumidification process at any time:
RH sensor is out of range
System Mode is switched to Off
The Outside air temp is below the Dhu OALK parameter
Dehumidification process is allowed when the Terminal Equipment Controller operates in
all system modes except Off. If there is a dehumidification demand. If the fan is OFF, the
fan is first turned ON and the dehumidification output is then activated.
There is NO active temperature lockout protection in this mode. If the dehumidification
process causes the room temperature to rise or fall, the Terminal Equipment Controller
will react by either activating the cooling or heating outputs based on its current system
mode settings.

17 | PIR Ready VT76x7 Series-Installation Guide
E) System mode setting
Sys mode
set Y/N
This menu is accessed to set system mode operation
Use ▲▼ to set value, Yes key to confirm
Sys mode
auto
Automatic mode
Automatic changeover mode between heating and cooling operation
Sys mode
cooling
Cooling mode
Cooling operation mode only
Sys mode
heating
Heating mode
Heating operation mode only
Sys mode
emergency
Emergency heat mode ( heat pump models only )
Forced auxiliary heat operation mode only
Sys mode
off
Off mode Normal cooling or heating operation disabled
If enabled in installer parameters, only the automatic heating frost protection
at 50 °F ( 10 °C ) is enabled
F) Fan mode setting
Fan mode
set Y/N
This section of the menu is permits the setting of the fan mode operation.
Use ▲▼ to set value, Yes key to confirm
Fan mode
On
On fan mode
Fan is on continuously, even when system mode is OFF.
Fan mode
Auto
Automatic fan mode
Fan cycles on a call for heating or cooling for both occupied & unoccupied
periods.
Fan mode
Smart
Smart fan mode
During occupied periods, fan is on continuously. In unoccupied mode, fan
cycles on a call for heating or cooling.
This selection is available on all models with a communication module, on all
stand-alone (Network Ready) scheduling models or if DI1 or DI2 is set to
RemNSB on stand-alone non-scheduling models.
G) Schedule set (2 events)
Scheduling can have 2 or 4 events per day. This is set in the configuration menu as per
parameter (2/4event )
Schedule
set Y/N
This section of the menu permits the user to set the whether 2 or 4 events is needed.
Each day can be tailored to specific schedules if needed.
2 events can be scheduled per day.
Occupied & unoccupied periods can be set for each day.

18 | PIR Ready VT76x7 Series-Installation Guide
Monday timer
Schedule set
Tuesday timer
Schedule set
Wednesday timer
Schedule set
Other days are
identical
Monday
set? Y/N
No next
Yes down
Tuesday
set? Y/N
No next
Yes down
Wednesda
set? Y/N
No next
Yes down
Selects the day to be scheduled or
modified
Yes key to access day scheduling, No key to jump to next day
Occupied
Day? Y/N
No next
Yes down
Occupied
Day? Y/N
No next
Yes down
Occupied
Day? Y/N
No next
Yes down
Yes = Daily schedules will be
accessed
No = Unoccupied mode all day
Yes key to access day scheduling, No key to jump to next day
Copy Y/N
Previous
Yes next
No down
Copy Y/N
Previous
Yes next
No down
Yes = Will copy previous day
schedule
No = Daily schedules will be
accessed
Yes key to copy previous day, No key to set new time value for each day
Occupied
00:00 AM
Use ▲▼
To set
value
Occupied
00:00 AM
Use ▲▼
To set
value
Occupied
00:00 AM
Use ▲▼
To set
value
Sets Event # 1 Occupied time
Will activate occupied setpoints
Use ▲▼ to set value, Yes key to confirm
Unoccup
00:00 AM
Use ▲▼
To set
value
Unoccup
00:00 AM
Use ▲▼
To set
value
Unoccup
00:00 AM
Use ▲▼
To set
value
Sets Event # 2 Unoccupied time
Will activate unoccupied setpoints
Use ▲▼ to set value, Yes key to confirm
Typical examples of a 2 event office schedule
Ex. #1 Office building closed all weekend
Event
Period #1 - Event #1
Period #1 - Event #2
Occupied
Unoccupied
Setpoint
Cool
Heat
Cool
Heat
Daily
72 °F
70 °F
80 °F
62 °F
Occupancy
Monday
7.00 AM
6.00 PM
Day time only
Tuesday
7.00 AM
6.00 PM
Day time only
Wednesday
7.00 AM
6.00 PM
Day time only
Thursday
7.00 AM
6.00 PM
Day time only
Friday
7.00 AM
6.00 PM
Day time only
Saturday
12.00 PM *
12.00 PM *
Unoccupied
Sunday
12.00 PM *
12.00 PM *
Unoccupied
*Scheduling consecutive events to the same time will cause the Terminal Equipment
Controller to choose the last event as the time at which it will set its schedule. In the
above example, the Terminal Equipment Controller will control to the unoccupied set
point until 7:00 AM Monday.
Ex. #2 Commercial building which is occupied all weekend
Event
Period #1 - Event
#1
Period #1 - Event
#2
Occupied
Unoccupied
Setpoint
Cool
Heat
Cool
Heat
Daily
72 °F
70 °F
80 °F
62 °F
Occupancy
Monday
8.00 AM
5.00 PM
Day time only
Tuesday
8.00 AM
5.00 PM
Day time only
Wednesday
8.00 AM
5.00 PM
Day time only
Thursday
8.00 AM
5.00 PM
Day time only
Friday
8.00 AM
5.00 PM
Day time only
Saturday
12.00 AM **
11.59 PM **
Occupied
Sunday
12.00 AM **
11.59 PM **
Occupied
Note: 12:00 PM = Noon
12:00 AM = Midnight

19 | PIR Ready VT76x7 Series-Installation Guide
** To schedule a day as occupied for 24 hours, set that day Occupied time to 12:00 AM
and Unoccupied time to 11:59 PM There will be a 1 minute unoccupied period every
night at 11:59 PM with this schedule configuration.
H) Schedule set (4 events)
Schedule
set Y/N
This section of the menu permits the user to set the whether 2 or 4 events is needed. Each
day can be tailored to specific schedules if needed.
4 events can be scheduled per day.
Occupied & Unoccupied periods can be set for each day.
Scheduling the 3 rd. & 4 th. events to the same time will cancel the last period.
Monday timer
Schedule set
Tuesday timer
Schedule set
Wednesday timer
Schedule set
Other days are identical
Monday
set? Y/N
No next
Yes down
Tuesday
set? Y/N
No next
Yes down
Wednesda
set? Y/N
No next
Yes down
Selects the day to be scheduled or
modified
Yes key to access day scheduling, No key to jump to next day
Occupied
Day? Y/N
No next
Yes down
Occupied
Day? Y/N
No next
Yes down
Occupied
Day? Y/N
No next
Yes down
Yes = Daily schedules will be
accessed
No = Unoccupied mode all day
Yes key to access day scheduling, No key to jump to next day
Copy Y/N
Previous
Yes next
No down
Copy Y/N
Previous
Yes next
No down
Yes = Will copy previous day
schedule
No = Daily schedules will be
accessed
Yes key to copy previous day, No key to set new time value for each day
Occupied
00:00 AM
Use ▲▼
To set
value
Occupied
00:00 AM
Use ▲▼
To set value
Occupied
00:00 AM
Use ▲▼
To set
value
Sets Event # 1 Occupied time
Will activate occupied setpoints
Use ▲▼ to set value, Yes key to confirm
Unoccup
00:00 AM
Use ▲▼
To set
value
Unoccup
00:00 AM
Use ▲▼
To set value
Unoccup
00:00 AM
Use ▲▼
To set
value
Sets Event # 2 Unoccupied time
Will activate unoccupied setpoints
Use ▲▼ to set value, Yes key to confirm
Occupie2
00:00 AM
Use ▲▼
To set
value
Occupie2
00:00 AM
Use ▲▼
To set value
Occupie2
00:00 AM
Use ▲▼
To set
value
Sets Event # 3 Occupied time
Will activate occupied setpoints
Use ▲▼ to set value, Yes key to confirm
Unoccup2
00:00 AM
Use ▲▼
To set
value
Unoccup2
00:00 AM
Use ▲▼
To set value
Unoccup2
00:00 AM
Use ▲▼
To set
value
Sets Event # 4 Unoccupied time
Will activate unoccupied setpoints
Use ▲▼ to set value, Yes key to confirm
Ex. #1 Four event retail establishment schedule
Event
Period 1 -
Event 1
Period 1 -
Event 2
Period 2 -
Event 3
Period 2 -
Event 4
Setpoint
Occupied
Unoccupied
Occupied
Unoccupied
Cool
Heat
Cool
Heat
Cool
Heat
Cool
Heat
Daily
72
°F
70
°F
80
°F
62
°F
72
°F
70 °F
80
°F
62 °F
Occupancy
Monday
7.00 AM
5.00 PM
12.00 PM *
12.00 PM *
Day time only
Tuesday
7.00 AM
5.00 PM
12.00 PM *
12.00 PM *
Day time only
Wednesday
7.00 AM
5.00 PM
12.00 PM *
12.00 PM *
Day time only
Thursday
7.00 AM
5.00 PM
7.00 PM
10.30 PM
Day/evening
time only
Friday
7.00 AM
5.00 PM
7.00 PM
10.30 PM
Day/evening
time only
Saturday
12.00 PM *
12.00 PM *
12.00 PM *
12.00 PM *
Unoccupied
Sunday
12.00 PM *
12.00 PM *
12.00 PM *
12.00 PM *
Unoccupied

20 | PIR Ready VT76x7 Series-Installation Guide
* Scheduling events to the same time will cancel the last period and leave the Terminal
Equipment Controller in unoccupied mode
Ex. #2 Residential
Event
Period 1 -
Event 1
Period 1 -
Event 2
Period 2 -
Event 3
Period 2 -
Event 4
Setpoint
Occupied
Unoccupied
Occupied
Unoccupied
Cool
Heat
Cool
Heat
Cool
Heat
Cool
Heat
Daily
72
°F
70
°F
80
°F
62
°F
72
°F
70 °F
80
°F
62 °F
Occupancy
Monday
6:00 AM
8:00 AM
4:00 PM
10:00 PM
Day/evening
time only
Tuesday
6:00 AM
8:00 AM
4:00 PM
10:00 PM
Day/evening
time only
Wednesday
6:00 AM
8:00 AM
4:00 PM
10:00 PM
Day/evening
time only
Thursday
6:00 AM
8:00 AM
4:00 PM
10:00 PM
Day/evening
time only
Friday
6:00 AM
8:00 AM
4:00 PM
11:30 PM
Day/evening
time only
Saturday
8:00 AM *
8:00 AM *
8:00 AM *
11:59 PM *
Day time only
Sunday
12:00 AM *
12:00 AM *
12:00 AM *
11:59 PM *
Occupied all
day
*Scheduling consecutive events to the same time will cause the Terminal Equipment
Controller to choose the last event as the time at which it will set its schedule. In the above
example for Saturday, the Terminal Equipment Controller will control to the occupied set
point from 8:00 AM until 11:59 PM. Since it is desired to be in occupied mode throughout
the night, then it is necessary to schedule the first event on Sunday at 12:00 AM. The
Terminal Equipment Controller will force a one minute unoccupied period for a one minute
period (between 11:59 PM and 12:00 AM on Saturday)
I) Clock/Day Settings
Clock
set Y/N
This section of the menu permits the user to set the time and day.
Time setting
Day setting
Time format setting
Time
set? Y/N
No next
Yes down
Day
set? Y/N
No next
Yes down
12/24hrs
set? Y/N
No = exit
Yes down
Time
0:00
Use ▲▼
To set value
Day
Monday
Use ▲▼
To set value
12/24hrs
12 hrs
Use ▲▼
To set value
J) Schedule hold
Schedule
hold Y/N
This menu will only appear on stand-alone (Network Ready) Terminal
Equipment Controller, i.e. without a BACnet™ / Echelon™ module.
This section of the menu permits the user to set a permanent schedule
hold, which bypasses the internal Terminal Equipment Controller
scheduling.
The permanent schedule hold function is typically used for non-
scheduled events that extend for various periods of time.
This manual suits for next models
5
Table of contents
Other Viconics Thermostat manuals

Viconics
Viconics VT8300 Series User manual

Viconics
Viconics PIR Ready7 VT76x7 Series Use and care manual

Viconics
Viconics VT7300A5000 User manual

Viconics
Viconics VZ7200F5x00W User guide

Viconics
Viconics VT7300F5500-2969 User manual

Viconics
Viconics VT8000 Series User manual

Viconics
Viconics VT8000 Series User manual
Popular Thermostat manuals by other brands

Aube Technologies
Aube Technologies TH450 owner's guide

olympia electronics
olympia electronics BS-901 quick start guide

Aube Technologies
Aube Technologies TH135-01 instruction manual

Cadet
Cadet SMART-BASE SBFT2 installation instructions

EPH Controls
EPH Controls CRT2 operating instructions

Grohe
Grohe GROHTHERM SMARTCONTROL 29 121 manual