Viking B-1 Instruction manual

TECHNICAL DATA
January 12, 2007 Deluge Devices 270a
RELEASE CONTROL PANEL
MODEL B-1
The Viking Corporation, 210 N Industrial Park Road, Hastings MI 49058
1. DESCRIPTION
The Viking Model B-1 Par-3 Release Control Panel is a supervised, 24 Volt, microprocessor-
controlled Release Control Panel. The panel is designed to operate up to two electric release
devices (usually solenoid valves) in the release piping of deluge or preaction systems. The
panel is available for use with either 120 VAC or 230 VAC power supplies.Abuilt-in battery com-
partment holds two 12 Volt batteries that are charged by an internal battery charger. Batteries
are available to provide up to 90 hours of backup power during AC power failure.
The Model B-1 Release Control Panel can be used with a wide range of compatible initiating
devices, such as heat (including linear heat detection systems like the Protectowire Systems),
photoelectric, ionization, and smoke detectors.
A dip switch ‘Function Selector’ allows field programming for one of four possible input/output
combinations (refer to Table 2).
In fire conditions, when an initiating device circuit (or predetermined combination of circuits) is
energized, the panel activates a combination of release device circuits and alarm circuits ac-
cording to the ‘Function Selector’ setting. On the panel’s display board, the appropriate Alarm,
Trouble, and Supervisory LED’s will flash until the event has been acknowledged.After depress-
ing the Tone or Alarm Silence button, the LED will remain steadily illuminated until the panel is
reset.
2. LISTINGS AND APPROVALS
Refer to Table 1
3. TECHNICAL DATA
I. Specifications
A. Enclosure
Dimensions: 16.125” high x 14.625” wide x 5.375” deep (50 cm x 37,1 cm x 13,7 cm)
Weight: 23 lbs. (10,4 kg)
Finish: Red Enamel
Vented Enclosure
B. Environment
Temperature: 32 °F to 120 °F (0 °C to 48 °C)
Humidity: 85% Relative Humidity (non-condensing) at 90 °F (32 °C) maximum
C. AC Power
Par-3 and Par-3C: 120 VAC, 50/60 Hz, 1.2 amps
Par-3E: 230 VAC, 50 Hz, 0.65 amps
Wire size: minimum #14 AWG with 600 V insulation
D. Battery
Type- Lead Acid
Maximum charging circuit: 27.6V, 1.5ASeeACCESSORIES for batteries available from Viking.
E. Initiating Device (Input) Circuits
Four style B (Class B)/Style D (Class A) circuits
Input 1: Detection Circuit
Input 2: Detection Circuit
Input 3: Waterflow (Alarm Pressure Switch)
Input 4: Supervisory Circuit
F. System Alarm
Power limited circuitry
Fuses: 2AG, 4 amperes
Normal operating voltage: 24VDC (ripple = 10mV peak to peak)
Alarm Current: 15mA minimum
Short circuit current: 40mA maximum
Maximum detector current in standby: 2 milliamps (peak) per zone
Maximum loop resistance: 100 ohms
End-of-Line resistor: 4.7K (provided)
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
Viking Technical Data may be found on
The Viking Corporation’s Web site at
http://www.vikinggroupinc.com.
The Web site may include a more recent
edition of this Technical Data Page.
Revised page replaces page 270 a-g dated August 17, 2006
(Added California State Fire Marshal approval)
Form No. F_063092
OBSOLETE

TECHNICAL DATA
January 12, 2007
Deluge Devices 270b
RELEASE CONTROL PANEL
MODEL B-1
The Viking Corporation, 210 N Industrial Park Road, Hastings MI 49058
Note: leave E-O-L resistors provided, on all unused circuits.
Detector loop current is sufficient to ensure operation of one alarmed
detector per zone.
Supervisory current: 5mA (including End-of-Line Resistor)
G. Heat Detectors:
Detection circuits allow for installation of any number of listed or ap-
proved normally open thermal detectors.
H. Smoke Detectors:
ContacttheVikingdistributorfor a listofcompatible smokedetectors,
information concerning the maximum number of smoke detectors
allowed per zone, and standby power requirements for the smoke
detector used. Also, refer to appropriate Fire Protection Equipment
Approval Guides.
For supervised four-wire smoke detectors, connect the Power Su-
pervision Relay to the last detector base 24V screw terminals.
See ACCESSORIES.
I. Indicating Appliance and Releasing (output) Circuits
Two Style Y and two Style Y/Z circuits
Output 1: Alarm Bell(Style Y/Z)
Output 2: Waterflow or Trouble Horn (Style Y/Z)
Output 3: Releasing Circuit 1 (Style Y)
Output 4: Releasing Circuit 2 or Trouble Horn(Style Y)
Normal operating voltage: 24VDC
Total current available to all four circuits + RMS regulated power
output circuit, not to exceed: 2.25 AMPS
Maximum signaling current per circuit: 2.25 AMPS
Supervised Circuitry Power limited circuitry (except for Municipal
Box output)
Fuses: 2AG, 4 amperes
Maximum allowable voltage drop due to wiring: 2 VDC.
End-of-Line resistor: 4.7K (provided)
Note: leave E-O-L resistors provided, on all unused circuits.
Note: Wiring must be configured to maintain a minimum voltage of 20.4V on release circuits.
Contact the Viking distributor for a list of compatible indicating appliances and releasing devices. Also, refer to Viking Technical
Data and appropriate Fire Protection Equipment Approval Guides.
J. Alarm Relay
Basic panel includes one non-silenceable Form-C dry alarm contact rated 2 amps at 30 VDC and 0.5 amps at 30 VAC (resis-
tive).
K. Trouble Relay
Basic panel includes one Form-C dry alarm contact rated 2 amps at 30 VDC and 0.5 amps at 30 VAC (resistive). Trouble relay
will silence when trouble condition is cleared.
L. Zone Relay Module
Model B-1 Panels include one Zone Relay Module (4XZM) providing dry Form-C contacts controlled by each of the four output
circuits plus one general alarm and one panel/field-wiring trouble relay. See Table 2.
M. Power Outputs
Four-wire Smoke Detector Power (resettable): Up to 200 mA total (four-wire smoke detector power plus non-resettable power
combined) DC current available. Maximum ripple voltage: 10mV p/p.
Non-resettable Power: Up to 200 mA total (four-wire smoke detector power plus non-resettable power combined) DC current
available.
Maximum ripple voltage: 10mV p/p.
RMS Regulated Power: Total current available for external devices: 0.5 amp (subtracted from 2.25 A available to indicating ap-
pliance circuits) DC current available.
Maximum ripple voltage: 100mV p/p.
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
Figure 1
OBSOLETE

TECHNICAL DATA
January 12, 2007 Deluge Devices 270c
RELEASE CONTROL PANEL
MODEL B-1
The Viking Corporation, 210 N Industrial Park Road, Hastings MI 49058
N. Front Panel Control Switches (Refer to Figure 1)
Switch 1: Tone Silence
Switch 2: Alarm Silence - Tone Silence and Alarm Silence control switches can be activated to acknowledge alarms. A second
“trouble” will resound the piezo.
Switch 3: Alarm Activate -The Alarm Activate switch may be used to activate indicating circuits and relays.
Switch 4: System Reset - The Reset switch clears any activated output circuits. If alarm or trouble conditions exist when the reset
switch is pushed, they will re-activate the panel.
O. Front Panel Zone Status LEDs
When the panel is activated, zone status LEDs illuminate, to indicate the status of Zone 1, Zone 2,Alarm Pressure, andAuxiliary
Supervisory circuits.
Alarm (red) LEDs indicate activation of a detection device.
Trouble (yellow) LEDs indicate electrical circuit failure, such as short circuits and loose wires.
P. Front Panel System Status LEDs
The presence of AC Power is indicated by a constant green LED, indicating normal conditions.
Alarm (red), Trouble (yellow), and Supervisory (yellow) LEDs activate as required to indicate System Alarm, Release operation,
Supervisory Device activation, and Circuit trouble.
LEDs also illuminate to indicate when the Alarm Silence switch has been activated.
Q. Last Event Recall
Follow procedure printed in Par-3 Owner’s Manual provided with panel.
R. Zone Disable Function
Follow procedure printed in Par-3 Owner’s Manual provided with panel.
S. Battery Fail and Earth Fault supervision
See Figure 2 for location of LEDs
T. Discharge timer option
Latched, 10 or 15 minutes. Refer to Par-3 Owner’s manual included with panel. Also refer to installation standards, Technical
Data, and all Authorities Having Jurisdiction when using timer configurations.
Output circuits protected against false activation by two step command sequence
U. Slide in zone identification labels
Spare labels included in Par-3 Owner’s Manual provided with panel.
V. Other Features
Piezo Sounder
Alarm signals are latching
Trouble signals are self restoring
Alarm and Trouble resound
II. Ordering Information
Part Numbers - Refer to Table 1
Available since 1991
A. Modules and Accessories (order separately)
1. Batteries
Two batteries of the same AH rating are required.
12V 7 Amp-Hour Viking P/N 07920
12V 12 Amp-Hour Viking P/N 07921 12V 18Amp-Hour Viking P/N 09867
Plug-in connector is provided with the Panel.
See POWER CALCULATIONS to determine which batteries meet standby battery requirements.
2. Zone Relay Module (4XZM) (Viking Part No. 07912)
Model B-1 Panels can accommodate a second 4XZM Zone Relay Module (one included in each panel) or one of the following
two Modules:
3. Transmitter Module (4XTM) (Viking P/N 07909)
Provides a supervised output for local energy municipal box transmitter and alarm and trouble reverse polarity circuits.
4. LED Interface Module (4XLM) (Viking P/N 07910)
For Remote Annunciator (RZA-4X) described below (Required for NYC approval).
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
OBSOLETE

TECHNICAL DATA
January 12, 2007
Deluge Devices 270d
RELEASE CONTROL PANEL
MODEL B-1
The Viking Corporation, 210 N Industrial Park Road, Hastings MI 49058
5. Remote Annunciator (RZA-4X) (Viking P/N 07911)
Mounts on standard single-gang box. (LED Interface Module (4XLM) described above is required).
Provides “System Trouble” LED
Local Piezo Sounder
Silence Switch (for local sounder)
Alarm/Waterflow Bell LED
Waterflow/Supervisory Bell LED
Releasing Circuit 1 LED
Supervisory Bell/Release Circuit 2 LED.
6. End-of-Line resistor (Viking Part No. 07913)
4.7K, ½ Watt, with terminal connector both ends, (for two-wire supervised circuits)
7. Power Supervisory Relay Coil (Viking Part No. 07919)
For four-wire smoke detector circuits
8. Voltage and Current Meters (4XZMM) (Viking Part No. 07917)
Mount inside cabinet
9. Digital Communicator NOTI-FIRE 911 (Viking Part No. 07918)
Kit For Central Station service
10. RFI Retrofit Kit (Viking Part No. 12696)
Includes Ferrite Beads, Transzorb and Dead Front Protective Panel
4. INSTALLATION
Prior to installation, review the Par-3 Owner’s Manual and Viking Field Wiring Diagrams. (See package inside panel.) Observe all
instructions provided in the Par-3 Owner’s Manual. Field wiring must be according to VIKING FIELD WIRING DIAGRAMS for the
specific mode of operation required. See Table 1.
All wiring should be done in accordance with National and/or Local codes for fire alarm systems.
The Authority Having Jurisdiction may have additional requirements.
Mount the cabinet in a clean, dry, vibration-free area where temperature and humidity conditions do not exceed limitations indi-
cated in TECHNICAL DATA.
Verify that all initiating devices (detectors), indicating appliances, and releasing devices are compatible with the Model B-1 Par-3
Release Control Panel. Contact the Viking distributor for a list of compatible devices. Also, refer to appropriate Fire Protection
Equipment Approval Guides.
Wire all alarm initiating devices sequentially for proper supervision.
Pull required conductors through the knockouts provided.
Prior to connecting to the panel, verify continuity of all circuitry.
Prior to connecting to the panel, check for, and correct any short circuits.
Make electrical connections to control panel for the detection, supervisory, alarm, trouble, and release circuits, according to ap-
propriate VIKING FIELD WIRING DIAGRAMS for the system used and the Owner’s Manual provided with the panel.
Where indicated on VIKING FIELD WIRING DIAGRAMS, install the 4.7 K Ohm ½ Watt End-of-Line Resistor (provided in
panel) at the remote end of circuit. End-of-Line Resistors should NOT be installed across Release Circuits.
On all un-used circuits, leave the 4.7 K Ohm ½ Watt End-of-Line Resistor (provided in panel) in place.
Maintain polarity on alarm bell and trouble bell circuits. Do not energize the panel until all associated, modules, and intercon-
necting cables have been connected.
Prior to energizing the panel:
Verify that dip switches controlling panel operation are in the proper position for the system used. Refer to Table 2 and VIKING
FIELD WIRING DIAGRAMS.
Verify that all modules are securely and properly positioned on their pins. If a module is loose, carefully align all pins and
press firmly into position.
Connect non-energized AC power to the panel. Refer to Figure 2 and VIKING FIELD WIRING DIAGRAMS.
Connect the wire providing in-coming voltage to the terminal marked “H”.
Connect the neutral wire to the terminal marked “N”.
Connect the ground wire to the terminal marked “G”.
Procedure for connecting Batteries: Note: Two battery plug/wire assemblies (long leads with plug) and jumper (short) wires are
provided with each panel. Connectors on one plug/wire assembly fit 7.0AH Batteries. Connectors on the other plug/wire assembly
fit 12.0 AH Batteries.
Position batteries end-to-end with terminals adjacent. Select the proper plug/wire assembly for the batteries used.
•
•
•
•
•
•
•
•
•
•
•
•
•
1.
2.
3.
4.
5.
6.
7.
a.
b.
c.
8. a.
b.
9. a.
b.
c.
10.
a.
OBSOLETE

TECHNICAL DATA
January 12, 2007 Deluge Devices 270e
RELEASE CONTROL PANEL
MODEL B-1
The Viking Corporation, 210 N Industrial Park Road, Hastings MI 49058
Connect the long RED lead to the positive terminal of one battery, and the long black lead to the negative terminal of the
other.
Place batteries inside the battery compartment of the Par-3 Release Control Panel with the unused terminals toward the open
door. Install batteries in the upright position only.
Plug the plug-in connector to J9 on the main board of the panel. (Refer to Figure 2 and VIKING FIELD WIRING DIAGRAMS.)
DO NOT install jumper at this time.
To energize the panel and place the system in service:
Energize the AC power supply to the panel. The Piezo will sound, and the “System Trouble” and “Power Trouble” LEDs will
flash.
Use the jumper (short) wire to connect the unused negative terminal of one battery with the unused positive terminal of the other
battery. The Piezo should silence, and the “System Trouble” and “Power Trouble” LEDs should stop flashing.
Perform appropriate tests to verify proper operation of the system.
After placing the system in service, close and lock the panel to prevent tampering with the unit.
When installing optional cards, modules, inter-connecting cables, or other associated equipment, refer to MAINTENANCE, technical
data for the optional equipment, and Owner’s Manual provided with the panel.
6. INSPECTIONS, TESTS AND MAINTENANCE
NOTICE: THE OWNER IS RESPONSIBLE FOR MAINTAINING THE FIRE PROTECTION SYSTEM AND DEVICES IN PROPER OPERAT-
ING CONDITION. THE VIKING MODEL B-1 PAR-3 RELEASE CONTROL PANEL MUST BE KEPT FREE OF FOREIGN MATTER AND
ENVIRONMENTAL CONDITIONS THAT COULD IMPAIR ITS OPERATION.
For minimum maintenance and inspection requirements, refer to NFPA 25. In addition, the Authority Having Jurisdiction may have ad-
ditional maintenance, testing, and inspection requirements that must be followed.
WARNING: ANYSYSTEM MAINTENANCE THAT REQUIRES PLACING ACONTROL VALVE OR DETECTION SYSTEM OUT OF SERVICE
MAY ELIMINATE THE FIRE PROTECTION CAPABILITIES OF THAT SYSTEM. PRIOR TO PROCEEDING, NOTIFY ALL AUTHORITIES
HAVING JURISDICTION. CONSIDERATION SHOULD BE GIVEN TO EMPLOYMENT OF A FIRE PATROL IN THE AFFECTED AREAS.
I. Tests
A. Prior to proceeding with tests:
Verify that installation complies with instructions in the Owner’s Manual provided with the panel and the appropriate VIKING
FIELD WIRING DIAGRAMS for the system used.
Notify the Authority Having Jurisdiction and all those in the area affected by the test.
B. Alarm Activate Switch
To test alarm bell, waterflow bell circuits and alarm, detection, and waterflow relays:
Push “Alarm Activate” (See Figure 1). Note: “Alarm Activate” is a latching function. “Alarm Silence” will silence indicating circuits
and System Alarm Relay and light the Alarm Silenced LED.
When test is complete, push “System Reset”. Conditions should return to normal.
C. Waterflow
To test waterflow alarm on Viking pre-action and Viking deluge systems, consult technical literature for the system used:
Turn the Alarm Test Valve to “Test” position. See Table 2 for output circuits and relays that should activate for the system used.
“Waterflow” circuits are latching.
When test is complete return the Alarm Test Valve to the normal position and push “System Reset”. Conditions should return to
normal.
C. Detection
To test detection circuits:
Close main water supply control valve, placing the system out of service.
CAUTION! FOR DELUGE AND SINGLE OR NON-INTERLOCKED PREACTION SYSTEMS, PERFORMING THIS TEST RESULTS IN
OPERATION OF THE DELUGE VALVE. FAILURE TO CLOSE THE MAIN WATER SUPPLY CONTROL VALVE WILL CAUSE WATER TO
FLOW INTO THE SPRINKLER PIPING.
CAUTION! FOR DOUBLE-INTERLOCKED SYSTEMS, SIMULTANEOUS OPERATION OF A DETECTOR AND LOWERING OF SUPER-
VISORY PRESSURE IN THE SPRINKLER PIPING WILL RESULT IN OPERATION OF THE DELUGE VALVE. FAILURE TO CLOSE THE
MAIN WATER SUPPLY CONTROL VALVE WILL CAUSE WATER TO FLOW INTO THE SPRINKLER PIPING.
b.
c.
d.
11.
12.
13.
14.
1.
2.
1.
2.
1.
2.
1.
OBSOLETE

TECHNICAL DATA
January 12, 2007
Deluge Devices 270f
RELEASE CONTROL PANEL
MODEL B-1
The Viking Corporation, 210 N Industrial Park Road, Hastings MI 49058
CAUTION! SIMULTANEOUS OPERATION OF BOTH DETECTION CIRCUITS ON ANY SYSTEM UTILIZING CROSS-ZONE DETECTION
WILL RESULT IN OPERATION OF THE DELUGE VALVE. FAILURE TO CLOSE THE MAIN WATER SUPPLY CONTROL VALVE WILL
CAUSE WATER TO FLOW INTO THE SPRINKLER PIPING.
Operate individual detectors, following instructions listed in technical data for the detector used. See Figure 2 for output circuits
and relays that should activate for the system used. “Detection” circuits are latching (except when configured for optional “timed
shut-off”. See Owner’s Manual).
When Test is complete, push “System Reset”. Conditions should return to normal.
Refer to technical data for the system used to open main water supply control valve and place the system back in service.
II. Maintenance
CAUTION: DISCONNECT ALL POWER SOURCES BEFORE SERVICING. THE PANEL AND ASSOCIATED EQUIPMENT MAY BE DAM-
AGED BY REMOVING AND/OR INSERTING CARDS, MODULES, OR INTERCONNECTING CABLES WHILE THE PANEL IS ENER-
GIZED.
7. AVAILABILITY
The Viking Model B-1 Release Control Panel is available through a network of domestic and international distributors. See the Viking
Corp. Web site for closest distributor or contact The Viking Corporation.
8. GUARANTEES
For details of warranty, refer to Viking’s current list price schedule or contact Viking directly.
2.
3.
4.
Table 1 - Part Numbers and Approvals
Name Power Supply Approvals Viking Part
No.
Par-3 110 VAC 50/60Hz UL1, FM, NYC3and CSFM407907
Par-3C 110 VAC 50/60Hz cUL207953
Par-3E 220 VAC 50/60Hz FM 07908
1UL listed Releasing Device Control Unit (UOJZ)
2cUL and CSA approved Par-3C
3 Accepted by New York City Department of Buildings (MEA 89-92-E) when configured for Single Hazard-Two
Zone operation (See Figure 1) and equipped with LED Interface Module (4XLM) and Remote Annuncitor
(RZA-4X) See ACCESSORIES
4Listed by the California State Fire Marshall (7770-0533:105)
OBSOLETE

TECHNICAL DATA
January 12, 2007 Deluge Devices 270g
RELEASE CONTROL PANEL
MODEL B-1
The Viking Corporation, 210 N Industrial Park Road, Hastings MI 49058
Table 2 - Dip Switch Settings for System Configuration Modes
DIP SWITCH SETTINGS
MODE DESCRIPTION CONFIGURATION OPERATION 123456
1Single Hazard -
Two Zone One release circuit.
Two detection circuits. Activation of EITHER detection cir-
cuit energizes the release circuit. OFFOFFOFFOFFOFF
NOT USED
2Single Hazard -
Cross Zone One release circuit.
Two detection circuits. BOTH detection circuits must acti-
vate to energize the release circuit. ON OFFOFFOFFOFF
3Dual Hazard
- Combined
Release
Two release circuits.
Two detection circuits.
Activation of EITHER detection
circuit energizes BOTH release cir-
cuits. OFF ON OFFOFFOFF
4Dual Hazard -
Split Release Two release circuits.
Two detection circuits.
Activation of detection circuit No.
1 energizes release circuit No. 1
Activation of detection circuit No. 2
energizes release circuit No. 2
ON ON OFFOFFOFF
Note: Dip Switches 3, 4 and 5 MUST be OFF to disable timer capabilities of the panel. For information concerning timer capabilities,
refer to PAR-3 Owners Manual. Also, refer to installation standards, Technical Data, and allAuthorities Having Jurisdiction when using
timer configurations.
Table 3 - Charts show Output and Relay Module Circuits Activated by Detection Circuits
OBSOLETE

TECHNICAL DATA
January 12, 2007
Deluge Devices 270h
RELEASE CONTROL PANEL
MODEL B-1
The Viking Corporation, 210 N Industrial Park Road, Hastings MI 49058
ITEM NO. PART
NUMBER DESCRIPTION QTY. NOTES
1 07912 Zone Relay Module 4XZM (Included with Panel)11 Optional1
2 07909 Transmitter Module 4XTM 1 Optional
3 -- LED Interface Module 4XLM 1 Optional
4 07911 Remote Annunciator Module RZA-4X 1 Optional
5 07917 Voltage, Current Meters 4XMM 1 Optional
607920 Battery, 12V, 7 Amp Hr. Capacity2OR 2 Two Batteries Required2
07921 Battery, 12V, 12 Amp Hr. Capacity2OR 2
09867 Battery, 12V, 18 Amp Hr. Capacity22
09866 Battery Box, Required when using 18 AH Batteries
7 07915 Fuses, 4 Amp 4 Included
8a 07914 Resistor, Dummy Load (Notifier 71245) 6 Included
8b 08391 Resistor, Dummy Load (Notifier 27072) 2 Included
9 07919 Power Relay 1 Optional
10a -- Battery Plug Wire Ass’y (7 Amp Battery) 1 Included
10b 08285 Battery Plug Wire Ass’y (12 Amp Battery) 1 Included
11 07913 Resistor, End-of-Line (Notifier 71252) 1 Optional
12a 08389 Mother Board 110 Volt31 Included3
12b 08390 Mother Board 220 Volt31 Included3
-- Indicates replacement part not available
1This unit can support a second Zone Relay Module 4XZM in addition to the one included with the panel.
2Always use two batteries of the same amperage. Order batteries separately after performing power calculations
to determine size of battery required to meet standby requirements.
3Voltage of AC Power Supply determines voltage of Mother Board required.
Figure 2 -
Replacement Parts
Revised page replaces page 270 a-g dated August 17, 2006
(Added California State Fire Marshal approval)
Form No. F_063092
OBSOLETE
Table of contents
Other Viking Control Panel manuals
Popular Control Panel manuals by other brands

Extron electronics
Extron electronics TLP Pro 320C user guide

Cermate Technologies
Cermate Technologies IT400 Series installation guide

Satel
Satel PERFECTA Quick installation guide

Siemens
Siemens SIMATIC HMI KTP400 Basic operating instructions

Plymovent
Plymovent CONTROLPRO instructions

Cooper Security
Cooper Security 9750 Installation and programming guide

WURM
WURM ANI-2F1 manual

Notifier
Notifier AFP-300 Operation manual

AMALGAMATED INSTRUMENT
AMALGAMATED INSTRUMENT PM4-TR Operation and instruction manual

Brother
Brother KE-430F Series Input Check

Schenck process
Schenck process Disomat Opus operating manual

Haes
Haes SZAOV Installation, commissioning & operating manual