Haes SZAOV Guide

SZAOV CONTROL
PANEL INSTALLATION,
COMMISSIONING &
OPERATING MANUAL
This manual covers the installation, programming and
commissioning of the Single Zone Automatically Opening Vent
Control Panel (SZAOV)

Single Zone AOV User Manual INTRODUCTION
2
Approved Document Ref: UI-SZAOV-01 Issue 2.01
INTRODUCTION
2797-CPR-747546
Haes Technologies Ltd, Unit 3, Horton Industrial Park, West Drayton, Uxbridge, UB7 8JD
21
Model Number CPR Number
SZAOV-1001 2797-CPR-747546
European Standard BS EN 12101-10:2005
Smoke and heat control systems –Part 10: Power supplies
Haes Technologies Ltd declare that the products identified above conform to the essential
requirements specified in the Construction Products Regulation CPR305/2011/EU.
In addition, the product complies with the following:
2014/35/EU, Low Voltage Directive
2014/30/EU, Electromagnetic Compatibility Directive
BS EN 61000-6-3:2007 + A1:2011, Electromagnetic Compatibility (EMC) General Standards.
Emission standard for residential, commercial & light industrial environments.
BS EN 12101-2:2017 Smoke and heat control systems. Natural smoke and heat exhaust
ventilators
This product has been designed to comply with the requirement of the low voltage safety and
the EMC directives. Failure to follow the instructions may compromise its adherence to this
standard.

Single zone AOV User Manual INTRODUCTION
3
Approved Document Ref: UI-SZAOV-01 Issue 2.01
List of optional functions with requirements:
Product: Single Zone Automatically Open Vent Control Panel
BS EN12101-10: 2005
Intended use: Smoke and heat control systems
Essential Characteristics
Requirement clauses in this European Standard
Operational reliability
6 and 7
Performance parameters under
fire conditions
4.1
Response time
4.1 and 6.2.2

Single Zone AOV User Manual SAFETY
4
Approved Document Ref: UI-SZAOV-01 Issue 2.01
SAFETY
IMPORTANT NOTICE
PLEASE READ THIS MANUAL CAREFULLY BEFORE HANDLING THE EQUIPMENT AND
OBSERVE ALL ADVICE GIVEN WITHIN IT.
THIS PARTICULARLY APPLIES TO THE PRECAUTIONS NECESSARY TO AVOID
ELECTRO-STATIC DISCHARGE
Important Safety Notes
The panel is safe to operate provided it has been installed in compliance with the
manufacturer’s instructions and used in accordance with this manual.
Hazardous voltages are present inside the panel—DO NOT open it unless you are qualified
and authorised to do so. There is no need to open the panel’s enclosure except to carry out
commissioning, maintenance and remedial work. This work must only be carried out by
competent service personnel who are fully conversant with the contents of the panel’s
installation manual and have the necessary skills for maintaining this equipment.
The product must be installed, commissioned and maintained for operation in accordance
with the instructions and the applicable wiring codes of practice and national standard
regulations for fire systems appropriate to the country and location of the installation.
This equipment is designed to be operated from 230VAC 50/60 Hz mains supplies and is of
Class I construction. As such it must be connected to a protective earthing conductor in the
fixed wiring of the installation. Failure to ensure that all conductive accessible parts of this
equipment are adequately bonded to the protective earth will render the equipment unsafe.
Disclaimer
No responsibility can be accepted by the manufacturer or distributors of this fire alarm panel
for any misinterpretation of an instruction or guidance note or for the compliance of the
system as a whole. The manufacturer’s policy is one of continuous improvement and we
reserve the right to make changes to product specifications at our discretion and without
prior notice. E & O E.
Warnings
Before installation, refer to the Ratings shown on the label inside the product
and to the ‘Specifications Chart’ in this document. If you are unclear on any
point, please DO NOT proceed. Contact the manufacturer or supplier for
clarification and guidance.
Only Trained service personnel should undertake the Installation,
Programming and Maintenance of this equipment.
!

Single zone AOV User Manual SAFETY
5
Approved Document Ref: UI-SZAOV-01 Issue 2.01
Cautions
Equipment Guarantee
This product has been manufactured in conformance with the requirements of
all applicable EU Council Directives and is not guaranteed unless the complete
system is installed and commissioned in accordance with the laid down
national standards by an approved and competent person or organisation.
This product has been designed to comply with the requirements of the Low Voltage Safety
and the EMC Directives. Failure to follow the installation instructions may compromise its
adherence to these standards.
Waste Electrical and Electronic Equipment Directive

Single Zone AOV User Manual TABLE OF CONTENTS
6
Approved Document Ref: UI-SZAOV-01 Issue 2.01
TABLE OF CONTENTS
INTRODUCTION ..................................................................................................................2
SAFETY................................................................................................................................4
IMPORTANT NOTICE.......................................................................................................4
Important Safety Notes......................................................................................................4
Disclaimer..........................................................................................................................4
Warnings........................................................................................................................4
Cautions.........................................................................................................................5
TABLE OF CONTENTS........................................................................................................6
PRODUCT OVERVIEW........................................................................................................8
Product codes and features.........................................................................................8
Input and output keys..................................................................................................8
Quiescent and alarm current details for standby battery calculations...........................8
SZAOV Cabinet..............................................................................................................9
Circuit Boards...............................................................................................................10
PCA034 Master PCB.................................................................................................10
PCA02-AOV –LED Display & Controls PCB.............................................................10
PIR/BMS (Plug-in) Card –PIR-0-10-3041-212 (Optional)..........................................10
Technical Specification.................................................................................................11
General Specification ................................................................................................11
Power Supply Specification –PSM3 - 24 (3 Amp).....................................................12
Electrical Specification - Inputs & Outputs.................................................................14
Electrical Specification - Inputs & Outputs.................................................................15
Circuit Description/Function..........................................................................................16
TPCA34 –SZAOV Master Card................................................................................16
PIR/BMS Plug-in Card (2-Way) –PIR-0-10-3041-212 (TPCA029) (Optional)............19
Detector Circuit Conventional System Schematic......................................................21
Detector Circuit Twin Wire System Schematic...........................................................22
INSTALLATION ..................................................................................................................23
Safety..............................................................................................................................23
ESD Precaution............................................................................................................24
Installing the System........................................................................................................24
General ........................................................................................................................24
Environment.................................................................................................................24
Mounting the Cabinet....................................................................................................24
Mains Connections.......................................................................................................25
Connecting the Batteries ..............................................................................................26
Battery Charging Voltage Checks.................................................................................26

Single zone AOV User Manual TABLE OF CONTENTS
7
Approved Document Ref: UI-SZAOV-01 Issue 2.01
SETUP AND PROGRAMMING...........................................................................................27
Twin Wire Mode...............................................................................................................27
DIL Switch Options ..........................................................................................................28
Level 3 Engineering Options............................................................................................29
Clear All Disablements .................................................................................................29
Miscellaneous Program Options...................................................................................30
OPTION 1 (Vent Open LED) Change / Remove Keypad Access Code.....................32
OPTION 2 (Vent Closed LED) Set Motor Opening Time............................................30
OPTION 3 (Vent Open LED and Vent Closed LED) Set Motor Closing Time.............30
OPTION 4 (Input LED) Disable Battery Monitoring....................................................31
OPTION 5 (Detector LED) Disable Muted Tone Beeps .............................................31
Input Circuit Function Settings......................................................................................32
Thermostat Controlled Ventilation Mode.......................................................................34
Type ‘A’ dependency mode ..........................................................................................35
PANEL CONTROLS & INDICATIONS ................................................................................36
Panel Display ...............................................................................................................36
OPERATING ...................................................................................................................36
Activate Controls ..........................................................................................................36
Status LED Indicators................................................................................................37
Keypad......................................................................................................................38
DISABLE MODE...........................................................................................................39
TEST MODE ................................................................................................................40
FUNCTIONALITY DURING A SYSTEM FAULT...........................................................40
SERVICE & MAINTENANCE..............................................................................................41
The Need for Maintenance ...............................................Error! Bookmark not defined.
Duties of the Responsible Person...................................Error! Bookmark not defined.
Routine Maintenance and Testing...................................Error! Bookmark not defined.
Daily................................................................................Error! Bookmark not defined.
Weekly............................................................................Error! Bookmark not defined.
Periodic Inspection and Servicing ...............................Error! Bookmark not defined.
EVERY FOUR YEARS....................................................Error! Bookmark not defined.
SCHEDULE OF TESTING..................................................................................................42

Single zone AOV User Manual PRODUCT OVERVIEW
8
Approved Document Ref: UI-SZAOV-01 Issue 2.01
PRODUCT OVERVIEW
SZAOV is a single zone Automatic Opening Vent control panel. The panel is available with a
3 Amp output, for controlling small loads.
The panel is supplied in a cabinet with space for two 7Ah batteries.
The panel is supplied in a sheet steel enclosure suitable for wall mounting with a hinged,
lockable front access door. The panel can be semi recessed using a suitable recessing
bezel. Cable entry is via 20mm knockouts located at the top and rear of the cabinet.
Different key types are used for the door lock and the ‘activate controls’ key switch. It is also
possible to enable the controls via a 4-digit code entry, if preferred. An eight-button keypad
is used to control the system and allow access to the function options. The three main
buttons, ‘OPEN VENT’ (red), ‘CLOSE VENT’ (blue) & ‘RESET’ (green) being much larger
and colour coded to assist the end users.
The panels are designed to control a single 24VDC motorised vent which uses polarity
reversal to control direction. A 1 Amp output is also provided for the control of magnetic
vents or other purposes.
The power supply of the SZAOV panel is approved to European standards BS EN 12101-10.
The panel has a reliability classification of Re 50.
This product has been designed and manufactured in the United Kingdom.
Product codes and features
Power
Enclosure Size
Batt Capacity
Inputs
Outputs
3 Amp
308W x 260H x
80D
7Ah
A, S, E, F
M, ACT(x1), CA, CF
Input and output keys
Inputs
Outputs
A
Alarm input circuit
M
Magnetic vent
S
Smoke detection circuit
ACT
Actuator
R
Rain sensor
CA
Common alarm contacts
P
PIR sensor
CF
Common fault contacts
E
External control switch
BMS
BMS 0-10v status
F
Fireman override
B
BMS 0-10v control
Quiescent and alarm current details for standby battery calculations
Standby Current
Alarm Current
65mA
106mA

Single zone AOV User Manual PRODUCT OVERVIEW
9
Approved Document Ref: UI-SZAOV-01 Issue 2.01
SZAOV Cabinet

Single zone AOV User Manual PRODUCT OVERVIEW
10
Approved Document Ref: UI-SZAOV-01 Issue 2.01
Circuit Boards
PCA034 Master PCB
PCA02-AOV –LED Display & Controls PCB
PIR/BMS (Plug-in) Card –PIR-0-10-3041-212 (Optional)

Single zone AOV User Manual PRODUCT OVERVIEW
11
Approved Document Ref: UI-SZAOV-01 Issue 2.01
Technical Specification
General Specification
Enclosure
Steel IP30. Epoxy powder coated Interpon Radon, silver
grey
Temperature range:
-5°C to +40°C
Maximum Relative Humidity:
95%
Number of conventional/twin wire
detection circuits
1
Conventional/twin wire detector
compatibility
Apollo: S65, Orbis. / Hochiki CDX. / Nittan EV
Cabling
Fire resistant screened cable, minimum size 1mm2. Max
cable length 1Km (20 Ohm). Fire Burn, FP200 or
equivalent (max capacitance 1uF, max inductance 1
millihenry).
Suitable cable glands must be used
Terminal capacity
0.5mm2to 2.5mm2solid or stranded wire.

Single zone AOV User Manual PRODUCT OVERVIEW
12
Approved Document Ref: UI-SZAOV-01 Issue 2.01
Power Supply Specification –PSM3 - 24 (3 Amp)
Mains supply
230VAC +10% / -15%
50Hz max current 1.2 Amp
Mains supply fuse
4 Amp (F4A 250V)
Not accessible for servicing.
Internal to switched mode power
unit
Power supply rating
3 Amps total including battery
charging
Maximum load shared = 3 Amp
Power supply output
voltage
22 –29.5VDC
Set for batt charge O/P - 29V
Maximum ripple voltage
120mV p-p
Min current supplied by
PSU (Imin)
40mA
Maximum continuous
load for battery standby
ImaxA:
70mA
ImaxB:
2 Amp
Battery size and type
2 x 7Ah 12volt VRLA Yuasa
NP range
Batteries shall comply to BS 62368-1
requirements. Fire rated batteries shall
be used.
Battery charging voltage
27.3VDC nominal
Battery charging output
current
700mA Current limited
Max current drawn from
batteries
3 Amps. Battery fuse 5A HBC
20mm
Battery high impedance
fault (Batt Hi Z)
Resistance > 1 Ohm
1-hour reporting time

Single zone AOV User Manual PRODUCT OVERVIEW
13
Approved Document Ref: UI-SZAOV-01 Issue 2.01
3 AMP Power Supply Module

Single zone AOV User Manual PRODUCT OVERVIEW
14
Approved Document Ref: UI-SZAOV-01 Issue 2.01
Electrical Specification - Inputs & Outputs
TPCA034 Master Card
PSU - - + +
28VDC supply input. Diode
protected for reversal and
independent short circuit
Max input current; 5 amps. Input
voltage 22VDC to 32VDC
DETECTOR - +
Fire alarm zone circuit.
Conventionally wired detection
circuit or Twin Wire combined
detection / sounder circuit.
6K8Ω 5% 0.25W EOL resistor.
Monitoring current limit 50mA,
fused @ 500mA. Typical max load
22 alarm devices @ 18mA each.
OPEN - +
External input to open the vent.
2K7 alarm. 6K8Ω 5% 0.25W EOL
resistor.
Monitoring current limit 1.5mA,
unfused.
CLOSE - +
External input to close the vent.
2K7 alarm. 6K8Ω 5% 0.25W EOL
resistor.
Monitoring current limit 1.5mA,
unfused.
MANUAL CL COM OP
Manual inputs to control the vent
during standby conditions. 2K7
signal. 6K8Ω 5% 0.25W EOL
resistor on each input to COM
Monitoring current limit 3mA for
each input, unfused.
FIREMAN CL COM OP
Fireman inputs to control the vent
during alarm conditions. 2K7
signal. 6K8Ω 5% 0.25W EOL
resistor on each input to COM
Monitoring current limit 3mA for
each input, unfused.
ACT + -
Dual polarity reversal actuator
drive outputs, 28VDC. Max 8A.
Max. inrush current of 20A for 2
seconds
Monitoring current limit 1.5mA.
O/C > 10K, S/C < 10R
Trip current set at 20A for
2 seconds then set at 8A.
AUX + -
Maintained magnetic vent output,
28VDC. Max 1 Amp.
Fused 1 Amp, 20mm glass quick
blow fuse.
FIRE NO NC COM
(Common Fire relay)
Alarm relay contact. Clean C/O.
Max 3A at 30VDC.
Unfused.
FAULT NC NO COM
(Common Fault relay)
Maintained fault relay contact.
Clean C/O Max 3A at 30VDC.
Unfused

Single zone AOV User Manual PRODUCT OVERVIEW
15
Approved Document Ref: UI-SZAOV-01 Issue 2.01
SENSOR + -
Temperature Sensor - 10K at
25degrees.
BATTERY + -
Battery charging output. 27.3VDC
nominal, 700mA current limited
Electrical Specification - Inputs & Outputs
PIR-0-10-3041-212 (TPCA029) - PIR/BMS Plug-in Card
PIR 1 + -
The input requires a 10KΩ
impedance to trigger, with a
6K8Ω 5% 0.25W EOL resistor
Monitoring current limit 14mA,
unfused
BMS 1 (0V IN OUT)
Building Management System
positional voltage input, 10%
steps of motor time.
Max 10VDC, 75KΩ impedance
Rain +/-
Rain sensor signal input. 2K7
alarm. 6K8Ω 5% 0.25W EOL
resistor.
Monitoring current limit 14mA,
unfused
12V +/-
12VDC supply output for PIR
power
12VDC, fused at 100mA resettable
fuse.

Single zone AOV User Manual PRODUCT OVERVIEW
16
Approved Document Ref: UI-SZAOV-01 Issue 2.01
Circuit Description/Function
TPCA34 –SZAOV Master Card
PSU (- - + +)
Monitored 28VDC input from power supply module. Diode protected for reversal and
independent short circuit. Maximum input current, 5 Amps. Input voltage 22 to 32VDC.
DETECTOR (- +)
Conventional / Twin Wire fire alarm zone circuit input (latching by default). Monitored via a
6K8 end of line resistor. Monitoring current limit is 50mA, fused at 500mA. Up to 20
detectors may be used on this circuit. These may use schottky diode bases for detector
removal monitoring, ensuring that if a detector is removed, other devices on the cable are
still functional.
The circuit can be used in ‘Twin Wire’ mode by selection of DIL switch 4 on the main PCB.
This allows use of 24v alarm sounders in reverse polarity on this circuit. Note: In this mode
the detectors require special ‘Sav-Wire’ bases.
An alarm on the detector circuit will activate the vent outputs, in the same way as activation
inputs from the Fireman switch, local vent control switches, or other activation inputs.
Some programming options are available for this circuit, please refer to the programming
and set up section.
OPEN (- +) | CLOSE (- +)
Fused motor drive inputs from an external fire or SZAOV panel, not normally powered (non-
latching by default). Used to force the vent either open or closed, depending on its current
condition, when the external panel goes into an alarm condition.
Alarm activating input; 2K7 alarm, 6K8 Ohm, 5% 0.25W, EOL resistor. Monitoring current
limit 14mA, unfused.
MANUAL (CL COM OP)
Control inputs for manual operation of the vent by a local 3-way control switch. Moves the
vent by 10% increments when activated for less than 3 seconds, otherwise the vent is fully
operated.
•CL –Close vent
•COM - Common reference
•OP –Open vent
These inputs can be configured to also operate as a thermostatic control of the vent.
Replace the 2K7 resistor in the diagram above with a 10K resistor and the vent will open or
close to a pre-configurable position.

Single zone AOV User Manual PRODUCT OVERVIEW
17
Approved Document Ref: UI-SZAOV-01 Issue 2.01
FIREMAN (CP COM OP)
Control input from external 3-way fireman control switch, for manual control of the vent:
•CL Activates the vent output (fully close vent)
•COM Common reference
•OP Activates the vent output (fully open vent)
In default condition, operation of this switch will fully open/close the vent, overriding local
switch settings/vent positions.
Note: If neither input is activated, vent follows panel automatic control.
ACT (+ -)
Dual polarity reversal vent drive actuator outputs - 28VDC, max 8A, protected by a current
trip circuit. Not normally powered. Operated by the inputs from either the main fireman
switch, or the local vent control switch; for a configurable time-period of 10 to 300 seconds.
The default setting is 60 seconds, during configuration of the panel, this should be set to the
time-period required to open/close the vent fully. Polarity is reversed for vent closure.
The resistance of the actuator is monitored. When above 10KΩ it is considered an open
circuit and less than 10Ω it is considered a short circuit. This monitoring is only active when
the actuator is in the fully open or fully closed position. A configuration option allows the
short circuit monitoring to be completely suppressed. This option might not meet the
requirements of local regulations. When used in this mode, connecting resistances of less
than 1Ω can cause damage to the circuitry of the actuator driver.
On commissioning, the vent should be set to the fully closed position prior to connection.
The actuator outputs may be changed to a continuous, maintained operation using DIL
switch 3, ‘ACT POWER’. The control logic can be inverted using DIL switch 1, ‘ACT
INVERT’.

Single zone AOV User Manual PRODUCT OVERVIEW
18
Approved Document Ref: UI-SZAOV-01 Issue 2.01
AUX (+ -)
A maintained magnetic vent 28v output for external magnetically controlled devices.
Switches off to release magnet in the alarm condition. The output can be inverted using DIL
switch 2 ‘AUX INVERT’ on the main PCB.
May also be used as an alternative vent auto close output.
FIRE (NO NC COM)
Common alarm changeover relay contacts, max 3A at 30VDC (unfused). Activates when an
alarm condition exists on the open/close input or detector circuit.
FAULT (NC NO COM)
Common fault signal changeover relay contacts, max 3A at 30VDC (unfused). Normally
energised (failsafe) contacts change-over when any fault is active on the panel or in the
event of total power loss.
SENSOR (+ -)
Connections for battery temperature sensor.
BATTERY (+ -)
Output connections for 7Ah 12Volt batteries charging (temperature compensated). 27.3VDC
output at 20C, Max. charging current: 700mA.

Single zone AOV User Manual PRODUCT OVERVIEW
19
Approved Document Ref: UI-SZAOV-01 Issue 2.01
PIR/BMS Plug-in Card (2-Way) –PIR-0-10-3041-212 (TPCA029) (Optional)
Although the PIR card is designed as a two-way card, when used on the SZAOV panel only
one side of PIR and BMS connectors can be used. This means only one PIR can be fitted in
the system.
PIR 1/PIR 2 (+ -)
The PIR input is available to monitor a typical security type PIR with N/C alarm and tamper
contacts. The PIR requires a 12VDC supply, taken from the boards 12V output. The input
requires a 10KΩ impedance to trigger, with a 6K8Ω 5% 0.25W EOL resistor. Monitoring
current limit is 14mA, unfused.
When operated, the PIR alarm prevents the vent from closing to guard against entrapment
injury. The PIR should be mounted in accordance with the manufacturer’s instructions, to
detect any presence in the vicinity of the entrapment risk.
BMS 1/BMS 2 (0V IN OUT)
Building Management System control interface, using 0-10 volt proportional control signals:
•0V –Common 0V output. This is 0 volts common reference for 0-10V input and
output
•IN –Positional voltage input. Accepts 0-10 volt (DC) signal in 1 volt steps per 10% of
motor time. Vent position is determined by running time, which by default is 60
seconds, i.e. 10% = 6 seconds running time, 50% = 30 seconds etc. Max input is
10VDC, with 75kΩ impedance.
•OUT –Positional voltage output. This output represents the position of the vent in
10% steps of motor run time. Provides feed-back of the 0-10V input status and vent
positional information. Max output is 10VDC 2mA. Max 20KΩ load and 680R
impedance.
RAIN (+ -)
Signal input from wind/rain sensors. Typically, a wind/rain sensor will have a closing contact
alarm signal and may require a 24V supply. The input requires a 2K7Ω impedance to trigger,
with a 6K8Ω 5%0.25W EOL resistor. Monitoring current limit is 14mA, unfused. Any one of
the wind/rain sensors can close a manually opened vent but will not override an alarm signal
input.

Single zone AOV User Manual PRODUCT OVERVIEW
20
Approved Document Ref: UI-SZAOV-01 Issue 2.01
12V (+ -)
12VDC supply output for PIR use. Max continuous rated load 100mA, fused at 100mA
resettable fuse.
This manual suits for next models
2
Table of contents
Other Haes Control Panel manuals

Haes
Haes AOV Series Guide

Haes
Haes AlarmSense Guide

Haes
Haes ELAN HS-5000 Series User manual

Haes
Haes ESPRIT-G Guide

Haes
Haes Esento Eclipse ECL-2 Guide

Haes
Haes ELAN HS-5100 User manual

Haes
Haes Excel-32 Series User manual

Haes
Haes FUSION 0832-CPD-1431 User manual

Haes
Haes ESENTO MARINE Guide

Haes
Haes ESENTO ESEN-8MAR Guide