VSI 1000-X Series User manual

Other manuals for 1000-X Series

2

This manual suits for next models

1

Other VSI Control Unit manuals

VSI AWWA C504 User manual

VSI

VSI AWWA C504 User manual

VSI AWWA C508 Series Installation and operating instructions

VSI

VSI AWWA C508 Series Installation and operating instructions

VSI SF-PB User manual

VSI

VSI SF-PB User manual

VSI 2100 Series User manual

VSI

VSI 2100 Series User manual

VSI 9000 Series User manual

VSI

VSI 9000 Series User manual

Popular Control Unit manuals by other brands

Seitz 14A80 user manual

Seitz

Seitz 14A80 user manual

Wilo RS485 Installation and operating instructions

Wilo

Wilo RS485 Installation and operating instructions

Becker CentralControl CC41 Commissioning Instruction

Becker

Becker CentralControl CC41 Commissioning Instruction

SICK CDB650 operating instructions

SICK

SICK CDB650 operating instructions

Panduit NetKey NKP5E88M Series installation instructions

Panduit

Panduit NetKey NKP5E88M Series installation instructions

MX Options Concentric Petite Fitting instructions

MX

MX Options Concentric Petite Fitting instructions

Clean Water Systems Fleck 2510 Installation & start?up guide

Clean Water Systems

Clean Water Systems Fleck 2510 Installation & start?up guide

Fairchild FSB44104A user guide

Fairchild

Fairchild FSB44104A user guide

LEGRAND Wattstopper LMIN-104 installation instructions

LEGRAND

LEGRAND Wattstopper LMIN-104 installation instructions

PMK ATT10BNCS instruction manual

PMK

PMK ATT10BNCS instruction manual

Tektronix TDS3FFT user manual

Tektronix

Tektronix TDS3FFT user manual

Woodward easYgen Technical manual

Woodward

Woodward easYgen Technical manual

Balluff BNI EIP-502-105-R015 user guide

Balluff

Balluff BNI EIP-502-105-R015 user guide

NXP Semiconductors TWR-LS1021A Getting started

NXP Semiconductors

NXP Semiconductors TWR-LS1021A Getting started

Advantech PCM-3117 Startup manual

Advantech

Advantech PCM-3117 Startup manual

Danfoss MCO 101 manual

Danfoss

Danfoss MCO 101 manual

Moons' Lin Engineering R701P user manual

Moons'

Moons' Lin Engineering R701P user manual

Aventics RV1 operating instructions

Aventics

Aventics RV1 operating instructions

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.

SF-LB QUICK SETUP GUIDE
The SF-LB control pack, if shipped together with a Series 1000-X actuator, is factory calibrated and
set for 90° rotation and no adjustment should be needed. However, if you are replacing the SF-LB
or the factory settings do not conform to your actuator/valve application, some adjustment may be
necessary.
INITIAL SETUP
If the SF-LB is not installed – install in the actuator by plugging in the two cables into the unit. Con-
nect the appropriate power to terminals 1&2. Connect the control signal to terminals 3&4 and note
that the polarity must be positive and negative.
If feedback is being used connect the wiring to terminals 5&6. The SF-LB provides position feedback
of 4-20mA.
At this point the Green LED “L1” should be illuminated. If red LED “L2” is illuminated then the control
signal is faulty or SC is not set correctly for your control signal. Ensure that SC is set for your applica-
tion control signal (2-10V or 4-20mA). See the chart below for failure mode conditions on the SF-LB
control pack. Your actuator should be ready to operate.
SF-LB CONTROL PACK LED’S
LED CAUSE DESCRIPTION REMEDY
LED-1 (GREEN) POWER IS PRESENT ON INPUT TERMINALS ALL IS NORMAL - NONE NEEDED
LED-2 (RED) CONTROL SIGNAL IS WRONG OR NOT PRESENT CHECK SC SWITCH TO ENSURE PROPER CONTROL
SIGNAL IS SELECTED - CHECK TO ENSURE SIGNAL IS
PRESENT
LED-3 (RED) POTENTIOMETER IS NOT CALIBRATED WITH ACTUATOR
OUTPUT
RE-CALIBRATE POTENTIOMETER PROCEDURE IN IOM
(CALL FOR ASSISTANCE)
LED-4 (RED) OVERTORQUE CONDITION PRESENT - VALVE BINDING,
OR MANUAL OVERRIDE HAS BEEN USED AND
ACTUATOR IS OUT OF SYNC WITH CONTROLLER
CHECK TO MAKE SURE VALVE IS NOT BINDING. RESET
CONTROL PACK BY ROTATING S-A FROM 1 TO 2 AND
BACK TO 1, or REMOVE POWER TO THE ACTUATOR AND
REPLACE
NOTE: THE ACTUATOR WILL NOT OPERATE WHEN MANUAL OVERRIDE PUSH BUTTON IS DEPRESSED
FIGURE A FIGURE B FIGURE C
LED 1
LED 2
LED 3
LED 4
SC
OPEN
SHUT
SET
SA SB DB
POWER CTRL
FEED
BACK
++ + -- -
SF-LB QUICK SETUP GUIDE
MANUAL OVERRIDE PUSH BUTTON
The Series 1000-X units are equipped with a manual override power button which disconnects
the power to the actuator motor so that the unit can be rotated using the provided hand crank or
the optional hand wheel. Although SF-LB LED’s are operating, the motor power is disconnected
internally. If manual operation of unit is performed, the unit will need to be re-set by switching SA
from 1 to 2 and back to 1 again.
SWITCH SETTINGS
SA is used for setting the “direct acting” (2V=closed and 10V=open) or “reverse acting “(2V=open and
10V=closed) rotation of the actuator. SA is also used for placing the actuator in “set mode”. Set mode
is used to stroke the actuator using the “open” and “shut” buttons and used for setting the stoke limit
position of the actuator. SB is used for setting the positioning of the actuator in the case of a control
signal loss. Figure C shows the side of the controller with the options using SA and SB. Actuators
are shipped with the SF-LB control packs set to “direct acting” and fail “in place”. SC is used for
selecting the control signal (2-10V or 4-20mA). DB is used for setting the sensitivity on the “dead
band” – rotate clockwise for less sensitive, rotate CCW for more sensitive. Units are set to mid-range
sensitivity from factory.
SETTING THE POSITION LIMITS
NOTE: ACTUATOR IS EQUIPPED WITH MECHANICAL STOPS. THESE ARE FOR SAFETY ONLY AND
SHOULD NOT BE USED TO SET THE POSITION LIMITS ON THE ACTUATOR.
Position limits are factory set to 90° rotation. If desired, the position limits can be re-configured to
rotate less than 90°. To re-set the position limits of the unit, SA should be placed in “set mode”
by switching to “2”. At this point, the open and shut buttons can be used to stroke the actuator to
the desired position. To set the closed limit, make sure the control signal is applied with the proper
setting. For example – 2V is need for closed. Rotate the valve to the closed position. While holding
the white “set button” also press the “shut” (middle) button and hold until the LED flashes – then
release both buttons. This sets the closed limit. To set the open limit, rotate the actuator to the
open position using the “open” (top) push button. Place 10V control signal on input. While holding
the white “set button”, press and hold the “open” button until the LED flashes – then release both
buttons. This sets the open limit. Finally, switch SA back to 1 or 3 depending on the operation of the
unit (1 is direct acting and 3 is reverse acting).
For the complete IOM on the Series 1000-X actuators, please visit www.valvesolutions.com or if
technical support is needed during setup or troubleshooting, please call 770-740-0800.
FIGURE D