5. FAQ
Q1: Can I combine three ET112s for a 3-phase system?
No. Use a real 3-phase meter.
Q2: Can I use other meters, for example from other brands?
No.
Q3: I already have a Fronius SmartGrid meter, can I use that?
No.
Q4: What are the differences between the various 3-phase meters?
• EM24 - REL200100000 - Carlo Gavazzi EM24DINAV93XISX
• ET112 - REL300100000 - Carlo Gavazzi ET112-DIN.AV01.X.S1.X
• ET340 - REL300300000 - Carlo Gavazzi ET340-DIN.AV23.X.S1.X
Differences:
• The ET meters don't have a front selector that the installer needs to put in a different setting than it comes out of the box:
easier, less mistakes to be made.
• The ET meters have no display. The only thing they have is an LED, which blinks in case of active communication.
• The new meters have two RJ45 sockets for the Modbus RS485 connection. But they are not used. Note the possible confusion
because of yet another RJ45 socket in the Victron world though. Don't mix that with VE.Bus, VE.Can or VE.net. Besides the
RJ45 sockets, the meters still also have screw terminals access below the sockets for the RS485 wiring, which is how we
advise to connect a meter to the RS485 to USB interface and then a GX device.
• Since there is no display, the modbus address can no longer be changed on the meter. Combining multiple of those meters on
one RS485 network is therefore not supported by Victron. You are advised to use multiple RS485 to USB interfaces.
3-phase new meter only (ET340):
• Measuring energy from single-phase PV Inverter on the second phase of the new meter, ET340, actually works. Whereas with
the old meter, the EM24, only the Power Metering (Watts) works. The Energy Metering (kWh) for a single phase PV Inverter on
the second phase of the EM24 does not work. See Q9 for the details.
Q5: Will you keep shipping both 3-phase meters? (ET340 & EM24)
Yes. There are still situations suitable for each. See Q8.
Q6: Can I buy those meters directly from Carlo Gavazzi instead of from you?
Yes. That is also why we make no secret of the CG part numbers.
Q7: I want to use Current Transformers (CTs), is that possible?
Yes. You can buy the CG EM24DINAV53DISX directly from Carlo Gavazzi or one of their distributors. Even though Victron does
not stock that type of meter, we do support it in our software.
Q8: What’s the difference between ET340 and EM24 in 3-phase systems?
These meters have a different way of calculating the total of energy imported and exported.
In the ET340, the energy imported and exported is counted at each individual phase and then the Total is provided from the sum
of those values.
In the EM24, the energy imported and exported is counted as a total power, with net differential readings from each phase
cancelling each other out.
Which Energy Meter is most suitable depends on the measuring configuration in your country. It is most common in Australia and
Germany for example to only be billed for the total in a 3-phase system. So it is more accurate to use an EM24 to match the
billing.
So if you are exporting from one phase and importing from another phase after the energy meter, but before the billing meter,
then you will not be charged for this, and the meter should not count it as an import and an export.
This is also how Victron’s phase compensation feature works, to make the most of the cost savings for an ESS system when
there is a differential in generation and load across different phases.
Energy Meter Manual
Page 11 FAQ