Voltex SAS135MH User manual

SAS135MH SMOKE ALARM
INSTALLATION MANUAL
AS 3786 2014
Congratulations on purchasing a Voltex Smoke Alarm.
Please read these instructions carefully before installation
and operation.
Sensing Type Photoelectric (Type A - contains no
radioactive material)
Power Supply
220-240V AC 50Hz
Replaceable DC 3V battery: Pairdeer/
Huiderui CR17450
Interconnectivity Hard Wired
Battery life 10 year backup Lithium
Wireless Option Wireless Module SASWM
Interconnection
Maximum 24 paired alarms
Max wiring length between first
and last alarm: 150 m
Size Φ135mm x 45mm
Temp range 0°C - 45°C
Max Humidity 93%RH
"Alarm Signal
Pattern" ISO 8201
Alarm Volume 85dB at 3m
Hush Time 10 mins
Compliance AS 3786: 2014
Certification CSIRO Verification Service
Important Safety Information
Nuisance Alarms
System Interconnection
Installation Procedure
Buttons and Indicators
Wiring Diagram
∫This Voltex Smoke Alarm is designed for use in dwellings and
shall be installed by a licensed electrician. It is intended to
detect smoke before it reaches the occupants of a building.
The ensuing alarm is designed to wake the occupants and
give them time to evacuate the building.
∫This smoke alarm SHALL be installed in accordance with
national and local council building regulations and the latest
edition of the Australian and New Zealand wiring Rules AS/
NZS 3000. A simplified, by State, installation requirements
guide is available on Voltex’s website.
∫ALL ELECTRICAL WORK MUST BE CARRIED BY A LISCENSED
ELECTRICAL CONTRACTOR OR ELECTRICIAN.
Recommended Installation Locations
∫At least one smoke alarm shall be fitted on each storey
(including basements) - in each bedroom and in corridors
or hallways which connect bedrooms and the rest of the
dwelling or as required by relevant local legislation.
∫Where practicable smoke alarms should be placed on the
ceiling.
∫It is important to install the smoke alarm in the centre of the
room, avoiding dead air spaces (an area in which trapped
hot air will prevent smoke from reaching the alarm). Smoke
alarms must not be placed within:
∫Smoke alarms must be paired (interconnected) with every
other smoke alarm so they all activate together.
∫300mm of a corner of a ceiling and a wall
∫300mm of a light fitting
∫400mm of an air-conditioning vent
∫400mm of the blades of a ceiling fan
Where it is not possible to place the alarm on the ceiling, the
smoke alarm may be installed on the wall at a minimum of
300mm and a maximum of 500mm off the ceiling at the junction
of the wall.
There are special requirements for stairways, sloping ceilings
and ceilings with exposed beams. Specific requirements are
explained in the relevant Building Regulation.
To reduce the likelihood of nuisance alarms, it is preferable
that smoke alarms are not located near cooking appliances,
bathrooms or laundries
WARNING: DO NOT CONNECT INTERCONNECTION WIRE TO ACTIVE,
NEUTRAL OR EARTH
NOTE: ONLY VOLTEX SMOKE ALAMRS CAN BE INTERCONNECTED
TO EACH OTHER
If more than one smoke alarm is installed all units shall be
interconnected or paired.
Interconnection can be achieved either by wiring the I-Connect
terminals of the alarms together or pairing using the optional
wireless module (not included).
The smoke alarm can be paired with Voltex Battery Smoke
Alarm type SAS115BW when fitted with a Wireless Module (not
included), Voltex Part number SASWM. See SASWM instructions
for pairing procedure.
The smoke alarm should not use both wireless and hardwired
interconnections. The interconnection will not function
if both are used at the same time.
NOTE:
1. Interconnection wire shall be no less than 1.5mm2 and shall
be SDI cable
2. Smoke alarms which are interconnected using hard wiring
must be on the same circuit.
1. Select an appropriate location and facilitate necessary
wiring.
2. Isolate the power supply and wire the appropriate power
terminals on the back of the smoke alarm.
3. Wire the interconnecting cable or insert the Voltex Wireless
Module (Part number SASWM) into the smoke alarm.
4. Mount the smoke alarm in the ceiling with the supplied
fixings and clip the smoke alarm shut.
5. Apply power to the smoke alarm unit. A green LED indicates
power is available.
6. Remove the battery isolation strip to connect battery.
7. Test the smoke alarm by pressing and holding the test
button. If installed correctly and unit is functioning properly,
an alarm should sound. If multiple alarms are installed, test
the interconnection on all alarms.
Terminal cover is supplied temperately in accessory bag,
make sure the terminal cover is installed after wiring.
Notes:
A
E-Loop
N
I-Connect
I-Connect
N
E-Loop
A
:
:
:
:
Interconnection
Neutral
Loop
Active
TERMINAL
A
E-Loop
N
I-Connect
A
E-Loop
N
I-Connect
A
E-Loop
N
I-Connect
Active
220-240 V a.c. Interconnection
Neutral
II210720-AZ

SAS135MH SMOKE ALARM
INSTALLATION MANUAL
AS 3786 2014
Congratulations on purchasing a Voltex Smoke Alarm.
Please read these instructions carefully before installation
and operation.
Sensing Type Photoelectric (Type A - contains no
radioactive material)
Power Supply
220-240V AC 50Hz
Replaceable DC 3V battery: Pairdeer/
Huiderui CR17450
Interconnectivity Hard Wired
Battery life 10 year backup Lithium
Wireless Option Wireless Module SASWM
Interconnection
Maximum 24 paired alarms
Max wiring length between first
and last alarm: 150 m
Size Φ135mm x 45mm
Temp range 0°C - 45°C
Max Humidity 93%RH
"Alarm Signal
Pattern" ISO 8201
Alarm Volume 85dB at 3m
Hush Time 10 mins
Compliance AS 3786: 2014
Certification CSIRO Verification Service
Important Safety Information
Nuisance Alarms
System Interconnection
Installation Procedure
Buttons and Indicators
Wiring Diagram
∫This Voltex Smoke Alarm is designed for use in dwellings and
shall be installed by a licensed electrician. It is intended to
detect smoke before it reaches the occupants of a building.
The ensuing alarm is designed to wake the occupants and
give them time to evacuate the building.
∫This smoke alarm SHALL be installed in accordance with
national and local council building regulations and the latest
edition of the Australian and New Zealand wiring Rules AS/
NZS 3000. A simplified, by State, installation requirements
guide is available on Voltex’s website.
∫ALL ELECTRICAL WORK MUST BE CARRIED BY A LISCENSED
ELECTRICAL CONTRACTOR OR ELECTRICIAN.
Recommended Installation Locations
∫At least one smoke alarm shall be fitted on each storey
(including basements) - in each bedroom and in corridors
or hallways which connect bedrooms and the rest of the
dwelling or as required by relevant local legislation.
∫Where practicable smoke alarms should be placed on the
ceiling.
∫It is important to install the smoke alarm in the centre of the
room, avoiding dead air spaces (an area in which trapped
hot air will prevent smoke from reaching the alarm). Smoke
alarms must not be placed within:
∫Smoke alarms must be paired (interconnected) with every
other smoke alarm so they all activate together.
∫300mm of a corner of a ceiling and a wall
∫300mm of a light fitting
∫400mm of an air-conditioning vent
∫400mm of the blades of a ceiling fan
Where it is not possible to place the alarm on the ceiling, the
smoke alarm may be installed on the wall at a minimum of
300mm and a maximum of 500mm off the ceiling at the junction
of the wall.
There are special requirements for stairways, sloping ceilings
and ceilings with exposed beams. Specific requirements are
explained in the relevant Building Regulation.
To reduce the likelihood of nuisance alarms, it is preferable
that smoke alarms are not located near cooking appliances,
bathrooms or laundries
WARNING: DO NOT CONNECT INTERCONNECTION WIRE TO ACTIVE,
NEUTRAL OR EARTH
NOTE: ONLY VOLTEX SMOKE ALAMRS CAN BE INTERCONNECTED
TO EACH OTHER
If more than one smoke alarm is installed all units shall be
interconnected or paired.
Interconnection can be achieved either by wiring the I-Connect
terminals of the alarms together or pairing using the optional
wireless module (not included).
The smoke alarm can be paired with Voltex Battery Smoke
Alarm type SAS115BW when fitted with a Wireless Module (not
included), Voltex Part number SASWM. See SASWM instructions
for pairing procedure.
The smoke alarm should not use both wireless and hardwired
interconnections. The interconnection will not function
if both are used at the same time.
NOTE:
1. Interconnection wire shall be no less than 1.5mm2 and shall
be SDI cable
2. Smoke alarms which are interconnected using hard wiring
must be on the same circuit.
1. Select an appropriate location and facilitate necessary
wiring.
2. Isolate the power supply and wire the appropriate power
terminals on the back of the smoke alarm.
3. Wire the interconnecting cable or insert the Voltex Wireless
Module (Part number SASWM) into the smoke alarm.
4. Mount the smoke alarm in the ceiling with the supplied
fixings and clip the smoke alarm shut.
5. Apply power to the smoke alarm unit. A green LED indicates
power is available.
6. Remove the battery isolation strip to connect battery.
7. Test the smoke alarm by pressing and holding the test
button. If installed correctly and unit is functioning properly,
an alarm should sound. If multiple alarms are installed, test
the interconnection on all alarms.
Terminal cover is supplied temperately in accessory bag,
make sure the terminal cover is installed after wiring.
Notes:
A
E-Loop
N
I-Connect
I-Connect
N
E-Loop
A
:
:
:
:
Interconnection
Neutral
Loop
Active
TERMINAL
A
E-Loop
N
I-Connect
A
E-Loop
N
I-Connect
A
E-Loop
N
I-Connect
Active
220-240 V a.c. Interconnection
Neutral
II210720-AZ

SAS135MH SMOKE ALARM
INSTALLATION MANUAL
AS 3786 2014
Congratulations on purchasing a Voltex Smoke Alarm.
Please read these instructions carefully before installation
and operation.
Sensing Type Photoelectric (Type A - contains no
radioactive material)
Power Supply
220-240V AC 50Hz
Replaceable DC 3V battery: Pairdeer/
Huiderui CR17450
Interconnectivity Hard Wired
Battery life 10 year backup Lithium
Wireless Option Wireless Module SASWM
Interconnection
Maximum 24 paired alarms
Max wiring length between first
and last alarm: 150 m
Size Φ135mm x 45mm
Temp range 0°C - 45°C
Max Humidity 93%RH
"Alarm Signal
Pattern" ISO 8201
Alarm Volume 85dB at 3m
Hush Time 10 mins
Compliance AS 3786: 2014
Certification CSIRO Verification Service
Important Safety Information
Nuisance Alarms
System Interconnection
Installation Procedure
Buttons and Indicators
Wiring Diagram
∫This Voltex Smoke Alarm is designed for use in dwellings and
shall be installed by a licensed electrician. It is intended to
detect smoke before it reaches the occupants of a building.
The ensuing alarm is designed to wake the occupants and
give them time to evacuate the building.
∫This smoke alarm SHALL be installed in accordance with
national and local council building regulations and the latest
edition of the Australian and New Zealand wiring Rules AS/
NZS 3000. A simplified, by State, installation requirements
guide is available on Voltex’s website.
∫ALL ELECTRICAL WORK MUST BE CARRIED BY A LISCENSED
ELECTRICAL CONTRACTOR OR ELECTRICIAN.
Recommended Installation Locations
∫At least one smoke alarm shall be fitted on each storey
(including basements) - in each bedroom and in corridors
or hallways which connect bedrooms and the rest of the
dwelling or as required by relevant local legislation.
∫Where practicable smoke alarms should be placed on the
ceiling.
∫It is important to install the smoke alarm in the centre of the
room, avoiding dead air spaces (an area in which trapped
hot air will prevent smoke from reaching the alarm). Smoke
alarms must not be placed within:
∫Smoke alarms must be paired (interconnected) with every
other smoke alarm so they all activate together.
∫300mm of a corner of a ceiling and a wall
∫300mm of a light fitting
∫400mm of an air-conditioning vent
∫400mm of the blades of a ceiling fan
Where it is not possible to place the alarm on the ceiling, the
smoke alarm may be installed on the wall at a minimum of
300mm and a maximum of 500mm off the ceiling at the junction
of the wall.
There are special requirements for stairways, sloping ceilings
and ceilings with exposed beams. Specific requirements are
explained in the relevant Building Regulation.
To reduce the likelihood of nuisance alarms, it is preferable
that smoke alarms are not located near cooking appliances,
bathrooms or laundries
WARNING: DO NOT CONNECT INTERCONNECTION WIRE TO ACTIVE,
NEUTRAL OR EARTH
NOTE: ONLY VOLTEX SMOKE ALAMRS CAN BE INTERCONNECTED
TO EACH OTHER
If more than one smoke alarm is installed all units shall be
interconnected or paired.
Interconnection can be achieved either by wiring the I-Connect
terminals of the alarms together or pairing using the optional
wireless module (not included).
The smoke alarm can be paired with Voltex Battery Smoke
Alarm type SAS115BW when fitted with a Wireless Module (not
included), Voltex Part number SASWM. See SASWM instructions
for pairing procedure.
The smoke alarm should not use both wireless and hardwired
interconnections. The interconnection will not function
if both are used at the same time.
NOTE:
1. Interconnection wire shall be no less than 1.5mm2 and shall
be SDI cable
2. Smoke alarms which are interconnected using hard wiring
must be on the same circuit.
1. Select an appropriate location and facilitate necessary
wiring.
2. Isolate the power supply and wire the appropriate power
terminals on the back of the smoke alarm.
3. Wire the interconnecting cable or insert the Voltex Wireless
Module (Part number SASWM) into the smoke alarm.
4. Mount the smoke alarm in the ceiling with the supplied
fixings and clip the smoke alarm shut.
5. Apply power to the smoke alarm unit. A green LED indicates
power is available.
6. Remove the battery isolation strip to connect battery.
7. Test the smoke alarm by pressing and holding the test
button. If installed correctly and unit is functioning properly,
an alarm should sound. If multiple alarms are installed, test
the interconnection on all alarms.
Terminal cover is supplied temperately in accessory bag,
make sure the terminal cover is installed after wiring.
Notes:
A
E-Loop
N
I-Connect
I-Connect
N
E-Loop
A
:
:
:
:
Interconnection
Neutral
Loop
Active
TERMINAL
A
E-Loop
N
I-Connect
A
E-Loop
N
I-Connect
A
E-Loop
N
I-Connect
Active
220-240 V a.c. Interconnection
Neutral
II210720-AZ

SAS135MH SMOKE ALARM
INSTALLATION MANUAL
AS 3786 2014
Congratulations on purchasing a Voltex Smoke Alarm.
Please read these instructions carefully before installation
and operation.
Sensing Type Photoelectric (Type A - contains no
radioactive material)
Power Supply
220-240V AC 50Hz
Replaceable DC 3V battery: Pairdeer/
Huiderui CR17450
Interconnectivity Hard Wired
Battery life 10 year backup Lithium
Wireless Option Wireless Module SASWM
Interconnection
Maximum 24 paired alarms
Max wiring length between first
and last alarm: 150 m
Size Φ135mm x 45mm
Temp range 0°C - 45°C
Max Humidity 93%RH
"Alarm Signal
Pattern" ISO 8201
Alarm Volume 85dB at 3m
Hush Time 10 mins
Compliance AS 3786: 2014
Certification CSIRO Verification Service
Important Safety Information
Nuisance Alarms
System Interconnection
Installation Procedure
Buttons and Indicators
Wiring Diagram
∫This Voltex Smoke Alarm is designed for use in dwellings and
shall be installed by a licensed electrician. It is intended to
detect smoke before it reaches the occupants of a building.
The ensuing alarm is designed to wake the occupants and
give them time to evacuate the building.
∫This smoke alarm SHALL be installed in accordance with
national and local council building regulations and the latest
edition of the Australian and New Zealand wiring Rules AS/
NZS 3000. A simplified, by State, installation requirements
guide is available on Voltex’s website.
∫ALL ELECTRICAL WORK MUST BE CARRIED BY A LISCENSED
ELECTRICAL CONTRACTOR OR ELECTRICIAN.
Recommended Installation Locations
∫At least one smoke alarm shall be fitted on each storey
(including basements) - in each bedroom and in corridors
or hallways which connect bedrooms and the rest of the
dwelling or as required by relevant local legislation.
∫Where practicable smoke alarms should be placed on the
ceiling.
∫It is important to install the smoke alarm in the centre of the
room, avoiding dead air spaces (an area in which trapped
hot air will prevent smoke from reaching the alarm). Smoke
alarms must not be placed within:
∫Smoke alarms must be paired (interconnected) with every
other smoke alarm so they all activate together.
∫300mm of a corner of a ceiling and a wall
∫300mm of a light fitting
∫400mm of an air-conditioning vent
∫400mm of the blades of a ceiling fan
Where it is not possible to place the alarm on the ceiling, the
smoke alarm may be installed on the wall at a minimum of
300mm and a maximum of 500mm off the ceiling at the junction
of the wall.
There are special requirements for stairways, sloping ceilings
and ceilings with exposed beams. Specific requirements are
explained in the relevant Building Regulation.
To reduce the likelihood of nuisance alarms, it is preferable
that smoke alarms are not located near cooking appliances,
bathrooms or laundries
WARNING: DO NOT CONNECT INTERCONNECTION WIRE TO ACTIVE,
NEUTRAL OR EARTH
NOTE: ONLY VOLTEX SMOKE ALAMRS CAN BE INTERCONNECTED
TO EACH OTHER
If more than one smoke alarm is installed all units shall be
interconnected or paired.
Interconnection can be achieved either by wiring the I-Connect
terminals of the alarms together or pairing using the optional
wireless module (not included).
The smoke alarm can be paired with Voltex Battery Smoke
Alarm type SAS115BW when fitted with a Wireless Module (not
included), Voltex Part number SASWM. See SASWM instructions
for pairing procedure.
The smoke alarm should not use both wireless and hardwired
interconnections. The interconnection will not function
if both are used at the same time.
NOTE:
1. Interconnection wire shall be no less than 1.5mm2 and shall
be SDI cable
2. Smoke alarms which are interconnected using hard wiring
must be on the same circuit.
1. Select an appropriate location and facilitate necessary
wiring.
2. Isolate the power supply and wire the appropriate power
terminals on the back of the smoke alarm.
3. Wire the interconnecting cable or insert the Voltex Wireless
Module (Part number SASWM) into the smoke alarm.
4. Mount the smoke alarm in the ceiling with the supplied
fixings and clip the smoke alarm shut.
5. Apply power to the smoke alarm unit. A green LED indicates
power is available.
6. Remove the battery isolation strip to connect battery.
7. Test the smoke alarm by pressing and holding the test
button. If installed correctly and unit is functioning properly,
an alarm should sound. If multiple alarms are installed, test
the interconnection on all alarms.
Terminal cover is supplied temperately in accessory bag,
make sure the terminal cover is installed after wiring.
Notes:
A
E-Loop
N
I-Connect
I-Connect
N
E-Loop
A
:
:
:
:
Interconnection
Neutral
Loop
Active
TERMINAL
A
E-Loop
N
I-Connect
A
E-Loop
N
I-Connect
A
E-Loop
N
I-Connect
Active
220-240 V a.c. Interconnection
Neutral
II210720-AZ

SAS135MH SMOKE ALARM
INSTALLATION MANUAL
AS 3786 2014
Congratulations on purchasing a Voltex Smoke Alarm.
Please read these instructions carefully before installation
and operation.
Sensing Type Photoelectric (Type A - contains no
radioactive material)
Power Supply
220-240V AC 50Hz
Replaceable DC 3V battery: Pairdeer/
Huiderui CR17450
Interconnectivity Hard Wired
Battery life 10 year backup Lithium
Wireless Option Wireless Module SASWM
Interconnection
Maximum 24 paired alarms
Max wiring length between first
and last alarm: 150 m
Size Φ135mm x 45mm
Temp range 0°C - 45°C
Max Humidity 93%RH
"Alarm Signal
Pattern" ISO 8201
Alarm Volume 85dB at 3m
Hush Time 10 mins
Compliance AS 3786: 2014
Certification CSIRO Verification Service
Important Safety Information
Nuisance Alarms
System Interconnection
Installation Procedure
Buttons and Indicators
Wiring Diagram
∫This Voltex Smoke Alarm is designed for use in dwellings and
shall be installed by a licensed electrician. It is intended to
detect smoke before it reaches the occupants of a building.
The ensuing alarm is designed to wake the occupants and
give them time to evacuate the building.
∫This smoke alarm SHALL be installed in accordance with
national and local council building regulations and the latest
edition of the Australian and New Zealand wiring Rules AS/
NZS 3000. A simplified, by State, installation requirements
guide is available on Voltex’s website.
∫ALL ELECTRICAL WORK MUST BE CARRIED BY A LISCENSED
ELECTRICAL CONTRACTOR OR ELECTRICIAN.
Recommended Installation Locations
∫At least one smoke alarm shall be fitted on each storey
(including basements) - in each bedroom and in corridors
or hallways which connect bedrooms and the rest of the
dwelling or as required by relevant local legislation.
∫Where practicable smoke alarms should be placed on the
ceiling.
∫It is important to install the smoke alarm in the centre of the
room, avoiding dead air spaces (an area in which trapped
hot air will prevent smoke from reaching the alarm). Smoke
alarms must not be placed within:
∫Smoke alarms must be paired (interconnected) with every
other smoke alarm so they all activate together.
∫300mm of a corner of a ceiling and a wall
∫300mm of a light fitting
∫400mm of an air-conditioning vent
∫400mm of the blades of a ceiling fan
Where it is not possible to place the alarm on the ceiling, the
smoke alarm may be installed on the wall at a minimum of
300mm and a maximum of 500mm off the ceiling at the junction
of the wall.
There are special requirements for stairways, sloping ceilings
and ceilings with exposed beams. Specific requirements are
explained in the relevant Building Regulation.
To reduce the likelihood of nuisance alarms, it is preferable
that smoke alarms are not located near cooking appliances,
bathrooms or laundries
WARNING: DO NOT CONNECT INTERCONNECTION WIRE TO ACTIVE,
NEUTRAL OR EARTH
NOTE: ONLY VOLTEX SMOKE ALAMRS CAN BE INTERCONNECTED
TO EACH OTHER
If more than one smoke alarm is installed all units shall be
interconnected or paired.
Interconnection can be achieved either by wiring the I-Connect
terminals of the alarms together or pairing using the optional
wireless module (not included).
The smoke alarm can be paired with Voltex Battery Smoke
Alarm type SAS115BW when fitted with a Wireless Module (not
included), Voltex Part number SASWM. See SASWM instructions
for pairing procedure.
The smoke alarm should not use both wireless and hardwired
interconnections. The interconnection will not function
if both are used at the same time.
NOTE:
1. Interconnection wire shall be no less than 1.5mm2 and shall
be SDI cable
2. Smoke alarms which are interconnected using hard wiring
must be on the same circuit.
1. Select an appropriate location and facilitate necessary
wiring.
2. Isolate the power supply and wire the appropriate power
terminals on the back of the smoke alarm.
3. Wire the interconnecting cable or insert the Voltex Wireless
Module (Part number SASWM) into the smoke alarm.
4. Mount the smoke alarm in the ceiling with the supplied
fixings and clip the smoke alarm shut.
5. Apply power to the smoke alarm unit. A green LED indicates
power is available.
6. Remove the battery isolation strip to connect battery.
7. Test the smoke alarm by pressing and holding the test
button. If installed correctly and unit is functioning properly,
an alarm should sound. If multiple alarms are installed, test
the interconnection on all alarms.
Terminal cover is supplied temperately in accessory bag,
make sure the terminal cover is installed after wiring.
Notes:
A
E-Loop
N
I-Connect
I-Connect
N
E-Loop
A
:
:
:
:
Interconnection
Neutral
Loop
Active
TERMINAL
A
E-Loop
N
I-Connect
A
E-Loop
N
I-Connect
A
E-Loop
N
I-Connect
Active
220-240 V a.c. Interconnection
Neutral
II210720-AZ

In the event of an alarm condition, pressing the HUSH button
on the alarm unit will silence the alarm for approximately 10
minutes.
NOTE: Where multiple alarms are interconnected, the HUSH
function WILL NOT OPERATE EXCEPT ON THE UNIT THAT THE
ALARM WAS TRIGGERED FROM. The triggered unit can be
identified by the RED LED flashing.
Do Not Disturb Mode
When the unit indicates a low battery alarm or internal fault,
pushing the HUSH button will silence the alarm for 10 hours
and the red LED will flash every 40 seconds.
¬
The smoke alarm incorporates a replaceable battery
(CR17450) which is designed to power the smoke alarm
in the event of a short-term power outage. The battery is
designed to last 10 years subject to normal use and regular
maintenance from the date of manufacture and can be
replaced by opening the smoke alarm and accessing the
battery under the battery cover
¬Periodically apply the Test Procedure to test the alarm.
¬Smoke Alarm are prone to dust and insect ingress which can
cause false alarm, it is prudent to clean the smoke alarm
periodically. The Smoke Alarm must be kept clean so that
excess dust does not build up. Any insects or cobwebs in the
vicinity of the Smoke Alarm should be promptly removed.
Vacuum the outside of the Smoke Alarm to remove any dust
build up.
¬
Do not spray any cleaning liquids directly onto the smoke alarm.
Replace the battery
Audio and Visual Indication System Configuration
Trouble Shooting
Alarm Memory
Warranty Information
Maintenance
Test Procedures For Hardwired Interconnection
HUSH Mode
1. Ensure the green LED is continuously illuminated on each
unit, this indicates 240V mains AC power is available.
2.
Pressing and holding the test button on any smoke
alarm for at least 5 seconds will activate an alarm and
cause the red LED on the front face to flash.
(Note: all other interconnected smoke alarms will stop
alarming when releasing the Test button, but the red LED
will flash for 3 minutes.
3. Repeat this procedure for each alarm.
*Continuous alarm pattern: Beep 0.5s- Pause 0.5s- Beep
0.5s- Pause 0.5s-Beep 0.5s- Pause 1.5s repeatedly per ISO
8201 Smoke is detected, and the building must be vacated
immediately. Emergency services must be notified.
NOTE: If self-test fault warning is existing, but the product
can sound alarm when press the test button. The product can
continue to be used. Need to test weekly by press the test button
instead of self-test weekly.
Problem Solution
Green LED not lit Check mains power connection
Hard wire paired
smokes don't
alarm during test
Check if Smoke Alarms are in same
circuit, interconnect cable is corrected
firmly and mains power is connected.
Wireless
interconnected
smoke alarms
don't alarm
during test
Clean the wireless paired smoke alarm per
instruction and repair.
Alarms sound
for no apparent
reason
Check for fumes, steam, etc. from the
kitchen or bathroom. Paint and other
fumes can cause nuisance alarms. Check
for any sign of contamination such as
cobwebs or dust. Clean the alarm.
Press the local Hush button to silent the
Smoke Alarm triggered, identify the alarm
that triggered by the flashing red LED
(alarm will not silence if it does not have a
flashing red LED)
If cannot hush the smoke alarm, push
the button located on the side and open
the Smoke Alarm, take off the battery.
Contact Voltex.
Chirp every 40
seconds and
cannot hush
Check if battery has been installed firmly,
contact Voltex
Dust and insect
Contamination
Vacuum the outside of the Smoke Alarm
to remove any dust build up. Smoke Alarm
are prone to dust and insect ingress which
can cause false alarm, it is prudent to
clean the smoke alarm periodically.
OPERATION MODE RED LED STATUS SOUND
Power Up Flash
No beep for
no wireless
interconnection.
No beep for
hard wired
interconnection.
Beep once when
wireless module is
installed & paired.
Beep 3 times when
wireless module is
installed but NOT
paired.
Alarm functioning
correctly
(standby)
Low intensity
flash every 40
seconds
-
Low battery
warning
Flash every 40
seconds
One chirp every 40
seconds.
Press HUSH button
enter ‘Do Not
Disturb’ Mode for 10
hours.
Fault warning Flash every 40
second
One chirp every
40 seconds. Press
HUSH button enter
‘Do Not Disturb’
Mode for 10 hours.
Self-test fault
warning
Flashes twice
every 40
seconds
-
HUSH mode
Flash once every
8 seconds for 10
min
-
Do not Disturb
Flash once very
40 seconds for
10 hours
-
Smoke detected
on local alarm*
Flash every
second
Continuous alarm
signal pattern,
Press HUSH button
to enter Silent Mode
for 10 min
Smoke detected
on interconnected
or paired unit
-
Continuous alarm
signal pattern,
Press HUSH button
to enter Silent Mode
for 10 min
Test function Flash every
second
Continuous alarm
signal pattern
until TEST button
released
Weekly self-test Flash once Chirps once every
week
End of Life (10
year) Warning
Flashes twice
every 40
seconds
Chips every 40
seconds
Cannot enter ‘Do
Not Disturb’ Mode.
Voltex warrants this accessory against defective workmanship
and faulty materials for seven (7) years from the original date of
purchase.
In an interconnected group, only the LED on the triggered alarm
flashes once approximately every 20 seconds for 72 hours. This
can be used to identify the triggered unit.
© Voltex Electrical 2020. All Rights Reserved.
CONFIG 1
Hardwire Interconnect Only, 1 Circuit
CONFIG 2
Hardwire & Wireless Interconnect, 1 Circuit
CONFIG 3
Wireless Interconnect Only, 2 Circuits
NOT ALLOWED

In the event of an alarm condition, pressing the HUSH button
on the alarm unit will silence the alarm for approximately 10
minutes.
NOTE: Where multiple alarms are interconnected, the HUSH
function WILL NOT OPERATE EXCEPT ON THE UNIT THAT THE
ALARM WAS TRIGGERED FROM. The triggered unit can be
identified by the RED LED flashing.
Do Not Disturb Mode
When the unit indicates a low battery alarm or internal fault,
pushing the HUSH button will silence the alarm for 10 hours
and the red LED will flash every 40 seconds.
¬
The smoke alarm incorporates a replaceable battery
(CR17450) which is designed to power the smoke alarm
in the event of a short-term power outage. The battery is
designed to last 10 years subject to normal use and regular
maintenance from the date of manufacture and can be
replaced by opening the smoke alarm and accessing the
battery under the battery cover
¬Periodically apply the Test Procedure to test the alarm.
¬Smoke Alarm are prone to dust and insect ingress which can
cause false alarm, it is prudent to clean the smoke alarm
periodically. The Smoke Alarm must be kept clean so that
excess dust does not build up. Any insects or cobwebs in the
vicinity of the Smoke Alarm should be promptly removed.
Vacuum the outside of the Smoke Alarm to remove any dust
build up.
¬
Do not spray any cleaning liquids directly onto the smoke alarm.
Replace the battery
Audio and Visual Indication System Configuration
Trouble Shooting
Alarm Memory
Warranty Information
Maintenance
Test Procedures For Hardwired Interconnection
HUSH Mode
1. Ensure the green LED is continuously illuminated on each
unit, this indicates 240V mains AC power is available.
2.
Pressing and holding the test button on any smoke
alarm for at least 5 seconds will activate an alarm and
cause the red LED on the front face to flash.
(Note: all other interconnected smoke alarms will stop
alarming when releasing the Test button, but the red LED
will flash for 3 minutes.
3. Repeat this procedure for each alarm.
*Continuous alarm pattern: Beep 0.5s- Pause 0.5s- Beep
0.5s- Pause 0.5s-Beep 0.5s- Pause 1.5s repeatedly per ISO
8201 Smoke is detected, and the building must be vacated
immediately. Emergency services must be notified.
NOTE: If self-test fault warning is existing, but the product
can sound alarm when press the test button. The product can
continue to be used. Need to test weekly by press the test button
instead of self-test weekly.
Problem Solution
Green LED not lit Check mains power connection
Hard wire paired
smokes don't
alarm during test
Check if Smoke Alarms are in same
circuit, interconnect cable is corrected
firmly and mains power is connected.
Wireless
interconnected
smoke alarms
don't alarm
during test
Clean the wireless paired smoke alarm per
instruction and repair.
Alarms sound
for no apparent
reason
Check for fumes, steam, etc. from the
kitchen or bathroom. Paint and other
fumes can cause nuisance alarms. Check
for any sign of contamination such as
cobwebs or dust. Clean the alarm.
Press the local Hush button to silent the
Smoke Alarm triggered, identify the alarm
that triggered by the flashing red LED
(alarm will not silence if it does not have a
flashing red LED)
If cannot hush the smoke alarm, push
the button located on the side and open
the Smoke Alarm, take off the battery.
Contact Voltex.
Chirp every 40
seconds and
cannot hush
Check if battery has been installed firmly,
contact Voltex
Dust and insect
Contamination
Vacuum the outside of the Smoke Alarm
to remove any dust build up. Smoke Alarm
are prone to dust and insect ingress which
can cause false alarm, it is prudent to
clean the smoke alarm periodically.
OPERATION MODE RED LED STATUS SOUND
Power Up Flash
No beep for
no wireless
interconnection.
No beep for
hard wired
interconnection.
Beep once when
wireless module is
installed & paired.
Beep 3 times when
wireless module is
installed but NOT
paired.
Alarm functioning
correctly
(standby)
Low intensity
flash every 40
seconds
-
Low battery
warning
Flash every 40
seconds
One chirp every 40
seconds.
Press HUSH button
enter ‘Do Not
Disturb’ Mode for 10
hours.
Fault warning Flash every 40
second
One chirp every
40 seconds. Press
HUSH button enter
‘Do Not Disturb’
Mode for 10 hours.
Self-test fault
warning
Flashes twice
every 40
seconds
-
HUSH mode
Flash once every
8 seconds for 10
min
-
Do not Disturb
Flash once very
40 seconds for
10 hours
-
Smoke detected
on local alarm*
Flash every
second
Continuous alarm
signal pattern,
Press HUSH button
to enter Silent Mode
for 10 min
Smoke detected
on interconnected
or paired unit
-
Continuous alarm
signal pattern,
Press HUSH button
to enter Silent Mode
for 10 min
Test function Flash every
second
Continuous alarm
signal pattern
until TEST button
released
Weekly self-test Flash once Chirps once every
week
End of Life (10
year) Warning
Flashes twice
every 40
seconds
Chips every 40
seconds
Cannot enter ‘Do
Not Disturb’ Mode.
Voltex warrants this accessory against defective workmanship
and faulty materials for seven (7) years from the original date of
purchase.
In an interconnected group, only the LED on the triggered alarm
flashes once approximately every 20 seconds for 72 hours. This
can be used to identify the triggered unit.
© Voltex Electrical 2020. All Rights Reserved.
CONFIG 1
Hardwire Interconnect Only, 1 Circuit
CONFIG 2
Hardwire & Wireless Interconnect, 1 Circuit
CONFIG 3
Wireless Interconnect Only, 2 Circuits
NOT ALLOWED

In the event of an alarm condition, pressing the HUSH button
on the alarm unit will silence the alarm for approximately 10
minutes.
NOTE: Where multiple alarms are interconnected, the HUSH
function WILL NOT OPERATE EXCEPT ON THE UNIT THAT THE
ALARM WAS TRIGGERED FROM. The triggered unit can be
identified by the RED LED flashing.
Do Not Disturb Mode
When the unit indicates a low battery alarm or internal fault,
pushing the HUSH button will silence the alarm for 10 hours
and the red LED will flash every 40 seconds.
¬
The smoke alarm incorporates a replaceable battery
(CR17450) which is designed to power the smoke alarm
in the event of a short-term power outage. The battery is
designed to last 10 years subject to normal use and regular
maintenance from the date of manufacture and can be
replaced by opening the smoke alarm and accessing the
battery under the battery cover
¬Periodically apply the Test Procedure to test the alarm.
¬Smoke Alarm are prone to dust and insect ingress which can
cause false alarm, it is prudent to clean the smoke alarm
periodically. The Smoke Alarm must be kept clean so that
excess dust does not build up. Any insects or cobwebs in the
vicinity of the Smoke Alarm should be promptly removed.
Vacuum the outside of the Smoke Alarm to remove any dust
build up.
¬
Do not spray any cleaning liquids directly onto the smoke alarm.
Replace the battery
Audio and Visual Indication System Configuration
Trouble Shooting
Alarm Memory
Warranty Information
Maintenance
Test Procedures For Hardwired Interconnection
HUSH Mode
1. Ensure the green LED is continuously illuminated on each
unit, this indicates 240V mains AC power is available.
2.
Pressing and holding the test button on any smoke
alarm for at least 5 seconds will activate an alarm and
cause the red LED on the front face to flash.
(Note: all other interconnected smoke alarms will stop
alarming when releasing the Test button, but the red LED
will flash for 3 minutes.
3. Repeat this procedure for each alarm.
*Continuous alarm pattern: Beep 0.5s- Pause 0.5s- Beep
0.5s- Pause 0.5s-Beep 0.5s- Pause 1.5s repeatedly per ISO
8201 Smoke is detected, and the building must be vacated
immediately. Emergency services must be notified.
NOTE: If self-test fault warning is existing, but the product
can sound alarm when press the test button. The product can
continue to be used. Need to test weekly by press the test button
instead of self-test weekly.
Problem Solution
Green LED not lit Check mains power connection
Hard wire paired
smokes don't
alarm during test
Check if Smoke Alarms are in same
circuit, interconnect cable is corrected
firmly and mains power is connected.
Wireless
interconnected
smoke alarms
don't alarm
during test
Clean the wireless paired smoke alarm per
instruction and repair.
Alarms sound
for no apparent
reason
Check for fumes, steam, etc. from the
kitchen or bathroom. Paint and other
fumes can cause nuisance alarms. Check
for any sign of contamination such as
cobwebs or dust. Clean the alarm.
Press the local Hush button to silent the
Smoke Alarm triggered, identify the alarm
that triggered by the flashing red LED
(alarm will not silence if it does not have a
flashing red LED)
If cannot hush the smoke alarm, push
the button located on the side and open
the Smoke Alarm, take off the battery.
Contact Voltex.
Chirp every 40
seconds and
cannot hush
Check if battery has been installed firmly,
contact Voltex
Dust and insect
Contamination
Vacuum the outside of the Smoke Alarm
to remove any dust build up. Smoke Alarm
are prone to dust and insect ingress which
can cause false alarm, it is prudent to
clean the smoke alarm periodically.
OPERATION MODE RED LED STATUS SOUND
Power Up Flash
No beep for
no wireless
interconnection.
No beep for
hard wired
interconnection.
Beep once when
wireless module is
installed & paired.
Beep 3 times when
wireless module is
installed but NOT
paired.
Alarm functioning
correctly
(standby)
Low intensity
flash every 40
seconds
-
Low battery
warning
Flash every 40
seconds
One chirp every 40
seconds.
Press HUSH button
enter ‘Do Not
Disturb’ Mode for 10
hours.
Fault warning Flash every 40
second
One chirp every
40 seconds. Press
HUSH button enter
‘Do Not Disturb’
Mode for 10 hours.
Self-test fault
warning
Flashes twice
every 40
seconds
-
HUSH mode
Flash once every
8 seconds for 10
min
-
Do not Disturb
Flash once very
40 seconds for
10 hours
-
Smoke detected
on local alarm*
Flash every
second
Continuous alarm
signal pattern,
Press HUSH button
to enter Silent Mode
for 10 min
Smoke detected
on interconnected
or paired unit
-
Continuous alarm
signal pattern,
Press HUSH button
to enter Silent Mode
for 10 min
Test function Flash every
second
Continuous alarm
signal pattern
until TEST button
released
Weekly self-test Flash once Chirps once every
week
End of Life (10
year) Warning
Flashes twice
every 40
seconds
Chips every 40
seconds
Cannot enter ‘Do
Not Disturb’ Mode.
Voltex warrants this accessory against defective workmanship
and faulty materials for seven (7) years from the original date of
purchase.
In an interconnected group, only the LED on the triggered alarm
flashes once approximately every 20 seconds for 72 hours. This
can be used to identify the triggered unit.
© Voltex Electrical 2020. All Rights Reserved.
CONFIG 1
Hardwire Interconnect Only, 1 Circuit
CONFIG 2
Hardwire & Wireless Interconnect, 1 Circuit
CONFIG 3
Wireless Interconnect Only, 2 Circuits
NOT ALLOWED

In the event of an alarm condition, pressing the HUSH button
on the alarm unit will silence the alarm for approximately 10
minutes.
NOTE: Where multiple alarms are interconnected, the HUSH
function WILL NOT OPERATE EXCEPT ON THE UNIT THAT THE
ALARM WAS TRIGGERED FROM. The triggered unit can be
identified by the RED LED flashing.
Do Not Disturb Mode
When the unit indicates a low battery alarm or internal fault,
pushing the HUSH button will silence the alarm for 10 hours
and the red LED will flash every 40 seconds.
¬
The smoke alarm incorporates a replaceable battery
(CR17450) which is designed to power the smoke alarm
in the event of a short-term power outage. The battery is
designed to last 10 years subject to normal use and regular
maintenance from the date of manufacture and can be
replaced by opening the smoke alarm and accessing the
battery under the battery cover
¬Periodically apply the Test Procedure to test the alarm.
¬Smoke Alarm are prone to dust and insect ingress which can
cause false alarm, it is prudent to clean the smoke alarm
periodically. The Smoke Alarm must be kept clean so that
excess dust does not build up. Any insects or cobwebs in the
vicinity of the Smoke Alarm should be promptly removed.
Vacuum the outside of the Smoke Alarm to remove any dust
build up.
¬
Do not spray any cleaning liquids directly onto the smoke alarm.
Replace the battery
Audio and Visual Indication System Configuration
Trouble Shooting
Alarm Memory
Warranty Information
Maintenance
Test Procedures For Hardwired Interconnection
HUSH Mode
1. Ensure the green LED is continuously illuminated on each
unit, this indicates 240V mains AC power is available.
2.
Pressing and holding the test button on any smoke
alarm for at least 5 seconds will activate an alarm and
cause the red LED on the front face to flash.
(Note: all other interconnected smoke alarms will stop
alarming when releasing the Test button, but the red LED
will flash for 3 minutes.
3. Repeat this procedure for each alarm.
*Continuous alarm pattern: Beep 0.5s- Pause 0.5s- Beep
0.5s- Pause 0.5s-Beep 0.5s- Pause 1.5s repeatedly per ISO
8201 Smoke is detected, and the building must be vacated
immediately. Emergency services must be notified.
NOTE: If self-test fault warning is existing, but the product
can sound alarm when press the test button. The product can
continue to be used. Need to test weekly by press the test button
instead of self-test weekly.
Problem Solution
Green LED not lit Check mains power connection
Hard wire paired
smokes don't
alarm during test
Check if Smoke Alarms are in same
circuit, interconnect cable is corrected
firmly and mains power is connected.
Wireless
interconnected
smoke alarms
don't alarm
during test
Clean the wireless paired smoke alarm per
instruction and repair.
Alarms sound
for no apparent
reason
Check for fumes, steam, etc. from the
kitchen or bathroom. Paint and other
fumes can cause nuisance alarms. Check
for any sign of contamination such as
cobwebs or dust. Clean the alarm.
Press the local Hush button to silent the
Smoke Alarm triggered, identify the alarm
that triggered by the flashing red LED
(alarm will not silence if it does not have a
flashing red LED)
If cannot hush the smoke alarm, push
the button located on the side and open
the Smoke Alarm, take off the battery.
Contact Voltex.
Chirp every 40
seconds and
cannot hush
Check if battery has been installed firmly,
contact Voltex
Dust and insect
Contamination
Vacuum the outside of the Smoke Alarm
to remove any dust build up. Smoke Alarm
are prone to dust and insect ingress which
can cause false alarm, it is prudent to
clean the smoke alarm periodically.
OPERATION MODE RED LED STATUS SOUND
Power Up Flash
No beep for
no wireless
interconnection.
No beep for
hard wired
interconnection.
Beep once when
wireless module is
installed & paired.
Beep 3 times when
wireless module is
installed but NOT
paired.
Alarm functioning
correctly
(standby)
Low intensity
flash every 40
seconds
-
Low battery
warning
Flash every 40
seconds
One chirp every 40
seconds.
Press HUSH button
enter ‘Do Not
Disturb’ Mode for 10
hours.
Fault warning Flash every 40
second
One chirp every
40 seconds. Press
HUSH button enter
‘Do Not Disturb’
Mode for 10 hours.
Self-test fault
warning
Flashes twice
every 40
seconds
-
HUSH mode
Flash once every
8 seconds for 10
min
-
Do not Disturb
Flash once very
40 seconds for
10 hours
-
Smoke detected
on local alarm*
Flash every
second
Continuous alarm
signal pattern,
Press HUSH button
to enter Silent Mode
for 10 min
Smoke detected
on interconnected
or paired unit
-
Continuous alarm
signal pattern,
Press HUSH button
to enter Silent Mode
for 10 min
Test function Flash every
second
Continuous alarm
signal pattern
until TEST button
released
Weekly self-test Flash once Chirps once every
week
End of Life (10
year) Warning
Flashes twice
every 40
seconds
Chips every 40
seconds
Cannot enter ‘Do
Not Disturb’ Mode.
Voltex warrants this accessory against defective workmanship
and faulty materials for seven (7) years from the original date of
purchase.
In an interconnected group, only the LED on the triggered alarm
flashes once approximately every 20 seconds for 72 hours. This
can be used to identify the triggered unit.
© Voltex Electrical 2020. All Rights Reserved.
CONFIG 1
Hardwire Interconnect Only, 1 Circuit
CONFIG 2
Hardwire & Wireless Interconnect, 1 Circuit
CONFIG 3
Wireless Interconnect Only, 2 Circuits
NOT ALLOWED
Table of contents
Other Voltex Smoke Alarm manuals
Popular Smoke Alarm manuals by other brands

Sontay
Sontay SD-521 quick guide

Xtralis
Xtralis vesda LaserFOCUS VLF-500 Product guide

Meridian
Meridian WLS906 Instructions for installation and use

Siemens
Siemens Sinteso Cerberus PRO FDA221 manual

Siemens
Siemens DELTA reflex 5TC1 290 Operating and mounting instructions

FFE
FFE Fireray 5000 Technical notes

System Sensor
System Sensor 1012 Ionization Installation and maintenance instructions

First Alert
First Alert 9120BA user manual

Fire Fighting Enterprises
Fire Fighting Enterprises FIRERAY 2000 EExd installation guide

First Alert
First Alert SA340B Specifications

Trust
Trust ZSDR-850 user manual

Kidde
Kidde P4010LDCS-WCA user guide