VSAIL VI-6627 User manual

VSL2.909.026ASY V1.01
Features
 Addressable Smoke Detector
 Advanced embedded MCU
 Drift compensation makes it environment
adaptable
 360°visible LED driven by Control panel
 Manually addressing via a dedicated hand
held programmer
 Designed to comply with EN 54-7
Description
VI-6627 Digital smoke detector can compensate the variation of environmental parameters and judge fire alarms
through algorithm fixed inside the excellent MCU,and send current operating state ,smoke concentration,environment
parameter etc.to control panel via digital signals transmission.With the pleasing appearance,it is easy to install and
maintain.The detector is suitable for hotels, restaurants, computer rooms, banks, malls, warehouses, libraries,
museums, offices and places with heavy moistures among the air. Besides, it is also applicable for places where black
smokes occurred when there is fire.
Technical data
Operating Voltage: 16-28V(Modulated-pulse)
Standby Current: ≤0.5mA
Alarm Current: ≤1.0 mA
Wiring Two-wire(non-polarized)
Temperature range: -10℃~50℃
Humidity: ≤95%RH, (40±2℃)No condensation
LED Alarm Indication: Red light emitting
LED Standby Indication: Red light flashing
LED Fault Indication: light is off
IP Rating: 32
Installation
 Dimensions:Showing on Fig.1
Fig.1 Dimensions
Installation and Operation Manual
V1.01
VI-6627 Digital Smoke Detector
Beijing VSAIL Fire Protection Equipment Co. Ltd.
Building 32, Huilongsen Technology Park,
No.99 14th Kechuang Street, BDA, Beijing, PRC
Common Base
VB
-
6617
Detector
VI-6627
VSL2.909.026ASY V1.01
 Mounting:
Warning: Please disconnect the loop power in order to avoid control panel broken by short circuit when
mounting Common Base.
Detector Head Mounting showing in Fig.2
Fig.2 Mounting
 Mounting Step
1.Install the Common Base into Back Box which had installed in the wall by using screw.( Back box is standard
86H50 box)Make sure the Common Base installed stable.
2.Connect the loop to Common Base Terminal 1,2.
3.Inastall the detector head on to Common Base and direct Alignment Mark to Mounting Mark at same time.
4.Turn Alignment Mark aim to Locking Mark finish the installation.
Wiring Details
1. Wiring Requirement:RVS-2*1.0 mm2 or1.5 mm2 wire for BUS, laid through metal tube (cable sink) or PVC tube.
2.1,2 Should connecting with fire alarm system detection loop(Non-polarized)
3.Loop wiring is shown in Fig.3
Fig.3. Loop wiring
Address setting
1.VI-6537 Digital Programmer is used to write an address of the Detector.Connecting Progarmmer with loop
terminals:1,2 of the Detector before it installation .
2.Set address ,Pressing Write key, the address will be shown on the numeric display if successful. It is fail if there
is no address. Please refer to VI-6537 Digital Programmer Manual for details.
3.Address range should be within 0-255. The address is unique in a loop.
Back Box
Alignment Mark
Mounting Mark
Locking Mark
L+
L-
Loop(Non-polarized)
VSL2.909.026ASY V1.01
Mode setting
Sensitivity Mode dB/m Application Environment
0 0.109 Clean Room
1 0.136 Hotel Room,Small Flat;
2 0.164 Office,Long Corridor
3 0.192 Ware House,Car Park
 Factory Setting:Sensitivity Mode 1
 The VI-6627 sensitivity mode can be set by Control Panel,please refer to the corresponding Manual for
details.
Testing
Warning:Power is switched off before all devices are installed completely.
The detector must be tested after installation or regular maintenance.
 Registration: The fire alarm control panel will registers the detector on line to check if the address of the
detectors mounted is the same address as that registered in the control panel.
 Fire condition: After registration, make detector under fire conditions by using Smoke generator to test
whether the detector alarms normally and control panel displays its registered address.
 Reset:After testing, reset the detector through control panel.
Fault Finding
Detector Fault on
Control Panel
Check wiring of Common base , no water no short-circuit and open circuit.
Chenk the connection between detector and common base.
Nuisance alarm The detector alarm frequently but there is no Fire and other unusual, then check whether
the chamber in the detector is too dirty and needs to be cleaned
Otherwise, the circuit may be broken.
Address Fault Address is set incorrectly,Reset by VI-6537 Digital Programmer.
Cautions
 Dust cover on the detector shouldn’t be removed between installation and acceptance test to avoid
contamination.
 If the detector gives fault warning after a long operation, first check if the chamber in detector are too dirty, or
the position is changed. At last, other faults should be considered.
 Fire alarm test requirement as specified in the applicable local codes,We suggest to test every 6 month.
 Please put on the dust cover if the room is decorated or wall-painted to avoid contamination.
Limited Warranty
VSAIL warrants that the product will be free of charge for repairing or replacing from defects in design, materials
and workmanship during the warranty period. This warranty doesn’t cover any product that is found to have been
improperly installed or used in any way not in accordance with the instructions supplied with the product. Anybody,
including the agents, distributors or employees, is not in the position to amend the contents of this warranty.
Please contact your local distributor for products not covered by this warranty.

Other VSAIL Security Sensor manuals

VSAIL VI-6631 User manual

VSAIL

VSAIL VI-6631 User manual

VSAIL VI-6647 User manual

VSAIL

VSAIL VI-6647 User manual

VSAIL VI-6637 User manual

VSAIL

VSAIL VI-6637 User manual

Popular Security Sensor manuals by other brands

Honeywell Satronic IRD 1010 manual

Honeywell

Honeywell Satronic IRD 1010 manual

Ecolink WST-302 manual

Ecolink

Ecolink WST-302 manual

ESYLUX EP10427404 operating instructions

ESYLUX

ESYLUX EP10427404 operating instructions

iRay Technology Luna1012X user manual

iRay Technology

iRay Technology Luna1012X user manual

Bosch D-tect 120 Professional instructions

Bosch

Bosch D-tect 120 Professional instructions

SICK deTem2 Core Mounting instructions

SICK

SICK deTem2 Core Mounting instructions

Honeywell SC100 installation guide

Honeywell

Honeywell SC100 installation guide

Niko 350-20061 manual

Niko

Niko 350-20061 manual

ITALIANA SENSORI 8032-ISR023 Installation, operation and maintenance manual

ITALIANA SENSORI

ITALIANA SENSORI 8032-ISR023 Installation, operation and maintenance manual

GJD D-TECT R Ricochet GJD830R manual

GJD

GJD D-TECT R Ricochet GJD830R manual

FootfallCam SpaceSense installation guide

FootfallCam

FootfallCam SpaceSense installation guide

EMX Industries IRB-MON2 instruction manual

EMX Industries

EMX Industries IRB-MON2 instruction manual

Roaring Forties SMA2751 owner's manual

Roaring Forties

Roaring Forties SMA2751 owner's manual

STEINEL IS 3360 COM1 Information manual

STEINEL

STEINEL IS 3360 COM1 Information manual

VIDICON PIR CRT installation manual

VIDICON

VIDICON PIR CRT installation manual

daviteq AV10-G4-NH3 manual

daviteq

daviteq AV10-G4-NH3 manual

Linde G-TECTA4GP operating manual

Linde

Linde G-TECTA4GP operating manual

DMP Electronics 1128 installation guide

DMP Electronics

DMP Electronics 1128 installation guide

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.