manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. VSAIL
  6. •
  7. Security Sensor
  8. •
  9. VSAIL VI-6637 User manual

VSAIL VI-6637 User manual

VSL2.909.025ASY V1.03
Features
Addressable Heat Detector
Advanced embedded MCU
360°visible LED driven by Control panel
Manually addressing via a dedicated hand
held programmer.
Two Response Modes:A1R/A2
Designed to comply with EN 54-5
Description
The detector has pleasing appearance and is easy to install and maintain. It is suitable for the environment without
smoke but a lot of dust or the places where smoke and vapor stay such as indoor parking, kitchen, boiler room, tea
stove room, generator room and drying workshop.
Technical data
Operating Voltage: 16-28V(Modulated-pulse)
Standby Current: ≤0.5mA
Alarm Current: ≤1.0 mA
Wiring Two-wire(non-polarized)
Signal Transmission distance: ≤2000m
Detector Classification A1R or A2
Temperature range: -10℃~50℃
Humidity: ≤95%RH, (40±2℃)No condensation
LED Alarm Indication: Red light emitting
LED Polling Indication: Red light flashing
IP Rating: 32
Installation
Dimensions:Showing on Fig.1
Fig.1 Dimensions
Installation
and
Operation
Manual
V1.03
VI-6637 Digital Heat Detector
Beijing VSAIL Fire Protection Equipment Co. Ltd.
Building 32, Huilongsen Technology Park,
No.99 14th Kechuang Street, BDA, Beijing, PRC
Common Base
VB-6617
Detector
VI-6637
VSL2.909.025ASY V1.03
Mounting:
Warning: Please disconnect the loop power in order to avoid control panel broken by short circuit when
mounting Common Base.
Detector Head Mounting showing in Fig.2
Fig.2
Mounting Step
1. Install the Common Base into Back Box which had installed in the wall by using screw.( Back box is standard
86H50 box)Make sure the Common Base installed stable.
2. Connect the loop to Common Base Terminal 1,2.
3. Inastall the detector head on to Common Base and direct Alignment Mark to Mounting Mark at same time.
4. Turn Alignment Mark aim to Locking Mark finishes the installation.
Wiring Details
1. Wiring Requirement: RVS-2*1.0 mm2 or1.5 mm2 wire for BUS, laid through metal tube (cable sink) or PVC tube.
2. L1, L2 should connecting with fire alarm system detection loop (Non-polarized)
3.Loop wiring is shown in Fig.3
Fig.3. Loop wiring
Address setting
1. VI-6537 Digital Programmer is used to write an address of the Detector. Connecting Programmer with loop
terminals: 1, 2 of the Detector before it installation.
2. Set address, Pressing Write key, the address will be shown on the numeric display if successful. It is fail if there
is no address. Please refer to VI-6537 Digital Programmer Manual for details.
3.Address range should be within 0-255. The address is unique in a loop.
Back Box
Alignment Mark
Mounting Mark
Locking Mark
Loop(Non-polarized)
L+
L-
VSL2.909.025ASY V1.03
Mode setting
Mode Class Application Temperature Static Response Temperature
Typical Maximum Min Max
1 A1R 25 50 54 65
2 A2 25 50 54 70
Mode 1 is Factory Setting.
The letter “R” suffix mean that the detector class incorporate a rate-of-rise characteristic. It will give rapid
response even when high rates of rise of air temperature starting at air temperatures substantially below the
typical application temperature.
The VI-6627 sensitivity mode can be set by Control Panel, please refer to the corresponding Manual for
details.
Testing
Warning:Power is switched on after all devices are installed completely.
The detector must be tested after installation or regular maintenance.
Registration: The fire alarm control panel will registers the detector on line to check if the address of the
detectors mounted is the same address as that registered in the control panel.
Fire condition: After registration, make detector under fire conditions by using hot air generator to test
whether the detector alarms normally and control panel displays its registered address.
Reset:After testing, reset the detector through control panel.
Fault Finding
Detector Fault on Control Panel Check wiring of Common base, no water no short-circuits and open circuit.
Check the connection between detector and common base.
Nuisance alarm The detector still in alarm status if there is no Fire and other unusual,means it
damaged.
Address Fault Address is set incorrectly, Reset by VI-6537 Digital Programmer.
Cautions
1. Dust cover on the detector shouldn’t be removed between installation and acceptance test to avoid
contamination.
2. If the detector gives fault warning after a long operation, first check if the detector are damaged, or the position
is changed. At last, other faults should be considered
3. Fire alarm test requirement as specified in the applicable local codes, we suggest to test every 6 month.
Please put on the dust cover if the room is decorated or wall-painted to avoid contamination.
Limited Warranty
VSAIL warrants that the product will be free of charge for repairing or replacing from defects in design, materials
and workmanship during the warranty period. This warranty doesn’t cover any product that is found to have been
improperly installed or used in any way not in accordance with the instructions supplied with the product. Anybody,
including the agents, distributors or employees, is not in the position to amend the contents of this warranty.
Please contact your local distributor for products not covered by this warranty.

Other VSAIL Security Sensor manuals

VSAIL VI-6627 User manual

VSAIL

VSAIL VI-6627 User manual

VSAIL VI-6631 User manual

VSAIL

VSAIL VI-6631 User manual

VSAIL VI-6647 User manual

VSAIL

VSAIL VI-6647 User manual

Popular Security Sensor manuals by other brands

Theben SPHINX 331 S KNX quick start guide

Theben

Theben SPHINX 331 S KNX quick start guide

Pilz PSEN ml sa 1.1 operating manual

Pilz

Pilz PSEN ml sa 1.1 operating manual

Berkeley Varitronics Systems PocketHound user guide

Berkeley Varitronics Systems

Berkeley Varitronics Systems PocketHound user guide

Pentatech MA80P v.2 owner's manual

Pentatech

Pentatech MA80P v.2 owner's manual

SICK Prime KTX-WN91141252ZZZZ manual

SICK

SICK Prime KTX-WN91141252ZZZZ manual

merten INSTABUS ARGUS 220 Connect manual

merten

merten INSTABUS ARGUS 220 Connect manual

Zircon Leak Alert + LED! user manual

Zircon

Zircon Leak Alert + LED! user manual

Eaton MPAD-C-A Product guide

Eaton

Eaton MPAD-C-A Product guide

CropX V02 installation guide

CropX

CropX V02 installation guide

EVERSPRING ST802 installation instructions

EVERSPRING

EVERSPRING ST802 installation instructions

Orno OR-CR-267 Service manual

Orno

Orno OR-CR-267 Service manual

AVS Electronics WIC 4 manual

AVS Electronics

AVS Electronics WIC 4 manual

GE 869 instruction manual

GE

GE 869 instruction manual

Endress+Hauser Liquiphant S FTL70 operating instructions

Endress+Hauser

Endress+Hauser Liquiphant S FTL70 operating instructions

hager EE 810 Setup instructions

hager

hager EE 810 Setup instructions

MUNBYN IMC02 user manual

MUNBYN

MUNBYN IMC02 user manual

GTV CM6 quick start guide

GTV

GTV CM6 quick start guide

SGB DLR-G Documentation

SGB

SGB DLR-G Documentation

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.